Honeywell INTELLIKNIGHT 5820XL- Manuals
Honeywell INTELLIKNIGHT 5820XL– User Manual in PDF format online.
Manuals:
User Manual Honeywell INTELLIKNIGHT 5820XL
Summary
151295 Installation Procedure Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Contr...
151209 1 Contents Section 1Introduction .............................................................................................................................................. 1-1 1.1 Overview of Basic System .......................................................................................
Contents 151209 7 Appendix ACompatible Devices ..................................................................................................................... A-1 A.1 Notification Appliances ..........................................................................................................
151209 1-1 Section 1Introduction The IntelliKnight 5820XL Fire Alarm Control/Communicator is an addressable fire control system that meets the requirements of UL 864. 1.1 Overview of Basic System The IntelliKnight 5820XL base system is packaged as an assembled stack of 3 circuit boards mounted to an...
IntelliKnight 5820XL Installation Manual 1-2 151209 combination. 1.1.2 Software Features • 125 software zones, 250 output groups. • Advanced smoke detector features: Automatic drift compensationMaintenance alert regionPoint status meets calibrated smoke test requirements for NFPA 72 • “JumpStart” fe...
Introduction 151209 1-3 1.3 Compatible Products Table 1-2 lists the products available from Silent Knight for use with the IntelliKnight 5820XL. Table 1-2: 5820XL Compatible Products Type of Device Model Description SK Addressable SLC Devices See Section 5.1 for a list of compatible devices. SD Addr...
IntelliKnight 5820XL Installation Manual 1-4 151209 The following modems have been tested by Silent Knight for compatibility with the 5820XL and the Silent Knight Software Suite software packages: 1.4 How to Contact Silent Knight If you have a question or encounter a problem not covered in this manu...
Introduction 151209 1-5 Limitations of Fire Alarm Systems Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer’s recommen...
IntelliKnight 5820XL Installation Manual 1-6 151209 materials, etc.). • Heat detectors do not sense particles of combustion and are designed to alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Heat detectors are designed to protect property, n...
Introduction 151209 1-7 Requirements and recommendations for proper use of fire alarm systems in- cluding smoke detectors and other fire alarm devices: Early fire detection is best achieved by the installation and maintenance of fire detection equipment in all rooms and areas of the house or buildin...
151209 2-1 Section 2Agency Listings, Approvals, and Requirements 2.1 Federal Communications Commission (FCC) 1. The following information must be provided to the telephone company before the IntelliKnight 5820XL can be connected to the phone lines: This equipment complies with Part 68 of the FCC rul...
IntelliKnight 5820XL Installation Manual 2-2 151209 disconnect the 5820XL until the problem has been resolved. This product cannot be adjusted or repaired in the field. It must be returned to the factory for service. This equipment is not designed for use with party line service. Connection to party...
Agency Listings, Approvals, and Requirements 151209 2-3 2.2 Underwriters Laboratories (UL) 2.2.1 Requirements for All Installations General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for additional requirements. The f...
IntelliKnight 5820XL Installation Manual 2-4 151209 2.2.2 Requirements for Central Station Fire Alarm Systems 1. Use both phone lines. Enable phone line monitors for both lines. 2. You must program a phone number and a test time so that the 5820XL sends an automatic daily test to the central station...
151209 3-1 Section 3Before You Begin Installation This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly, especially if you are installing a 5820XL panel for the first time. 3.1 What’s in the Box? The IntelliKnight ...
IntelliKnight 5820XL Installation Manual 3-2 151209 3.3 Electrical Specification Table 3-1 list the terminal block on the 5820XL as well as a description of each individual terminal and their respective electrical rating. Table 3-1: Terminal Descriptions and Electrical Specifications Terminal # and ...
IntelliKnight 5820XL Installation Manual 3-4 151209 3.4 Wiring Specifications Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or cause false alarms. To avoid induced noise, follow these guidelines: • Isolate input wiring from high cur...
IntelliKnight 5820XL Installation Manual 3-6 151209 3.5 Board Assembly Diagram Figure 3-2 Model 5820XL Assembly Figure 3-2 shows the circuit boards, metal housing and annunciator that attach the 5820XL assembly to the cabinet. If you should need to remove the board assembly for repair, remove the fo...
Before You Begin Installation 151209 3-7 3.6 Calculating Current Draw and Standby Battery This section is for helping you determine the current draw and standby battery needs if you are using SK addressable devices (Table 3-2) or SD addressable devices (Table 3-3). 3.6.1 Current Draw Worksheet Requi...
