Page 2 - SUPER TRADELINE
L4006,7,8; L6006,7,8 AQUASTAT ® CONTROLLERS 60-2104—10 2 ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE ® wholesaler or distributor, refer to the TRADELINE ® Catalog or price sheets for complete ordering number. If you have additional questions, need ...
Page 8 - INSTALLATION; When Installing This Product...; WARNING; CAUTION; Mounting Immersion Well and Direct
L4006,7,8; L6006,7,8 AQUASTAT ® CONTROLLERS 60-2104—10 8 INSTALLATION When Installing This Product… 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the...
Page 9 - Mounting Remote Bulb Models
L4006,7,8; L6006,7,8 AQUASTAT ® CONTROLLERS 9 60-2104—10 Fig. 6. Internal view of L6006A. Installing Direct Immersion Models (L4006C, L6006B) Models that provide for direct immersion of the sensing element into the boiler include a bulb compression fitting assembly instead of an immersion well. Inst...
Page 10 - Mounting With Bulb Compression Fitting
L4006,7,8; L6006,7,8 AQUASTAT ® CONTROLLERS 60-2104—10 10 Fig. 8. Immersion well fitting. Fig. 9. Internal view of L4008L or L6008G. Mounting With Bulb Compression Fitting 1. Screw the fitting into the boiler or pipe tapping. 2. Slide the sealing washer onto the bulb. 3. Insert the bulb into the fit...
Page 11 - Mounting with Guard Bracket
L4006,7,8; L6006,7,8 AQUASTAT ® CONTROLLERS 11 60-2104—10 Fig. 12. Bulb support. 3. Break the holder to the desired length. (See Fig. 13). NOTE: The holder must be long enough to hold the sensing bulb in freely circulating air away from the duct wall. Neatly coil the excess capillary at the controll...
Page 12 - Mounting on Suction Line; Mounting Surface Mount Models
L4006,7,8; L6006,7,8 AQUASTAT ® CONTROLLERS 60-2104—10 12 Mounting on Suction Line 1. In cooling units with more than one suction line, place the sensing bulb on the common line. 2. Make certain the bulb is at least 2 ft (0.6 m) from the point at which the suction line leaves the cooler. This preven...
Page 14 - OPERATION; High Limit Controller
L4006,7,8; L6006,7,8 AQUASTAT ® CONTROLLERS 60-2104—10 14 Fig. 25. Typical wiring hookup using L6006 or L6007 with L8148A. Fig. 26. Typical systems with 120 volt electric heat primaries. Fig. 27. Typical Powerpile System wiring diagram. Fig. 28. Typical oil burner installation using L4008G. OPERATIO...
Page 15 - Low Limit Controller; ADJUSTMENTS; Adjusting Differential
L4006,7,8; L6006,7,8 AQUASTAT ® CONTROLLERS 15 60-2104—10 Fig. 29. Operation of L6008G. Fig. 30. Operation of L4008L. Low Limit Controller R-B terminals provide low limit switching function (contacts open at set point on temperature rise). Maintains minimum boiler temperature for domestic hot water....
Page 16 - Adjusting L6008G Interstage Differential
L4006,7,8; L6006,7,8 AQUASTAT ® CONTROLLERS 60-2104—10 16 Adjust the control point to correspond with the boiler manufacturer recommendations. To adjust, insert a screwdriver in the slotted screw type head located beneath the window in the cover. Turn the scale to the desired control point. Adjustin...
Page 17 - CHECKOUT
L4006,7,8; L6006,7,8 AQUASTAT ® CONTROLLERS 17 60-2104—10 CHECKOUT WARNING Explosion Hazard. Can cause serious injury, death or property damage. This product is intended for use only in systems with a pressure relief valve. Check to make certain that the Aquastat Controller is properly installed and...
Page 18 - MATERIAL SAFETY DATA SHEET; Acute Health Effects:
L4006,7,8; L6006,7,8 AQUASTAT ® CONTROLLERS 60-2104—10 18 MATERIAL SAFETY DATA SHEET Section 1. Product And Company Identification Product Name: Heat Conductive Compound MSDS ID: DS9021 Synonyms: MS1699 Product Use: Heat conductive material used to enhance contact and heat transfer in temperature se...