Page 2 - Installation Guide; TablE Of CONTENTs; Read and save these instructions.; For assistance with this product please visit
Installation Guide TablE Of CONTENTs Specifications ................................................................................................................................. 1Accessories ............................................................................................................
Page 3 - spECifiCaTiONs aNd aCCEssOriEs
HZ322 TrueZONE 69-299—0 spECifiCaTiONs aNd aCCEssOriEs Input Ratings: Voltage: 18-30 VAC 50/60 Hz transformer of 40 VA or more. Current Draw: Zone Panel: 7.5 VA max.All VA specifications at 24 VAC. Wiring: 18- or 20-gauge solid (not stranded) wire. Humidity Ratings: 5% to 90% RH non-condensing. Temp...
Page 4 - MOuNTiNg; The HZ322 TrueZONE panel can be mounted in
Installation Guide 69-299—0 2 M28029 MOuNTiNg Mount the HZ322 TrueZONE panel near the HVAC equipment; locate it on a wall, stud, roof truss, or cold-air return. NOTE: The HZ322 TrueZONE panel can be mounted in any orientation; level it for appearance only. Please refer to TrueZONE Panel Frequently A...
Page 5 - WiriNg; Multiple dampers can be wired in parallel.
HZ322 TrueZONE 69-299—0 WiriNg Follow these steps for wiring all systems. However, wiring will vary depending on equipment. For conventional sys-tems, refer to page 5. For heat pump systems, see page 6.Wiring must comply with applicable codes, ordinances, and regulations. Use the following wiring di...
Page 6 - Connect DATS as shown.; Connect transformer as shown.
Installation Guide 69-299—0 The DS/BK terminal is used with a variable-speed fan. Connect the DS, BK, ODD, or DHUM terminal on the HVAC equipment to this terminal. When 1 zone is calling this terminal will be de-energized of 24 VAC. This reduces blower speed on most variable speed blowers. Connect D...
Page 7 - CONvENTiONal
HZ322 TrueZONE 69-299—0 M4 OPEN M6 CLOSED M1 COMMON M28208 R C L1 (HOT) L2 HVAC FAN RELAY G Y 24 VOLT TRANS. C R W W2 C7735A1000 DATS DEDICATED TRANSFORMER ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED RRD OR MARD DAMPER POWER-OPEN POWER-CLOSED COMPRESSOR RELAY ...
Page 8 - HEaT puMp; Fig. 12. Zone panel wiring—heat pump with electric auxiliary heat.
Installation Guide 69-299—0 6 HEaT puMp Fig. 12. Zone panel wiring—heat pump with electric auxiliary heat. Use the following diagram for wiring a heat pump with electric auxiliary heat. NOTE: You can use a conventional thermostat for a heat pump system; however, em heat can only be controlled by hea...
Page 9 - CONfiguraTiON; To enter Configuration:
HZ322 TrueZONE 69-299—0 CONfiguraTiON To enter Configuration: HOME WIRELESS MODE BACK NEXT CONFIG CHECK OUT ADJUST SETTING M24799 1 Press the Mode button (the Config LED will light up). HOME MODE BACK NEXT CONFIG CHECK OUT ADJUST SETTING M24810 WIRELESS 2 Use the Back and Next buttons to navigate th...
Page 10 - advaNCEd CONfiguraTiON; CONNECT WirElEss dEviCEs
Installation Guide 69-299—0 advaNCEd CONfiguraTiON Table 5. Advanced Configuration. Menu Name Menu Title (LCD top line) Menu Options (LCD bottom line; defaults in bold) Menu option description Notes: Heat Fan HEAT FAN CONTROL [HVAC] PANEL Fan control by HVAC In heat mode, fan controlled by HVAC or t...
Page 11 - OpEraTiON; LED; Checkout Step; CHECkOuT
HZ322 TrueZONE 9 69-299—0 The HZ322 TrueZONE panel contains an LED display that communicates system and zone status. The LEDs indicate the following information. OpEraTiON M28026 HZ322 HEAT 1 HEAT 2 COOL 1 COOL 2 FAN PURGE EM HEAT ZONE 1 ZONE 2 ZONE 3 EMERGENCY HEAT Much of this information, as well...
Page 12 - Automation and Control Solutions; WarraNTy
Honeywell International Inc.1985 Douglas Drive NorthGolden Valley, MN 55422customer.honeywell.com Automation and Control Solutions Honeywell Limited-Honeywell Limitée35 Dynamic DriveToronto, Ontario M1V 4Z9 Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers. ® U.S...