IntelliKnight 5820XL Installation Manual 3-8 151209 3.6.1.1 Current Draw Worksheet for SK SLC Devices Use Table 3-2 to determine current requirements during alarm/battery standby operation when SK SLC devices are installed. You can install up 99 SK detectors per loop (396 max per panel) and 99 SK mo...
IntelliKnight 5820XL Installation Manual 3-14 151209 3.7 Installation Tasks Overview This section provides a chart listing tasks that need to be performed when installing the IntelliKnight 5820XL system. The chart is intended to be a handy way for you to make sure you have completed all necessary ta...
151209 4-1 Section 4Control Panel Installation 4.1 Mounting the Control Panel Cabinet Read the environmental specifications in Section 3.2 before mounting the control panel cabinet. This will ensure that you select a suitable location. The panel should be accessible to main drop wiring runs. It shou...
IntelliKnight 5820XL Installation Manual 4-2 151209 4.2 AC Connection At installation, connect the AC terminals to the power source as shown in Figure 4-1. It may be necessary for a professional electrician to make this connection. The AC terminals are rated at 120 VAC, 50 or 60 Hz, 2.5A. Figure 4-1...
Control Panel Installation 151209 4-3 4.3 Battery Connection The control panel battery charge capacity is 7.0 to 35 AH. Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Section 3.6). Wire batteries in series to produce a 24-volt equiv...
IntelliKnight 5820XL Installation Manual 4-4 151209 4.3.1 RBB Accessory Cabinet The Model RBB Accessory cabinet can be used when you are required to use backup batteries that are too large to fit into the main control panel cabinet. The RBB cabinet holds batteries up to the 35 AH size. The RBB dimen...
Control Panel Installation 151209 4-5 3. Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4-5. Figure 4-5 Battery Connections in the RBB Cabinet Note: Figure 4-5 is an example of how the wire connections can be routed. However, any other cabinet knock-...
IntelliKnight 5820XL Installation Manual 4-6 151209 4.4 SBUS Wiring This section contains information on calculating SBUS wire distances and the types of wiring configurations (Class A and B). 4.4.1 Calculating Wiring Distance for SBUS Modules The following instructions will guide you in determining...
IntelliKnight 5820XL Installation Manual 4-8 151209 Wiring Distance calculation example: Suppose a system is configured with the following SBUS modules: 2 - Module 5860 Fire Annunciator 1 - 5895XL Intelligent Power Expander 1 - 5865 LED Annunciator 1 - 5824 Serial/Parallel Interface Module The total...
Control Panel Installation 151209 4-9 4.4.2 Wiring Configurations Figure 4-7 illustrates Class A wiring configuration and Figure 4-8 illustrates Class B configuration. Figure 4-7 SBUS Class A Wiring Figure 4-8 SBUS Class B Wiring SupervisedPower Limited Caution For proper system supervision do not u...
IntelliKnight 5820XL Installation Manual 4-10 151209 4.5 Remote Annunciator 5860 Installation The optional Model 5860 Remote Annunciator, shown in Figure 4-9, performs the same functions as the on-board annunciator. Up to 8 annunciators can be added to the IntelliKnight 5820XL system. Figure 4-9 Mod...
Control Panel Installation 151209 4-13 Flush Mounting with an Electrical Box The 5860 annunciator can be used with the following types of electrical boxes: 4S, single-gang, and double-gang. If an electrical box is used, the box must be 1-3/8” back from the face of the wall to accommodate the annunci...
IntelliKnight 5820XL Installation Manual 4-14 151209 4. After the annunciator wiring to the panel has been completed (described in Sec- tion 4.5.2), replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel. Figure 4-13 Flush Mounting ...
Control Panel Installation 151209 4-15 4.5.2 Model 5860 Connection to the Panel Connect the 5860 to the panel as shown in Figure 4-14. Figure 4-14 Model 5860 Connection to the Panel SupervisedPower Limited
IntelliKnight 5820XL Installation Manual 4-16 151209 4.6 5815XL Installation The 5815XL SLC expander lets you add 127 SD addressable devices or 99 SK detectors and 99 SK modules. Add up to three 5815XLs to a system to achieve the maximum number of devices on the system. To install the 5815XL: 1. Mak...
Control Panel Installation 151209 4-17 4.6.1 5815XL Connection to the Panel Connect the 5815XL to the control panel as shown in Figure 4-16. After the 5815XL is connected to the panel, it must be added to the system. This programming step is described in Section 4.10. Figure 4-16 5815XL Connection t...
IntelliKnight 5820XL Installation Manual 4-18 151209 4.7 5824 Serial/Parallel Interface Module Installation The 5824 serial/parallel interface module allows you to connect a printer to the panel, so you can print a real-time log of system events, a report of detector status, and event history. Instr...
