Page 2 - Check that the delivery corresponds to your order, see Chapter 3.
AT LEAST THE 11 FOLLOWING STEPS OF THE START-UP QUICK GUIDE MUST BE PERFORMED DURING THE INSTALLATION AND COMMISSIONING. IF ANY PROBLEMS OCCUR, PLEASE CONTACT YOUR LOCAL DISTRIBUTOR. Start-up Quick Guide 1. Check that the delivery corresponds to your order, see Chapter 3. 2. Before taking any commis...
Page 3 - CONTENTS; Programming Manual for NXL HVAC drives
CONTENTS NXL HVAC & COMPACT USER’S MANUAL INDEX 1 SAFETY 2 EU DIRECTIVE 3 RECEIPT OF DELIVERY 4 TECHNICAL DATA 5 INSTALLATION 6 CABLING AND CONNECTIONS 7 CONTROL KEYPAD 8 COMMISSIONING 9 FAULT TRACING 10 DESCRIPTION OF BOARD NXLOPTAA 11 DESCRIPTION OF BOARD NXLOPTAI 12 NXL HVAC BASIC SPEED CONTR...
Page 5 - Index
Honeywell Honeywell Honeywell Honeywell Index 5(96) NXL HVAC & COMPACT User's Manual Index Date: 28.10.2008 1. SAFETY .................................................................................................................................. 7 1.1 Warnings ...................................
Page 6 - HVAC parameters in NXL HVAC (Control keypad: Menu P2
6(96) Index 6.2.5 Control terminal signals .................................................................................................. 46 6.2.5.1 Jumper selections on NXL basic board....................................................................... 47 6.2.6 Motor thermistor (PTC) connect...
Page 7 - SAFETY
Honeywell Honeywell Honeywell Safety 7(96) 1 1. SAFETY 1.1 Warnings 1 The components of the power unit of the frequency converter are live when NXL is connected to mains potential. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury. The control unit is ...
Page 8 - Safety; Honeywell; Earthing and earth fault protection; Warning symbols; General warning; Hot surface – Risk of burn; MOTOR RUN CHECK LIST
8(96) Safety Honeywell Honeywell Honeywell Honeywell 1 1.3 Earthing and earth fault protection The Honeywell NXL frequency converter must always be earthed with an earthing conductor connected to the earthing terminal . The earth fault protection inside the frequency converter protects only the conv...
Page 9 - EU DIRECTIVE; NXL frequency converter EMC classification
EU Directive 9(96) 2 2. EU DIRECTIVE 2.1 CE marking The CE marking on the product guarantees the free movement of the product within the EEA (European Economic Area). It also guarantees that the product meets the various requirements placed upon it (such as the EMC Directive and possibly other direc...
Page 10 - EU Directive; NX EMC levels
10(96) EU Directive Honeywell Honeywell Honeywell Honeywell 2 All NX frequency converters fulfil all EMC immunity requirements (standards EN 61000-6-1, 61000-6-2 and EN 61800-3). 2.2.4 Honeywell EMC classes and market requirements NX EMC levels Hospital Airport Residential Area Commercial Light Indu...
Page 11 - EU DECLARATION OF CONFORMITY
EU Directive 11(96) 2 EU DECLARATION OF CONFORMITY We Manufacturer's name: Vacon Oyj Manufacturer's address: P.O.Box 25 Runsorintie 7 FIN-65381 Vaasa Finland hereby declare that the product Product name: NXL Frequency Converter Model designation: NXL 0001 V3 5…to 0061 V3 5… NXL 0002 V3 2...to 0006 V...
Page 13 - Receipt of delivery; RECEIPT OF DELIVERY; Type designation code NXL Compact; NXL
Receipt of delivery 13(96) 3 3. RECEIPT OF DELIVERY NXL frequency converters have undergone scrupulous tests and quality checks at the factory before they are delivered to the customer. However, after unpacking the product, check that no signs of transport damages are to be found on the product and ...
