Page 3 - General Information; Package Contents; Honeywell Fire Panel
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide – 1 – General Information The IPGSM-DPC Commercial Fire Communicator (henceforth referred to as IPGSM-DPC) includes everything you need to upgrade a commercial fire system that previously reported by POTS to a system that uses the...
Page 4 - Operation
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide – 2 – Operation The IPGSM-DPC replaces the fire panel's POTS communications path. When an event occurs, the fire panel goes off-hook to dial the central station. The IPGSM-DPC detects the off-hook condition and provides the fire p...
Page 5 - Installation; ULC Compliance
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide – 3 – Installation ULC Compliance To meet Canadian ULC compliance, ensure the following: IPGSM-DPC must be installed in accordance with Canadian Electrical Code, Part 1. IPGSM-DPC must be mounted in the same room and within 20...
Page 7 - LED Display Information; plastic screw
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide – 5 – 4. Connect the LED Display board to its connector, then slide the board into the mounting rails. (Refer to the “ LED Display Information ” topic if a wire is detached from its connector.) 5. Carefully remove the packaging ma...
Page 8 - CONDUIT; FUSE; BATTERY; iGSM Comm Module; BLU; TO Cabinet Ground Post; BLU; Tin wire ends; DO NOT REMOVE these knockouts.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide – 6 – IPGSM-DPC-001-V1 TB 1 678 5 1011 9 234 1 FOR EXTERNAL ANTENNA50 OHM MMCX ONLY PRIMARY POWER: 9 - 16.5 VACCURRENT: 900mA PEAK, 70mA STANDBYBATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP FCC:XXXXXXXXXX IC: YYYYYYYYYY RSSI M0 M1 GPRS IB...
Page 9 - Wiring the 659EN Line Fault Monitor (if required); Line Fault Monitor is installed.; Example wiring for an addressable fire control panel:
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide – 7 – Wiring the 659EN Line Fault Monitor (if required) The IPGSM-DPC is compatible with the Honeywell brand FACP’s listed on page 1 when the model 659EN Line Fault Monitor is installed. 1. Refer to the installation guide for the ...
Page 10 - STEP 5 – Program the Communications Module; Space; ] key to scroll through a list of options.; If a Com Path Choice of IP&GSM or IP was selected, prompt 9 will
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide – 8 – STEP 5 – Program the Communications Module You must use the 7720P Programming tool to program the IPGSM-DPC. When using the 7720P Programming tool, the values given below are for most installations. Press the [#] key to acce...
Page 11 - Display; Module is not yet initialized.; Failed to Update; Setting Factory Defaults; Close and lock the cabinet cover.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide – 9 – To exit the programming mode, press [N] in response to the "Review?" prompt. Then press [Y] to the "Exit Prog Mode?" prompt. Upon exiting, the root file is updated to log the changes made. A message is displa...
Page 12 - Dialer Capture Module Information; LED Indicator; Panel Status; If a wire pulled out of the LED Board Connector; NC; zzer; RADIO TROUBLE
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide – 10 – Dialer Capture Module Information LED Indicator STATUS RED – Steady ON Messages exist in buffer. RED – Flashing No messages to be sent. Waiting for messages. GREEN – Steady ON Normal Indication. GREEN – Blinks every 2 sec. ...
Page 13 - PowerBoost1 Module Information; Missing or low battery.; You must use the DIP switch settings shown below.; PowerBoost1
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide – 11 – PowerBoost1 Module Information LED Indicator STATUS AC (green) AC power available. ACTIVE (green) Cyclical flashing – normal communications. Repetition of 3 flashes – loss of communications. LOW BATT (yellow) Missing or low...
Page 14 - iGSM Communications Module Information; GRN
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide – 12 – iGSM Communications Module Information TB 1 67 8 5 1011 9 234 1 PRIMARY POWER: 9 - 16.5 V AC CURRE N T: 900mA PEAK, 70mA STA N DBY BATTERY: 8V . 3.1 AHr FOR 24 Hr BACKUP FCC:XXXXXXXXXX IC: YYYYYYYYYY RSSI M0 M1 GPRS IBS iPG...
Page 15 - RF Specifications; Central Station Messages
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide – 13 – RF Specifications Band Transmission Frequency (MHz) Transmit Power (dBm) Receive Frequency (MHz) Receive Sensitivity (dBm) Number of Channels Channel Spacing (MHz) Duplex Separation (kHz) GSM 850 824-849 33 869-894 -107 124...
Page 16 - IPGSM-DPC Trouble Detection Information; Fault Condition; IPGSM-DPC Specifications; ITEM
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide – 14 – IPGSM-DPC Trouble Detection Information Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-DPC, and Telco 2 is used by the IPGSM-DPC to report faults to the Fire Panel. If Telco 1 is not operation...
Page 17 - NOTES
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide – 15 – NOTES
Page 23 - Wiring Diagram
Wiring Diagram The wiring diagram below is depicted for point-to-point electrical connection checks used for troubleshooting or component replacement. It is not intended to show the physical routing of wires. When replacing a wire or component, ensure the wire is routed in the same manner as the ori...
Page 24 - This Class A digital apparatus complies with Canadian ICES-003.; IC STATEMENT; For the latest warranty information, please go to:
IC STATEMENT Notice: This Class A digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada. IC STATEMENT This device complies with RSS 210 of IC. Operation is subject to the following two conditions: (1) This device may not ca...