Control Panel Installation 151209 4-19 Figure 4-18 Printer Connection 4.7.1 Selecting 5824 Options Configuring the 5824 includes the following steps: • Add the module to the system. JumpStart will add the module automatically (see Section 6.1). You can also add it manually (see Section 7.3.2). • Sel...
IntelliKnight 5820XL Installation Manual 4-20 151209 Printer and Output Port Options 1. From the Installer Main Menu, select for Program Menu. 2. Select for Module. 3. Select for Edit Module. 4. From the list that displays, select the 5824 module you want to configure. 5. Press to bypass the next tw...
Control Panel Installation 151209 4-23 4.8.3 LED Wiring There are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its power from Pin 11. Internal resistors are sized so that there is approximately 10 mA of current for each LED, no series resistors are required. LED output...
IntelliKnight 5820XL Installation Manual 4-24 151209 4.8.4 Dry Contact Wiring The 8 input circuits on the 5880 board are for monitoring switch inputs-any type of switch supported by the control panel can be used with the 5880. For example, you can use a 5880 to monitor pull stations, water flow, tam...
IntelliKnight 5820XL Installation Manual 4-26 151209 4.9.1 FACP Connection The 5865 connects to the panel via the SBUS. Make connections as shown in Figure 4-25. After the 5865 is connected to the panel, it must be added to the system. This programming step is described in Section 4.10. Figure 4-25 ...
IntelliKnight 5820XL Installation Manual 4-28 151209 show through the label when illuminated. Figure 4-27 Inserting Zone Description Labels
Control Panel Installation 151209 4-29 4.10 C onfiguring Modules This section describes how to configure any system hardware modules that have been added to the system. 4.10.1 Assigning Module IDs When installing a hardware module (such as, 5815XL, 5824, 5860, 5895XL, 5865-3 or 5865-4), you must use...
IntelliKnight 5820XL Installation Manual 4-30 151209 4.11 Telephone Connection Connect the telephone lines as shown in Figure 4-29. The Model 7860 phone cord is available from Silent Knight for this purpose. A number of programmable options are available for customizing telephone lines. These option...
Control Panel Installation 151209 4-31 4.12 Flexputs ™ I/O Circuits The six Flexput™ circuits are an innovative and versatile feature of the control panel. They can be used as: Class A or B notification circuits, Class A or B initiation circuits (either 2 or 4 wire detectors), or as auxiliary power ...
Control Panel Installation 151209 4-33 4.12.1.2 Class A Notification Wiring You must use an appliance from the list of compatible appliances in the Appendix at the back of this manual. To install a Class A notification appliance circuit: 1. Wire the Class A notification appliances as shown in Figure...
IntelliKnight 5820XL Installation Manual 4-34 151209 4.12.2 Conventional Input Switch Circuits This section of the manual explains how to install conventional initiating devices for Class A (Style D) or Class B (Style B) configurations. 4.12.2.1 Class B Inputs You can connect conventional Class B sw...
Control Panel Installation 151209 4-35 4.12.2.2 Class A Inputs You can connect conventional Class A switches, such as waterflow switches and pull stations, directly to the Flexput circuits of the control panel. To install a Class A switch: 1. Wire the Class A switch as shown in Figure 4-33. 2. Confi...
IntelliKnight 5820XL Installation Manual 4-38 151209 4.12.4 Installing 4-Wire Smoke Detectors Any compatible U.L. listed four-wire smoke detector can be used with the control panel (see Appendix A for list of compatible smoke detectors). Figure 4-34 and Figure 4-35 illustrate how to connect a UL lis...
Control Panel Installation 151209 4-39 4.12.4.2 Installing 4-Wire Class A Smoke Detectors Figure 4-37 illustrates how to install 4-wire Class A detectors. Conventions used for wiring 4-wire Class A loops: 1. Up to two Class A 4-wire loops can be connected to the control panel at once. 2. Smoke power...
IntelliKnight 5820XL Installation Manual 4-40 151209 4.12.5 Auxiliary Power Installation Flexput Circuits 1-6 on the control panel can be used as auxiliary power circuits. The three types of auxiliary power available are: • Door Holder Power (see Section 4.12.5.1) • Constant Power (see Section 4.12....
Control Panel Installation 151209 4-41 4.12.5.3 Resettable Power Resettable power is typically used to power beam detectors, flame detectors and conventional 4-wire smoke detectors. For circuits selected as Resettable, 24-volt power is always present at the terminals unless a system reset occurs. If...
IntelliKnight 5820XL Installation Manual 4-42 151209 4.14 Remote Station Applications 4.14.1 Keltron Model 3158 Installation The control panel is compatible with Keltron Model 3158, used for direct connection to a Keltron receiver. The 3158 reports alarms, supervisories, and troubles. The steps for ...