Page 14 - Type designation code NXL HVAC; HVAC; Storage; Storing temperature; Maintenance
14(96) Receipt of delivery Honeywell Honeywell Honeywell Honeywell 3 3.2 Type designation code NXL HVAC HVAC 03 C 2 Enclosure & EMC classification 2 = IP21, EMC class H (fulfils EN 61800-3 cat C2, EN 55011 class A) 5 = IP54, EMC class C (fullfils EN 61800-3 cat C1, EN 55011 class B) Control keyp...
Page 16 - Technical data; TECHNICAL DATA; Introduction
16(96) Technical data Honeywell Honeywell Honeywell Honeywell 4 4. TECHNICAL DATA 4.1 Introduction Honeywell NXL is a compact frequency converter with the output ranging from 250 W to 30 kW. The Motor and Application Control Block is based on microprocessor software. The microprocessor controls the ...
Page 19 - Low; EM
Technical data 19(96) 4 4.2.1 NXL HVAC – Mains voltage 380 – 500 V Mains voltage 380-500 V, 50/60 Hz, 3~ Series NXL HVAC Loadability Motor shaft power Low High 400V supply 500V supply Frequency converter type Rated con- tinuous current I L (A) 10% over- load current (A) Rated con- tinuous current I ...
Page 21 - Technical
Technical data 21(96) 4 Immunity Complies with EN50082-1, -2, EN61800-3 EMC Emissions MF2-MF3: EMC level N; With an external RFI filter (option) attached EMC-level H (see Ch. 6.1.2.2) MF4-MF6: IP21 : EMC-level H: EN 61800-3 (2004) Cat C2, EN 55011 Class A IP54 : EMC level C: EN 61800-3 (2004) Cat C1...
Page 22 - Installation; INSTALLATION; Mounting; The NXL type MF2 is mounted with two screws using the; middle; holes of the mounting plates. If an; two; and bigger types are always mounted with; four; MF2 without a filter
22(96) Installation Honeywell Honeywell Honeywell Honeywell 5 5. INSTALLATION 5.1 Mounting 5.1.1 NXL Compact (MF2 and MF3) There are two possible positions in the wall mounting for the frames MF2 and MF3 (see Figure 5-1) The NXL type MF2 is mounted with two screws using the middle holes of the mount...
Page 23 - Type
Installation 23(96) 5 Figure 5-3. NXL Compact dimensions, MF2 Table 5-1. Dimensions of NXL, MF2 Dimensions (mm) Type W1 W2 H1 H2 H3 H4 H5 H6 H7 H8 D1 D2 ∅ MF2 30 60 172 152 140 130 80 42 11 6 150 144 6 W1 Ø H2 H3 H8 H5 D1 D2 H1 H4 H6 H7 W2 nxlk7.fh8
Page 25 - Dimensions
Installation 25(96) 5 5.1.2 NXL HVAC (MF4 – MF6) The frequency converter shall be fixed with four screws (or bolts, depending on the unit size). Enough space shall be reserved around the frequency converter in order to ensure a sufficient cooling, see Table 5-4 and Figure 5-6. Also see to that the m...
Page 26 - Cooling; = distance from one frequency converter to another or
26(96) Installation Honeywell Honeywell Honeywell Honeywell 5 C A NK5_2 D B A B 5.2 Cooling Forced air flow cooling is used for NXL HVAC and NXL Compact size MF3. Enough free space shall be left above and below the frequency converter to ensure sufficient air circulation and cooling. You will find t...
Page 27 - to; class T; with a simple procedure presented in the figures below.
Installation 27(96) 5 5.3 Changing EMC protection class from H/C to T in NXL HVAC The EMC protection class of NXL HVAC frequency converter types can be changed from class H/C to class T with a simple procedure presented in the figures below. Figure 5-7. Changing of EMC protection class, MF4 (left) a...
