Page 2 - Battery Installation and Replacement; Figure 1. 5808W3 Wireless Smoke/Heat Detector; Programming; NOTE; Mounting; A GOOD TRANSMISSION PATH MUST BE; Figure 2. Detector Mounting Base

- 2 - Battery Installation and Replacement To replace the battery: 1. Remove the detector from its mounting base by twisting the detector counterclockwise. Remove the battery, and dispose properly. 2. To ensure proper power-down sequence, wait a minimum of 20 seconds before installing new battery. 3...

Page 3 - Figure 4. Recessed Test Switch Opening and SENS-RDR Position; Testing Signal Strength; NOTE: Remove battery tab before installation.; Testing Programmed Loops

- 3 - Dust covers are an effective way to limit the entry of dust into the smoke detector sensing chamber during construction. However, they may not completely prevent airborne dust particles from entering the detector. Therefore, it is recommended that the detectors be removed before beginning cons...

Page 4 - Maintenance; Figure 5. Removing Screen/Sensing Chamber; Specifications; Please refer to insert for the Limitations of Fire Alarm Systems.; D100-100-00 I56-2768-001R

Maintenance NOTE: Before performing maintenance on the detector, notify the proper authorities and the central station that maintenance is being performed and the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent any unwanted alarms. Power must b...