IntelliKnight 5820XL Installation Manual 4-44 151209 4.14.2 City Box Connection Using the 5220 Module This section describes how to connect the control panel to a local energy municipal fire alarm box or “city box” as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service....
IntelliKnight 5820XL Installation Manual 4-46 151209 4. Program the Flexput circuit used as a notification circuit, continuous and non- silencing. Refer to Section 7.4.1 for zone grouping and mapping. 5. If necessary, adjust loop current using the potentiometer (R10) on the 5220 board . Normal loop ...
Control Panel Installation 151209 4-49 4.14.5 Using a MR-201/T Control Relay From Air Products When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote...
IntelliKnight 5820XL Installation Manual 4-50 151209 4.14.6 Transmitter Activated by Dry Contacts This section describes the connection of a UL 864 listed remote station transmitter to the 5820XL FACP dry contacts. The FACP contacts must be supervised by the remote station transmitter module using e...
151209 5-1 Section 5SD and SK SLC Device Installation 5.1 List of SK SLC Devices The following SK SLC devices can be used with the control panel. See the appropriate section number in this manual or the device installation instructions (packaged with the device) for more information. Note: The contr...
IntelliKnight 5820XL Installation Manual 5-2 151209 5.2 List of SD SLC Devices The following SD SLC devices can be used with the control panel. See the appropriate section number in this manual or the device installation instructions (packaged with the device) for more information. Note: The control...
SD and SK SLC Device Installation 151209 5-3 5.3 Maximum Number of Devices The 5820XL supports SK or SD devices on one 5820XL system. The maximum number of devices per system varies depending on device protocol and the number of 5815XL signaling circuit loop (SLC) expanders added to the system. Devi...
IntelliKnight 5820XL Installation Manual 5-4 151209 5.4 Wiring Requirements for SLC Devices The following information applies to all SLC devices. Refer to the section that describes the type of device you are installing for details. 5.4.1 Wiring 5815XL in Style 4 (Class B) Configuration No special w...
SD and SK SLC Device Installation 151209 5-7 5.5 Wiring SK SLC Detectors This section describes how to install SK heat and smoke detectors. All detectors ship with installation instructions. Refer to the detector’s installation instructions for more detailed information. This information applies to ...
IntelliKnight 5820XL Installation Manual 5-8 151209 5.6 Addressing SK SLC Devices All SK devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones place in a one or two digit number, and use the TENS rotary dial to set the tens place i...
SD and SK SLC Device Installation 151209 5-9 5.7 Wiring SD Detectors The information in this section applies to the following SD models: This section describes how to install SD heat and smoke detectors. All detectors ship with installation instructions. Refer to each detectors' installation instruc...
IntelliKnight 5820XL Installation Manual 5-10 151209 5.8 Addressing SD Devices This section explains how to address SD detectors and modules. 5.8.1 SD505-APS, SD505-AHS, & SD505-AIS The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and SD505-AIS ionization smoke detector are e...
SD and SK SLC Device Installation 151209 5-11 5.8.2 SLC Devices with DIP Switches Input and relay module addresses are set using the DIP switches on the module board. The chart below shows the available addresses. For example, to select address 3, place DIP switches 1 and 2 in the up position. The r...
151209 6-1 Section 6Programming Overview This section of the manual is intended to give you an overview of the programming process. Please read this section of the manual carefully, especially if you are programming the control panel for the first time. The JumpStart AutoProgramming feature automate...
IntelliKnight 5820XL Installation Manual 6-2 151209 6.1.1 Input Points JumpStart will determine the number and type of input points (detectors or contact monitor modules) on each SLC loop. JumpStart assigns the correct detector type (heat, ionization or photoelectric), so the installer does not need...
Programming Overview 151209 6-3 6.1.3 Running JumpStart Run JumpStart immediately after you have addressed and connected all input devices (detectors, pull stations, and so on) and output devices (notification appliances, relays, and so on). Note: If you need to install a few devices after you have ...
Programming Overview 151209 6-5 6.2 Mapping Overview This section of the manual is an overview of mapping. Details about how to select mapping options appear in the appropriate subsections in Section 7. Mapping is an important concept with the control panel. In general terms, mapping is assigning or...
IntelliKnight 5820XL Installation Manual 6-6 151209 6.2.1 Input Point Mapping Input points are assigned to input zones, as the example in Figure 6-2 shows. Any input point can be assigned to any input zone. (Input points can be assigned to one zone only. An input point can be designated as “Unused,”...