Page 28 - Cabling and connections; CABLING AND CONNECTIONS; Power connections
28(96) Cabling and connections Honeywell Honeywell Honeywell Honeywell 6 6. CABLING AND CONNECTIONS 6.1 Power connections Figure 6-1. Power connections, MF2 Figure 6-2. Power connections, NXL Compact MF3 (1~/3~) Figure 6-3. Power connections, NXL HVAC (MF4-MF6) nxlk10.fh8 L1 L2 U/T1 V/T2 W/T3 L1 L2 ...
Page 29 - Level C
Honeywell Honeywell Honeywell Cabling and connections 29(96) 6 6.1.1 Cabling Use cables with heat resistance of at least +70 ° C. The cables and the fuses must be dimensioned according to the tables below. Installation of cables according to UL regulations is presented in Chapter 6.1.4. The fuses fu...
Page 30 - PVC isolated; cable where there
30(96) Cabling and connections Honeywell Honeywell Honeywell Honeywell 6 6.1.1.1 Cable and fuse sizes Terminal cable size (min/max) Frame Type I L [A] Fuse [A] Mains cable Cu [mm 2 ] Main terminal [mm 2 ] Earth terminal [mm 2 ] Control terminal [mm 2 ] Relay terminal [mm 2 ] MF2 NXL0002 2 10 2*1.5+1...
Page 31 - includes all; Mounting procedure; Figure 1; Remove the cable cover. Observe the places for; Figure 2
Cabling and connections 31(96) 6 6.1.2 Mounting of cable accessories Enclosed to your NXL frequency converter you have received a plastic bag containing components that are needed for the installation of the mains and motor cables in the frequency converter. Figure 6-4. Cable accessories Components:...
Page 32 - Figure 5; Close the cover of the frequency converter.
32(96) Cabling and connections Honeywell Honeywell Honeywell Honeywell 6 5. Place the rubber grommets in the openings as shown in Figure 5 . 6. Fix the cable entry gland to the frame of the frequency converter with the five M4x10 screws ( Figure 6 ). Close the cover of the frequency converter.
Page 33 - Di sta nce
Cabling and connections 33(96) 6 6.1.3 Installation instructions 1 Before starting the installation, check that none of the components of the frequency converter is live. 2 The NXL frequency converter types MF2 and MF3 shall be installed inside switchgear, separate cubicle or electrical room because...
Page 34 - Frame; M AIN S; Earth
34(96) Cabling and connections Honeywell Honeywell Honeywell Honeywell 6 6.1.3.1 Stripping lengths of motor and mains cables Figure 6-5.Stripping of cables Frame A1 B1 C1 D1 A2 B2 C2 D2 MF2 7 35 7 20 7 50 7 35 MF3 7 40 7 30 7 60 7 40 MF4 15 35 10 20 7 50 7 35 MF5 20 40 10 30 20 60 10 40 MF6 20 90 15...
Page 35 - Installation of cables to NXL; Earth terminal
Cabling and connections 35(96) 6 6.1.3.2 Installation of cables to NXL Note: In case you want to connect an external brake resistor (MF3 and bigger sizes), see separate Brake Resistor Manual. Figure 6-6. NXL Compact, MF2 Figure 6-7. Cable installation in NXL Compact, MF2 (500V, 3-phase) Earth termin...
Page 37 - Installation of an external RFI filter to NXL Compact (MF2-3); PE
Cabling and connections 37(96) 6 Installation of an external RFI filter to NXL Compact (MF2-3) The EMC protection class of NXL Compact frequency converters MF2 and MF3 can be changed from N to H with an optional external RFI filter. Install the power cables in terminals L1, L2 and L3 and the groundi...
