Page 2 - ORDERING INFORMATION; PREFACE
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 2 ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need f...
Page 3 - SPECIFICATIONS
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 3 65-0303—05 The software upgrade is automatic after the above steps. The OI Display connects to the Honeywell server, which verifies the configuration file, erases the old application and downloads the new one. The OI Display may have difficulty finding ...
Page 4 - SAFETY FEATURES; WARNING
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 4 required to correct the interference at his own expense. This Class A digital apparatus complies with Canadian ICES-003. Cet Appareil numérique de la classe A est conforme à la norme NMB-003 du Canada. SAFETY FEATURES The OI Displays contain ...
Page 12 - PAGE NAVIGATION; Common OI Display Page Symbols
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 12 STARTING THE S7999C OI DISPLAY Power-up Validation The Home page will appear and the “Power” LED will be on continuously and the “COM” LED will be blinking when the device is properly powered and communicating to the Sola Control. The “COM” ...
Page 13 - Configure Button; Configuration Password
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 13 65-0303—05 • History: used to view burner control history (see “History Button” on page 16 for more details). • ?: used to expand the pump status information. • Modulation: used to toggle between status displays: pump, setpoints, and modulation. Fig. 1...
Page 14 - Keyboard; Login
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 14 Three levels of access to Sola Control parameters are permitted. Each access level has defined rights when interfacing with configuration and status parameters within the controls. • End user: The end user can read or view the control parame...
Page 15 - Change Parameter Settings; Verify
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 15 65-0303—05 Change Parameter Settings Change parameter settings by selecting the parameter on the page. A dialog box displays for the parameter with controls allowing the user to change the value (see Fig. 19). After changing the setting to a new value,...
Page 16 - History Button
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 16 Fig. 22. Safety parameter confirmation. Press the Yes button to confirm each safety parameter block. If the No button is selected, the safety parameter block remains unconfirmed and the Configuration menu page is displayed. The control remai...
Page 18 - Operation Button
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 18 Fig. 27. Control expanded lockout detail. Fig. 28. Control expanded alert detail. Operation Button The operation button displays the SOLA Control running operation, including setpoint and firing rate values. From this page the user can chang...
Page 19 - Diagnostics Button
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 19 65-0303—05 Diagnostics Button The Diagnostics button displays analog and digital I/O status of the SOLA Control. A snapshot of the diagnostic status is displayed and updated once per second as it changes in the control. See “R7910A or R7911 Diagnostics...
Page 20 - Configuration
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 20 A new control is visible when configuration and status data is gathered from it. This collection procedure takes a few minutes. The control is marked as “Unknown” when no configuration information exists. Normally, control configuration data...
Page 23 - DHW Storage Configuration
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 23 65-0303—05 Domestic Hot Water (DHW) Configuration Parameters (R7910A Hydronic Control Only) Table 11 displays Domestic Hot Water (DHW) configuration parameters. Fig. 41. Domestic Hot Water (DHW) configuration. DHW Storage Configuration Table 12 display...
Page 26 - Pump Configuration Parameters
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 26 Pump Configuration Parameters Table 17 displays Pump configuration parameters. Use the left and right arrows to switch between Central Heat, Boiler, DHW, System, Auxiliary 1, and Auxiliary 2 pumps. The parameters are the same for all pumps. ...
Page 27 - Statistics Configuration Parameters
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 27 65-0303—05 Statistics Configuration Parameters Table 15 displays Statistics configuration parameters. Fig. 46. Statistics configuration. High Limit Configuration Parameters (R7910A Hydronic Control Only) Table 19 displays outlet high limit configuratio...
Page 28 - Stack Limit Configuration Parameters
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 28 Stack Limit Configuration Parameters Table 20 displays stack limit configuration parameters. Fig. 48. Stack Limit configuration. Delta T Limit Configuration Parameters (R7910A Hydronic Control Only) Table 21 displays other limit parameters. ...
Page 30 - Safety Configuration Parameters
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 30 Frost Protection Parameters (R7910A Hydronic Control Only) Table 25 displays frost protection parameters. Fig. 51. Frost Protection configuration. Annunciation Configuration Parameters Table 26 displays annunciation configuration parameters....
Page 32 - Safety Parameter Verification
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 32 Fig. 56. Burner Control Flame Failure configuration. Safety Parameter Verification When any of the safety configuration parameters are changed, the safety parameter verification procedure must be performed before the control will resume burn...
Page 35 - Fan Parameters
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 35 65-0303—05 Individual R7910A or R7911 Configuration Parameters Table 31 and Table 32 displays system configuration parameters for individual controls. Fig. 66. System configuration (R7911 shown). Fan Parameters Table 33 displays fan parameters. Fig. 67...
Page 38 - DETAILS
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 38 DETAILS Details of the hydronic or steam system is accomplished through the detail status pages. The detail status page is shown below. Screens will appear only if they are configured for your system. Information shown is current status. For...
Page 40 - Burner Control Status
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 40 Fig. 76. DHW Hydronic Status menu (middle). Fig. 77. DHW Hydronic Status menu (bottom). Burner Control Status The Burner Control status page will display the status data shown in Table 47. The bar graph displayed for this status is the outle...
Page 46 - INSTALLER CHECKOUT; Diagnostics Tests
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 46 Fig. 94. Diagnostics analog I/O page (left). Fig. 95. Diagnostics analog I/O page (center). Fig. 96. Diagnostics analog I/O page (right). INSTALLER CHECKOUT Diagnostics Tests Pressing the Diagnostics Test button launches the diagnostic tests...
Page 48 - ADVANCED SETUP
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE 65-0303—05 48 Fig. 103. Screen disabled for cleaning. Pressing the SYSTEM CONFIGURATION button starts up the system configuration. For more information, see “System Configuration (S7999B OI DisplayOnly)” on page 19. Pressing the ADVANCED SETUP button star...
Page 51 - Trend Analysis Snapshot; Diagnostics
51 65-0303—05 • Setpoint (for corresponding demand source) • Burner firing rate • Hysteresis on (for corresponding demand source) • Hysteresis off (for corresponding demand source) The Clear button is disabled for the PID analysis (doesn’t apply to hysteresis). The default sample rate is 15 sec peri...