Programming Overview 151209 6-7 6.2.2 Output Circuit Mapping Figure 6-3 is a simple example showing how to assign notification and relay output circuits to groups. For an example of a simple floor above/floor below application, see Figure 6-5. Figure 6-3 Assigning Output Circuits to Groups (Example)
IntelliKnight 5820XL Installation Manual 6-8 151209 6.2.3 Zone Event Mapping There are 11 types of events that can occur in zones (see below). For each event type, you can activate up to 8 output groups and patterns. If it is necessary to map to more than 8 output groups, an output group template ma...
IntelliKnight 5820XL Installation Manual 6-10 151209 6.2.4 Mapping LED Points Figure 6-6 is a simple example showing how LED points are mapped to zones and output groups. Typically you would create two output groups for each zone, one for alarms and one for troubles. (LED points are available when M...
Programming Overview 151209 6-11 6.3 Programming Using the 5660 Silent Knight Software Suite You can use the 5660 Silent Knight Software Suite (SKSS) to program the control panel onsite or remotely. SKSS is an optional software package that lets you easily program the control panel using a Windows-b...
IntelliKnight 5820XL Installation Manual 6-12 151209 To exit Program Mode: When you have completed working with the menus, press (left arrow) several times until you are exited from programming mode. Two prompts will display. The first prompt is to make sure you intended to leave the Program Menu (s...
IntelliKnight 5820XL Installation Manual 6-14 151209 6.5 Programming Menu Quick Reference This section of the manual lists all Program Menu options in the order they appear on the sub-menus. Default settings are indicated in text or marked with an asterisk. The comments column provide quick informat...
151209 7-1 Section 7Programming This section of the manual describes how to manually program the control panel from the built-in annunciator. Each subsection discusses these menu options in detail. All options described in this section can be performed using the 5660 Silent Knight Software Suite (SK...
IntelliKnight 5820XL Installation Manual 7-2 151209 7.2 SLC Family The 5820XL supports SD protocol SLC devices or SK series SLC devices. You must configure the 5820XL to accept the protocol of the devices you are installing. You cannot mix SLC devices of different protocols. 1. Press or to display t...
Programming 151209 7-3 7. If you wish to edit the modules name press the or arrow to select each character for the modules name (or press to bypass name edit). Press the to move to the next character. Figure 7-1 Edit module Name Programming Screen Example 7.3.1.2 Setting the 5815XL Wiring Class 8. C...
IntelliKnight 5820XL Installation Manual 7-4 151209 if desired. You must save changes when you exit the Program Menu or the new module will not be added. Note: If you Add a Module that has not been physically connected, the panel will go into trouble after it reinitializes (when you exit the Program...
Programming 151209 7-5 7.4 Zone Through the zone option in the program menu you can edit, add, delete, and view zone points. Selections made here affect all detectors and switches in the zone. Up to 125 zones can be used in the system. 7.4.1 Edit Zone Features that can be edited through the edit zon...
IntelliKnight 5820XL Installation Manual 7-6 151209 Appendix B for a list of available characters and their numeric designators. 9. Repeat step 8 until the name is complete. 10. Press when the name is complete. 7.4.1.2 Edit Zone Properties Zone properties consist of alarm delay characteristics, and ...
Programming 151209 7-7 Alarm Delay Characteristics 3. Select the alarm delay characteristics (see Table 7-1) by pressing the or arrow. 4. Press . Table 7-1: Alarm Delay Characteristics Type of Delay Description 1-Count One Count (No Delay). When this option is enabled, an alarm occurs immediately wh...
IntelliKnight 5820XL Installation Manual 7-8 151209 Heat Temperature Setting Use this feature to set the temperature at which heat detectors will respond. The range is 135° to 150° F. All detectors in the zone will respond in the same way. The Model SD505-AHS Heat Detector is an absolute temperature...
Programming 151209 7-9 Mapping to Zone Events Eight types of events can occur in zones. For each event type, you can activate up to 8 output groups or output group template, specifying a pattern for each. The following is a list of all event types: Note: Abbreviations in the parenthesizes are the ch...
IntelliKnight 5820XL Installation Manual 7-10 151209 8. Select options for each event that could occur in this zone. Figure 7-3 is a com- plete example of how you might map a zone. Figure 7-3 Selecting Output Groups/templates and Cadence Patterns for a Zone Event Indicates type of event (in this cas...
Programming 151209 7-11 Zone Mapping Example Suppose you want to program Zone 1 so that: • Any alarm (detector, water flow or manual pull) would activate Output Group 1 using the ANSI cadence pattern. • Manual pull alarm would activate Output Group 3 using constant output. • Troubles would activate ...