Page 38 - RFI Filter type; Table 6-5. RFI filter types and their dimensions
38(96) Cabling and connections Honeywell Honeywell Honeywell Honeywell 6 RFI Filter type Input voltage Dimensions WxHxD (mm) NXLRFIV35 380-500V 3~ 60x252x35 NXLRFIV12 208-240V 1~ 60x252x35 Table 6-5. RFI filter types and their dimensions
Page 39 - Earth terminals; DC terminals
Cabling and connections 39(96) 6 Figure 6-13. NXL HVAC (03-12), MF4 Figure 6-14. Cable installation in NXL HVAC (03-12), MF4 Earth terminals Mains cable Motor cable Brake resistor terminals DC terminals
Page 42 - Table 6-6. Tightening torques of terminals; Cable and motor insulation checks
42(96) Cabling and connections Honeywell Honeywell Honeywell Honeywell 6 6.1.4 Cable installation and the UL standards To meet the UL (Underwriters Laboratories) regulations, a UL-approved copper cable with a minimum heat-resistance of +60/75 ° C must be used. The tightening torques of the terminals...
Page 43 - slot connector; Figure 6-19. Option board slots D and E in frames MF4 – MF6; Allowed option boards in NXL HVAC:; SLOT D; CI; SLOT E; AA; AI; C8 CI
Cabling and connections 43(96) 6 6.2 Control unit 6.2.1 NXL Compact (MF2 – MF3) The control unit of the NXL frequency converter is integrated with the power unit and consists roughly of the control board and one optional board , which can be connected to the slot connector of the control board. 6.2....
Page 45 - NXL HVAC; or
Cabling and connections 45(96) 6 6.2.4 Control I/O Terminal Signal Description 1 +10V ref Reference output Voltage for potentiometer, etc. 2 AI1+ Analogue input, voltage range 0—10V DC. Voltage input frequency reference 3 AI1- I/O Ground Ground for reference and controls 4 AI2+ 5 AI2- /GND Analogue ...
Page 46 - Terminal; additional inputs terminal signals defined in
46(96) Cabling and connections Honeywell Honeywell Honeywell Honeywell 6 6.2.5 Control terminal signals Terminal Signal Technical information 1 +10 Vref Reference voltage Maximum current 10 mA 2 AI1+ Analogue input, voltage (MF4 and bigger: voltage or current) MF2-MF3: Voltage input MF4-MF6 Selectio...
Page 47 - Jumper selections on NXL basic board; Jum p e r b lo ck X 4 in; Jum p er b lo ck; Termination resistor RS 4 8 5 is in use
Cabling and connections 47(96) 6 6.2.5.1 Jumper selections on NXL basic board The user is able to customise the functions of the frequency converter to better suit his needs by selecting certain positions for the jumpers on the NXL board. The positions of the jumpers determine the signal type of ana...
Page 49 - Jumper block X4
Cabling and connections 49(96) 6 Figure 6-24. The location of jumper blocks in MF2 (left) and MF3 (right) Figure 6-25. The location of jumper blocks in the control board of NXL HVAC Jumper block X4 Jumper block X4 Jumper block X7 X9 X13 X8
Page 50 - External PTC Resistor; must be; followed otherwise a
50(96) Cabling and connections Honeywell Honeywell Honeywell Honeywell 6 6.2.6 Motor thermistor (PTC) connection There are three possibilities to connect a PTC resistor to NXL: 1. With optional board NXLOPTAI. (Recommended method. Board included in NXL HVAC as standard) NXL equipped with NXLOPTAI fu...
Page 51 - Control Keypad; CONTROL KEYPAD; Indications on the Keypad display; Figure 7-1. NXL control keypad and drive status indications; RUN
Control Keypad 51(96) 7 7. CONTROL KEYPAD The control keypad is the link between the NXL frequency converter and the user. The NXL control keypad features a seven-segment display with seven indicators for the Run status (RUN, , READY, STOP, ALARM, FAULT) and three indicators for the control place (I...
Page 54 - start
54(96) Control Keypad Honeywell Honeywell Honeywell Honeywell 7 = Start button. Pressing this button starts the motor if the keypad is the active control place. See Chapter 7.4.3.1. = Stop button. Pressing this button stops the motor (unless disabled by parameter P3.4). Stop button serves also for a...
