Page 2 - D896 AUTOMATIC VENT DAMPER; ORDERING INFORMATION; TRADELINE® Models; Standard Models
D896 AUTOMATIC VENT DAMPER 68-0186 2 ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to theTRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or...
Page 3 - APPLICATION
D896 AUTOMATIC VENT DAMPER 68-0186 3 NOTE: A minimum of a 30 VA transformer must be usedwhen D896 is installed with S86/S8600/S8610/S8620. Electrical Connections:Four-wire plug receptacle. Thermostat Anticipator Setting:0.13A. Operating Times: Approximate Damper Opening Time: 30 seconds.Approximate ...
Page 4 - INSTALLATION; When Installing this Product...; CAUTION; Location; WARNING; Mounting
D896 AUTOMATIC VENT DAMPER 68-0186 4 IMPORTANT 1. The atmospheric draft hood outlet area must besmaller or equal to the inlet area of the damperassembly. 2. If a second gas valve needs to be installed, referto the gas valve manufacturer instructions for theprocedure. 3. Using a dual automatic valve ...
Page 5 - Wiring
D896 AUTOMATIC VENT DAMPER 68-0186 5 Fig. 3. Installing D896 Vent Damper. IMPORTANT Never mount the vent damper with the motoractuator above or below the vent. Do not install the damper blade plug if the vent damper is installed on a system with a continuous or standing pilot. Thehole provides the m...
Page 7 - Snap-TiteTM Connector Release; SETTINGS; OPERATION AND CHECKOUT; Operation
D896 AUTOMATIC VENT DAMPER 68-0186 7 MV MV/PV PV GND(BURNER) 24VGND 24V SPARK S8600F, H, M; S8610F,H POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. REMOVE PLUG ONLY IF USING VENT DAMPER. FUSE BLOWS ON STARTUP WHEN PLUG IS REMOVED; THEN MODULE OPERATES ONLY WHEN VENT DAMP...
Page 8 - Checkout; Heating; Cooling; TROUBLESHOOTING
D896 AUTOMATIC VENT DAMPER 68-0186 8 Fig. 10. Snap-Tite™ Box Connector release. Checkout Heating 1. Turn on the power supply.2. If using a thermostat, set the heat anticipator at 0.13A.3. Set the thermostat or controller to 10 ° F (6 ° C) above the room temperature to call for heat. 4. Check that th...
Page 9 - INSTRUCTIONS TO THE HOMEOWNER
D896 AUTOMATIC VENT DAMPER 68-0186 9 Thermostat Setting Symptom Possible Cause Action Set thermostat 10°Fabove room temperatureto call for heat. No response from D896. Incorrect wiring or blownfuse. • Check the circuit breaker or fuse and,if necessary, reset or replace. • Check the transformer and l...
Page 10 - ANSI STANDARDS
D896 AUTOMATIC VENT DAMPER 68-0186 10 ANSI STANDARDS EXHIBIT A Procedure For Safety Inspection of an Existing Appliance Installation The following procedure is intended as a guide to aid indetermining that an appliance is properly installed and is in asafe condition for continuing use. This procedur...