Programming 151209 7-13 7.4.1.5 Zone Accessory Options This option applies to detectors that are used with Sounder bases and Relay bases. Single / Multi-station cadence pattern Fire Cadence:_ _ / CO Cadence:_ _ (choose from Patterns 00 to 23). Note: The B200S Sounder bases is intended to be used alo...
IntelliKnight 5820XL Installation Manual 7-14 151209 7.4.4 View Zone Points To view the points in a zone, follow these steps: 1. Enter the installer code. 2. Press or to display the main menu. 3. Select for Program Menu. 4. Press to enter zone menu. 5. Press to view zone points. 6. Enter the number ...
Programming 151209 7-15 7.5 Group An output group is made up of output points that have been programmed to respond in the same way. Output groups simplify programming because you have to program the output characteristics that are common to all of the group points once, instead of programming each i...
IntelliKnight 5820XL Installation Manual 7-18 151209 12. To edit group properties, press . 13. Press the or arrows to select the desired latching option. 14. Press . 15. Press the or arrows to select the desired silencing option. Refer to Table 7- 2. 16. Press . 17. Enable group activation for a con...
Programming 151209 7-19 A warning screen will display. If you want to proceed with deleting the group, select Yes. To cancel, select No. 7.5.4 View Group Points 1. Enter the installer code. 2. Press or to display the main menu. 3. Select for Program Menu. 4. Press to enter group menu. 5. Press to vi...
IntelliKnight 5820XL Installation Manual 7-20 151209 This can be done by creating a template which includes output groups 1 and 2. Then you can map all the zones to the template you created. This will free up output group assignments that are common to several zones. This is very useful when you nee...
Programming 151209 7-21 7.6 Point You may need to change characteristics of individual input points (detectors and switches) even after using JumpStart. This section explains how to change options for: type of input point; latching/non-latching status (switches); and name and zone assignment of a po...
Programming 151209 7-29 7.7 System Options This section of the manual explains how to customize software options that affect general operation of the system. This includes such items as: AC loss hours, system clock options, holidays schedule, telephone and reporting account options. Refer to each in...
IntelliKnight 5820XL Installation Manual 7-30 151209 7.7.1.1 Edit Accounts 6. From the next menu, select for Edit Account. A screen similar to one shown in Figure 7-12 will display. The following subsec-tions describe the options on each field. Figure 7-12 Reporting Account Editing Screen Select Acc...
Programming 151209 7-31 9. Press the or arrow to select the reporting format, then press . Events to Report The next six options select which types of events (or event families) will be reported to this account. (See Figure 7-12 for location of these options on the screen.) Events are reported by zo...
IntelliKnight 5820XL Installation Manual 7-32 151209 12. Enter the number of switch attempts (or press the or arrow), then press . Telephone Number Enter up to 40 characters for phone number for this account. The following special characters are available: Use the number buttons on the annunciator o...
Programming 151209 7-33 7.7.2 Phone Lines To access the phone lines screen: 1. Enter the installer code. 2. Press or to display the main menu. 3. Select for Program Menu. 4. From the Program Menu, select for System Options. 5. Select for the phone lines menu. 6. Select the phone line to be edited (1...
IntelliKnight 5820XL Installation Manual 7-34 151209 Or Press to bypass the dialing prefix option. 7.7.2.2 Number of Answer Rings This option is used in conjunction with the 5660 SKSS. Use the option to determine the number of rings before the panel answers a call from the computer. Range is 00-15 r...
IntelliKnight 5820XL Installation Manual 7-38 151209 7.7.4 Miscellaneous Options 1 Through this programming option you can set the water flow delay time, low AC report delay, enable or disable automatic daylight savings time adjustment, clock format, and AC clock frequency. 7.7.4.1 Water Flow Delay ...
Programming 151209 7-39 7.7.4.2 Low AC Report Delay Note: You must select 1-3 hours in UL central station installations and UL remote signaling installations. You can adjust the number of hours before a Low AC report will be sent to the central station. To program low AC report delay, follow these s...
IntelliKnight 5820XL Installation Manual 7-40 151209 60 Hz. selection To change the AC line frequency, continue programming from step 9 above: 10. Select 50, 60 or Neither, by pressing the or arrow, then press . 7.7.5 Miscellaneous Options 2 Through this programming option you can turn the strobe sy...
Programming 151209 7-41 10. Press the or arrow to toggle this selection between Zone or Point. 11. Then press or . See Section 9 for reporting codes. 7.7.6 Miscellaneous Options 3 From Miscellaneous Options 3, you set the alarm verification time, turn the Plex Door option on/off, and set the start a...
Programming 151209 7-43 7.7.7 Edit Banner Message The banner is the message that displays on the panel LCD when the system is normal, that is, when no alarms or troubles exist and no one is currently using system menus. You can create a customized message, which can be up to 40 characters, two lines...