Page 55 - Main menu; Location
Control Keypad 55(96) 7 7.4 Navigation on the control keypad The data on the control keypad are arranged in menus and submenus. The menus are used for example for the display and editing of measurement and control signals, parameter settings (chapter 7.4.2), reference values (Chapter 7.4.3) and faul...
Page 57 - Menu functions
Control Keypad 57(96) 7 Menu functions Code Menu Min Max Selections M1 Monitoring menu V1.1 V1.24 See chapter 7.4.1 for the monitoring values NXL HVAC P2.1 = HVAC parameters P2.1.15 = Basic parameters NXL Compact P2.1 = Basic parameters P2 Parameter menu P2.1 P2.10 P2.2 = Input signals P2.3 = Output...
Page 59 - Code
Control Keypad 59(96) 7 Code Signal name Unit ID Description V1.1 Output frequency Hz 1 Frequency to the motor V1.2 Frequency reference Hz 25 V1.3 Motor speed rpm 2 Calculated motor speed V1.4 Motor current A 3 Measured motor current V1.5 Motor torque % 4 Calculated actual torque/nominal torque of t...
Page 60 - The value will not change unless the Enter button is pushed.
60(96) Control Keypad Honeywell Honeywell Honeywell Honeywell 7 7.4.2 Parameter menu (P2) Parameters are the way of conveying the commands of the user to the frequency converter. The parameter values can be edited by entering the Parameter Menu from the Main Menu when the location indication P2 is v...
Page 61 - Figure 7-6. Parameter value change procedure
Control Keypad 61(96) 7 Figure 7-6. Parameter value change procedure enter STOP I/O term READY STOP I/O term READY STOP I/O term READY STOP I/O term READY STOP I/O term READY STOP I/O term READY STOP I/O term READY nxlk17.fh8 Hz Hz Hz
Page 62 - Parameters in Menu; place; Control place; Keypad; then be browsed through with the
62(96) Control Keypad Honeywell Honeywell Honeywell Honeywell 7 7.4.3 Keypad control menu (K3) In the Keypad Controls Menu , you can choose the control place, edit the frequency reference and change the direction of the motor. Enter the submenu level with the Menu button right . Parameters in Menu K...
Page 63 - Keypad reference; the keypad has been selected as the active control place.; Stop button activation; always
Control Keypad 63(96) 7 7.4.3.2 Keypad reference The keypad reference submenu (R3.2) displays and allows the operator to edit the frequency reference. The changes will take place immediately. This reference value will not, however, influence the rotation speed of the motor unless the keypad has been...
Page 64 - Fault type symbol
64(96) Control Keypad Honeywell Honeywell Honeywell Honeywell 7 7.4.4 Active faults menu (F4) The Active faults menu can be entered from the Main menu by pushing the Menu button right when the location indication F4 is visible on the keypad display. The memory of active faults can store the maximum ...
Page 65 - fault texts and codes that appear on the keypad; Fault
Control Keypad 65(96) 7 7.4.5 Fault codes The fault codes, their causes and correcting actions are presented in the table below. The shadowed faults are A faults only. The items written in white on black background present faults for which you can program different responses in the application. See ...
Page 66 - Motor underload protection has tripped.; control cable is broken or loose
66(96) Control Keypad Honeywell Honeywell Honeywell Honeywell 7 17 Motor underload/ Pump Dry detection/ Broken belt Detection Motor underload protection has tripped. FAN: check that Belt is not broken PUMP: check that Pump is not dry 22 EEPROM checksum fault Parameter save fault − faulty operation −...
Page 67 - Fieldbus fault
Control Keypad 67(96) 7 53 Fieldbus fault The data connection between the fieldbus Master and the fieldbus board is broken Check installation. If installation is correct contact the nearest Honeywell distributor 54 Slot fault Defective option board or slot Check board and slot. Contact the nearest H...
Page 68 - System menu
68(96) Control Keypad Honeywell Honeywell Honeywell Honeywell 7 7.4.7 System menu (S6) The System menu can be entered from the main menu by pushing the Menu button right when the location indication S6 is visible on the display. The controls associated with the general use of the frequency converter...
