Page 3 - General Information; Package Contents; Operation; UL Compliance
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide – 1 – General Information The IPGSM-DP Commercial Fire Communicator (henceforth referred to as IPGSM-DP) includes everything you need to upgrade a commercial fire system that previously reported by POTS to a system that uses the In...
Page 7 - CONDUIT; BATTERY; iGSM Comm Module
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide – 5 – IPGSM-DP-001-V2[US Only] TB 1 678 5 1011 9 234 1 FOR EXTERNAL ANTENNA50 OHM MMCX ONLY PRIMARY POWER: 9 - 16.5 VACCURRENT: 900mA PEAK, 70mA STANDBYBATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP FCC:XXXXXXXXXX IC: YYYYYYYYYY RSSI M0 M1 ...
Page 8 - STEP 5 – Program the Communications Module; Space; ] key to scroll through a list of options.; If a Com Path Choice of IP&GSM or IP was selected, prompt 9 will
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide – 6 – STEP 5 – Program the Communications Module You must use the 7720P Programming tool to program the IPGSM-DP. When using the 7720P Programming tool, the values given below are for most installations. Press the [#] key to accept...
Page 9 - Display; Module is not yet initialized.; Failed to Update; Setting Factory Defaults; Close the Wall Outlet Box, then close and lock the cabinet cover.
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide – 7 – To exit the programming mode, press [N] in response to the "Review?" prompt. Then press [Y] to the "Exit Prog Mode?" prompt. Upon exiting, the root file is updated to log the changes made. A message is display...
Page 10 - LED Display Information; used, both Telco paths must be; Buzzer
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide – 8 – IPGSM-DP Trouble Detection Information Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-DP, and Telco 2 is used by the IPGSM-DP to report faults to the Fire Panel. If Telco 1 is not operational, t...
Page 11 - PowerBoost1 Module Information; LED Indicator; Missing or low battery.; You must use the DIP switch settings shown below.; PowerBoost1; NC
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide – 9 – Note: If a wire pulled out of the LED Board Connector refer to the diagram on right and reinsert wire, ensuring the connector pin is locked in. PowerBoost1 Module Information LED Indicator STATUS AC (green) AC power available...
Page 12 - iGSM Communications Module Information; GRN
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide – 10 – iGSM Communications Module Information TB 1 678 5 1011 9 234 1 PRIMARY POWER: 9 - 16.5 VACCURRENT: 900mA PEAK, 70mA STANDBYBATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP FCC:XXXXXXXXXX IC: YYYYYYYYYY RSSI M0 M1 GPRS IBS iPGSM-COM-002...
Page 13 - RF Specifications; IPGSM-DP Specifications; ITEM; maximum 1A
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide – 11 – RF Specifications Band Transmission Frequency (MHz) Transmit Power (dBm) Receive Frequency (MHz) Receive Sensitivity (dBm) Number of Channels Channel Spacing (MHz) Duplex Separation (kHz) GSM 850 824-849 33 869-894 -107 124 ...
Page 14 - NOTES
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide – 12 – NOTES
Page 15 - Wiring Diagram
Wiring Diagram The wiring diagram below is depicted for point-to-point electrical connection checks used for troubleshooting or component replacement. It is not intended to show the physical routing of wires. When replacing a wire or component, ensure the wire is routed in the same manner as the ori...
Page 16 - For the latest warranty information, please go to:
FCC STATEMENT Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environmen...