Programming 151209 7-45 7.9 Computer Account An installer at the panel site can initiate communications between the panel and a computer running the 5660 SKSS (see also Section 8.5.18). In order for this communication to function properly both the computer (running the software) and the control pane...
IntelliKnight 5820XL Installation Manual 7-46 151209 7.10 Access Codes Access codes provide the user access to the control panel functions. Each access code can be customized for each user. This allows some users the ability to access programming and other higher level panel functions, while other u...
IntelliKnight 5820XL Installation Manual 7-48 151209 17. Press . 18. Repeat steps 14 through 17 until user profile is complete. ENTER ACK
151209 8-1 Section 8System Operation Operation of the control panel is simple. Menus guide you step-by-step through operations. This section of the manual is an overview of the operation menus. Please read this entire section carefully before operating the panel. Press to view Main Menu: Select the ...
IntelliKnight 5820XL Installation Manual 8-2 151209 8.2.1 LCD Displays The control panel LCD displays system messages, annunciates alarms, supervisories and troubles; provides status information; and prompts for input. These messages can be up to 80 characters, displaying over four lines of 20 chara...
System Operation 151209 8-3 8.4 Menu System The control panel is easy to operate from Main Menu. To view the Main Menu press the or button on the control panel or remote annunciator, then turn the firefighters key clockwise or enter your access code. The Main Menu will appear as shown in Section 8.4...
IntelliKnight 5820XL Installation Manual 8-4 151209 8.4.2 Using the Menus 8.5 Basic Operation 8.5.1 Setting Time and Date 1. From the Main Menu, select for Set Date and Time. 2. Make changes in the fields on the screen. Use (right arrow) to move through the fields. Use the and to select options in t...
System Operation 151209 8-5 8.5.4 Disable / Enable a Zone 1. From the Main Menu, select for Point Functions. 2. Select for Disable/Enable Point. 3. Select to Disable Zone Points or to Enable Zone Points. 4. Use the or arrow key to select the Zone and press . 8.5.5 Disable / Enable a Point 1. From th...
IntelliKnight 5820XL Installation Manual 8-6 151209 8.5.6 View Event History Use the View Event History feature to display events on LCD. From the Main Menu, press to select Event History. Events will begin displaying with most recent events first. The panel can store up to 1000 events. When it reac...
System Operation 151209 8-7 • All four lines of the LCD are not full. This test takes approximately 15 seconds to complete. You can press any key to end manually while the test is still in progress. When the test ends, you will be returned to the <Test Menu>. 8.5.9 Conduct a Walk Test 1. From ...
IntelliKnight 5820XL Installation Manual 8-8 151209 2. Select for Dialer Test. The screen will display “Manual dialer test started”. When the test is completed, you will be returned to the <Test Menu>. 8.5.11 Silence alarms or troubles Press and enter your code or rotate the key at the prompt....
System Operation 151209 8-9 5. A screen similar to those shown in Figure 8-4 will display. Figure 8-4 Checking Detector Sensitivity Compliance If a printer is attached to the system (via a Module 5824 serial/parallel interface module), you can print detector status (see Section 8.5.19). 8.5.14 View ...
IntelliKnight 5820XL Installation Manual 8-10 151209 8.5.16 View System Information Press from the Main Menu to view the panel model and serial number and system version number and date. The information displays for several seconds then returns to the main menu. 8.5.17 Reset dialer From the Main Men...
IntelliKnight 5820XL Installation Manual 8-12 151209 Note: Detector status can also be viewed and printed using the 5660 SKSS or 5670 SKSS (facility mon- itoring only). 8.6 Operation Mode Behavior The control panel can be in one of seven conditions at any given moment: Normal, Alarm, Prealarm, Super...
System Operation 151209 8-17 8.7 Releasing Operations This control panel supports two types of releasing, Double Interlock Zone, and Single Interlock Zone. The Double Interlock Zone operation requires an interlock switch input in the system, and the Single Interlock does not. An interlock switch is ...
IntelliKnight 5820XL Installation Manual 8-18 151209 for zone option programming. 8.7.1 Single Interlock Zone Releasing A single interlock zone utilizes a minimum of two addressable detectors and a designated manual release switch. Conditions Required for an Pre-Alert Output Activation If any single...
System Operation 151209 8-19 8.7.2 Double Interlock Zone Releasing A Double Interlock Zone uses a minimum of two Addressable detectors, a designated manual release switch, and an interlock switch input. An interlock switch is typically a dry-contact pressure switch and will be referred to as an inte...