Page 69 - AI mode
Control Keypad 69(96) 7 T6.8.2.4 Operating hours trip counter hh:mm: ss P6.8.2.5 Clear operating time counter 0 = No action 1 = Clear T6.8.2.3, T6.8.2.4 S6.8.3 Software info I6.8.3.1 Software package Scroll information with menu button right I6.8.3.2 System SW version I6.8.3.3 Firmware interface I6....
Page 70 - Figure 7-10. Storing and loading of parameter sets
70(96) Control Keypad Honeywell Honeywell Honeywell Honeywell 7 7.4.7.1 Copy parameters The Copy parameters submenu (S6.3) is located under the System menu. The Honeywell NX frequency converter features a possibility for the user to store and load two customised parameter sets (all parameters includ...
Page 73 - Example; Transfer delay between the frequency converter and the PC = 600 ms
Control Keypad 73(96) 7 HMI acknowledge timeout (P6.7.3) This function allows the user to change the timeout of the HMI acknowledgement time. Note! If the frequency converter has been connected to the PC with a normal cable , the default values of parameters 6.7.3 and 6.7.4 (200 and 5) must not be c...
Page 74 - Trip counters; Page; The trip counters run only when the motor is running.
74(96) Control Keypad Honeywell Honeywell Honeywell Honeywell 7 Counters submenu (S6.8.1) In the Counters submenu (S6.8.1) you can find information related to the frequency converter operation times, i.e. the total numbers of MWh, operation days and operation hours passed so far. Unlike the counters...
Page 75 - Menu button right
Control Keypad 75(96) 7 Software info submenu (S6.8.3) The following information can be found under the Software info submenu (S6.8.3): Page Content I6.8.3.1 Software package I6.8.3.2 System software version I6.8.3.3 Firmware interface I6.8.3.4 System load Table 7-8. Software information pages Appli...
Page 76 - Figure 7-16. Expander board information menu
76(96) Control Keypad Honeywell Honeywell Honeywell Honeywell 7 For more information on the expander board-related parameters, see Chapter 7.4.9. Figure 7-16. Expander board information menu 7.4.7.6 AI mode The parameters P6.9.1 and P6.9.2 select the analogue input mode. P6.9.1 appears only in class...
Page 77 - Modbus RTU; Table 7-12. Modbus commands supported by NXL; Control terminal
Control Keypad 77(96) 7 7.4.8 Modbus interface NXL has a built-in Modbus RTU bus interface. The signal level of the interface is in accordance with the RS-485 standard. Protocol: Modbus RTU Baud rates: 300, 600, 1200, 2400, 4800, 9600, 19200, 38700, 57600 (bit/s) Signal level: RS-485 (TIA/EIA-485-A)...
Page 78 - Output Process data
78(96) Control Keypad Honeywell Honeywell Honeywell Honeywell 7 7.4.8.2 Termination Resistor The RS-485 bus is terminated with 120 Ω termination resistors in both ends. NXL has a built-in termination resistor which is switched off as a default. See the jumper selections in chapter 6.2.5.1 7.4.8.3 Mo...
Page 79 - Status Word; Status word; Actual speed; Description
Control Keypad 79(96) 7 Status Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 - - - - - - - - F Z AREF W FLT DIR RUN RDY Information about the status of the device and messages is indicated in the Status word . The Status word is composed of 16 bits the meanings of which are described in the table below...
Page 81 - Expander board menu; Further keypad functions
Control Keypad 81(96) 7 Communication time-out (P6.10.7) If communication between two messages is broken for a longer time than that defined by this parameter, a communication error is initiated. If the value of this parameter is 0 , the function is not used. 0 = Not used 1 = 1 second 2 = 2 seconds,...
Page 82 - COMMISSIONING
82(96) Commissioning Honeywell Honeywell Honeywell Honeywell 8 8. COMMISSIONING 8.1 Safety Before commissioning, note the following directions and warnings: 1 Internal components and circuit boards of the frequency converter (except for the galvanically isolated I/O terminals) are live when NXL is c...
