Page 2 - Outdoor Mounting

H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS 63-2579—3 2 Outdoor Mounting The H7635C senses outdoor air humidity and temperature. Mount this control where it can sense average outdoor air humidity and temperature. Normally, the north side of a building provides ...

Page 3 - WIRING

H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS 3 63-2579—3 WIRING For voltage output, shielded cable (16-22 AWG) should be used. For current output, either shielded cable or twisted pair (16-22 AWG) can be used. NOTE: When using shielded cable, ground the shield o...

Page 5 - CHECKOUT; CAUTION; Converting Output Signal to Percent RH

H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS 5 63-2579—3 CHECKOUT CAUTION Equipment Damage Hazard.Can short electric circuitry. • Never connect 120 Vac to the transducer. • Connect only DC voltage to a transducer intended for DC supply. NOTE: Use laboratory qual...

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8

Summary

Page 2 - Outdoor Mounting

H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS 63-2579—3 2 Outdoor Mounting The H7635C senses outdoor air humidity and temperature. Mount this control where it can sense average outdoor air humidity and temperature. Normally, the north side of a building provides ...

Page 3 - WIRING

H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS 3 63-2579—3 WIRING For voltage output, shielded cable (16-22 AWG) should be used. For current output, either shielded cable or twisted pair (16-22 AWG) can be used. NOTE: When using shielded cable, ground the shield o...

Page 5 - CHECKOUT; CAUTION; Converting Output Signal to Percent RH

H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS 5 63-2579—3 CHECKOUT CAUTION Equipment Damage Hazard.Can short electric circuitry. • Never connect 120 Vac to the transducer. • Connect only DC voltage to a transducer intended for DC supply. NOTE: Use laboratory qual...