System Operation 151209 8-21 8.8 Smoke Alarm Verification Figure 8-6 illustrates how the Smoke Alarm Verification cycle operates. Figure 8-6 Smoke Verification Cycle During the Confirmation Period if there is no alarm indication then the system will return to normal operation.
151209 9-1 Section 9Reporting This section lists receivers that are compatible with this control panel, and the reporting codes sent by the control panel for SIA and Contact ID formats. 9.1 Receivers Compatible with the Control Panel Table 9-1 shows receivers compatible with the control panel. 9.2 R...
Testing and Troubleshooting 151209 10-3 condition is transmitted. 2) Notify facility personnel of a test so that alarm sounding devices are ignored during the test period. 3) When necessary, activation of Notification Appliances can be prevented by the DISABLE function Testing: 1) Activate a input v...
IntelliKnight 5820XL Installation Manual 10-4 151209 10.3 Built-in Troubleshooting and Testing Tools The fire control panel has several built-in testing and troubleshooting tools that can be utilized to save time while testing and troubleshooting points and SLC devices. 10.3.1 SLC Device Locator SLC...
IntelliKnight 5820XL Installation Manual 10-6 151209 10.3.3 I/O Point Control This feature allows you to toggle any output on or off and trip any input device. This can be useful to test a point’s output mapping. Follow these steps to control a I/O point: 1. Select (Point Functions) from the Main Me...
151209 11-1 Section 11Installation Records This section of the manual is for you to use if you wish to track of how points, zones, and groups have been programmed. 11.1 SLC Point Record You can use the chart that begins below to keep track of SLC points. Default addresses for ID:On-board: = 33 5815-...
Installation Records 151209 11-7 Copy these pages if you additional sheets. 5815-3 68 5815-3 98 5815-3 69 5815-3 99 5815-3 70 5815-3 100 5815-3 71 5815-3 101 5815-3 72 5815-3 102 5815-3 73 5815-3 103 5815-3 74 5815-3 104 5815-3 75 5815-3 105 5815-3 76 5815-3 106 5815-3 77 5815-3 107 5815-3 78 5815-3...
IntelliKnight 5820XL Installation Manual 11-8 151209 11.2 Conventional Output Point Record This chart can be used to keep track of how conventional output points (circuits) have been configured. Point/Circuit Group Description 1 2 3 4 5 6 7 8
151209 A-1 Appendix ACompatible Devices A.1 Notification Appliances For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each loop. All supervised notification appliances used with the control panel must be polarized. Note: Not all devices can use the Sync ...
IntelliKnight 5820XL Installation Manual A-12 151209 A.2 Two-Wire Smoke Detectors Table A-2 lists two-wire smoke detectors that are compatible with the fire control panel. The table is organized by manufacturer. The columns show the number of detectors per loop that can be used. Note: The maximum nu...
151209 B-1 Appendix BSpecial Characters Lists This section contains tables of programmable characters that may be used for device, module, and zone names or phone numbers. B.1 Characters used for Naming Table B-1 list the available character and their associated numeric designator. When programming ...
Silent Knight Fire Product Warranty and Return Policy General Terms and Conditions • All new fire products manufactured by Silent Knight have a limited warranty period of 36 months from the date of manufacture against defects in materials and workmanship. See limited warranty statement for details. ...
Advanced Replacement Policy • Silent Knight offers an option of advance replacement for fire product printed circuit boards that fail during the first 6 months of the warranty period. These items must be returned with transportation charges prepaid and must be accompanied by a return authorization. ...
Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use an...
Cut Along the Dotted Line IntelliKnight 5820XL Basic Operating Instructions These instructions must be framed and displayed next to the IntelliKnight 5820XL panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems. Operation Keystrokes Silence alarms and troubles Press then ...
Honeywell Manuals
-
Honeywell DT8050A
Installation Manual
-
Honeywell DT8050A
Manual
-
Honeywell DT8050A
User Manual
-
Honeywell DT8050
Manual
-
Honeywell DT8050
User Manual
-
Honeywell TPFIT25WK
User Manual
-
Honeywell TPFIT25AWK
User Manual
-
Honeywell TPFIT32WK
User Manual
-
Honeywell TPFIT32AWK
User Manual
-
Honeywell 24DX47
User Manual
-
Honeywell 24DX47
Manual
-
Honeywell TPFIT50PWK
User Manual
-
Honeywell TPFIT50WK
User Manual
-
Honeywell TPFIT50AWK
User Manual
-
Honeywell TPFIT50APWK
User Manual
-
Honeywell 00010
User Manual
-
Honeywell ADVBLEWIFI
Manual
-
Honeywell ADVBLEWIFI
User Manual
-
Honeywell ADVBLE
Manual
-
Honeywell ADVBLE
User Manual