Page 83 - Commissioning; Perform run test; without motor; Perform either Test A or Test B:
Commissioning 83(96) 8 - motor nominal speed - motor nominal current You will find the values needed for the parameters on the motor rating plate. NOTE! You can also run the Start-up Wizard. See Chapter 7.3 or NXL HVAC quick guide for more information. 8 Perform run test without motor Perform either...
Page 86 - NXL HVAC Quick; to see the values with different modes in wizard.
86(96) Commissioning Honeywell Honeywell Honeywell Honeywell 8 8.3.2 HVAC parameters in NXL HVAC (Control keypad: Menu P2 B2.1) Code Parameter Min Max Unit Default** Cust ID Note P2.1.1 Min frequency 0,00 Par. 2.1.2 Hz 0,00 101 P2.1.2 Max frequency Par. 2.1.1 320,00 Hz 50,00 102 NOTE : If f max >...
Page 88 - See; FAULT TRACING; symbol
88(96) Commissioning Honeywell Honeywell Honeywell Honeywell 8 P2.1.16 P2.1.15.16 Analogue output function 0 12 1 307 0 =Not used 1 =Output freq. (0—f max ) 2 =Freq. reference (0—f max ) 3 =Motor speed (0—Motor nominal speed) 4 =Output current (0— I nMotor ) 5 =Motor torque (0—T nMotor ) 6 =Motor po...
Page 89 - Fault tracing; fault can be reset with the
Fault tracing 89(96) 9 fault can be reset with the Reset button on the control keypad or via the I/O terminal. The faults are stored in the Fault history menu (H5) which can be browsed. The different fault codes you will find in the table below. The fault codes, their causes and correcting actions a...
Page 92 - DESCRIPTION OF EXPANDER BOARD NXLOPTAA; Honeywell NXL
92(96) Honeywell Honeywell Honeywell Honeywell 10 10. DESCRIPTION OF EXPANDER BOARD NXLOPTAA Description: I/O expander board with one relay output, one open collector output and three digital inputs. Allowed slots: Honeywell NXL board slot E Type ID: 16705 Terminals: Two terminal blocks; Screw termi...
Page 93 - Expander board NXLOPTAI; DESCRIPTION OF EXPANDER BOARD NXLOPTAI; board slot E (standard board in NXL HVAC)
Expander board NXLOPTAI 93(96) 11 11. DESCRIPTION OF EXPANDER BOARD NXLOPTAI Description: I/O expander board with one relay output (NO), three digital inputs and one thermistor input for Honeywell NXL frequency converters Allowed slots: Honeywell NXL board slot E (standard board in NXL HVAC) Type ID...
Page 94 - Hone
94(96) Expander board NXLOPTAI Hone Hone Hone Hone ywell ywell ywell ywell 11 Terminal Parameter setting Description X4 12 +24V Control voltage output; voltage for switches etc, max. 150 mA 13 GND Ground for controls, e.g. for +24 V and DO 14 DIN1 DIGIN:B.1 Digital input 1 15 DIN2 DIGIN:B.2 Digital ...
Page 95 - NXL HVAC BASIC SPEED CONTROL – QUICK SETUP; What you need to know
NXL HVAC Basic speed control – Quick setup 95(96) 12 12. NXL HVAC BASIC SPEED CONTROL – QUICK SETUP This chapter provides basic setup instructions for the user of NXL HVAC inverters, when using Basic Speed Control in HVAC applications. What you need to know Motor nameplate data Nominal current Nomin...
Page 96 - Find out more
Automation and Control Solutions Honeywell GmbH Böblinger Str. 17 71101 Schönaich, Germany Telephone (49) 7031 637 01 Telefax (49) 7073 637 493 www.ecc.emea.honeywell.com EN1B-0388GE51 R1107 November 2007 © 2007 Honeywell International Inc. Find out more For more information on Honeywell’s frequency...