Honeywell Ademco Security Systems - Manuals
Honeywell Ademco Security Systems – Manual in PDF format online.
Manuals:
Manual Honeywell Ademco Security Systems
Summary
RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscr...
Table Of Contents • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Features and Installation Highlights ...............................................................................................1-1 Capabilities ..................................................................
Table Of Contents • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Menu Mode Programming...................................................................................................................5-1 Zone Programming Overview ( ∗ 56 and ∗ 58 Menu Modes) .....................
S E C T I O N 1 Features and Installation Highlights • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • SIA Installations: The VISTA-10PSIA is a certified SIA-compliant control that meets SIA specifications for False Alarm Reduction. The VISTA-10P is not certified as SIA complia...
NOTE: All devices and accessories used in a Canadian installation must be Listed for use in Canada. Important Installation Highlights (Installer Please Read) • This system uses addressable keypads and Relay Modules (see table of addresses in Programming Overview section). • Keypads must be set for a...
S E C T I O N 2 Mounting and Wiring the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Cabinet and Lock 1. Mount the control cabinet to a sturdy wall in a clean, dry area, which is not readily accessible to the general public, using fasteners or anchors (not supplied...
Mounting Board with RF Receiver 1. a. Remove the receiver board from its case, then insert the top of the board into the slots at the top of the cabinet, as shown in Detail A in Figure 3. Make sure that the board rests on the correct row of tabs. b. Swing the base of the board into the mounting clip...
Wiring to Keypads 1. Connect keypads to the keypad terminals as shown on the Summary of Connections diagram. Determine wire size using the Wire Run Chart below. 2. Set keypad addresses. Refer to the address setting instructions included with the keypads and set each keypad device address according t...
Sounder (Bell) Connections 1. Make sounder connections to alarm output terminals 3 (+) and 4 (–). For supervised output, continue with steps 2 and 3. 2. Cut the red Bell Supervision Jumper located above terminals 2 and 3 on the control board. 3. Connect a 2k ohm resistor across the terminals of the ...
CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE 24-HOUR BATTERY BACKUP REQUIREMENTS The California State Fire Marshal and UL have regulations which require that all residential fire alarm control panels must be provided with a backup battery which has sufficient capacity to operate the...
Hardwire Zones Normally Open Zones/ Normally Open EOLR Zones 1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device. 2. Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type” prompt. Normally Closed...
Installing the RF Receiver You can any ADEMCO 5800 Series Wireless Receivers, including: RF Receiver No. of Zones 5881L/5882L up to 8 5881M/5882M up to 16 (transmitter zone numbers = 9-24; button zone numbers = 49-56) 5883, 6150RF up to 16 (transmitter zone numbers = 9-24; button zone numbers = 49-5...
Installing the Transmitters 1. To be sure reception of the transmitter's signal at the proposed mounting location is adequate, perform a Go/No Go Test, described in the Testing the System section. 2. Install transmitters in accordance with the instructions provided with each. 3. Set 5827, 5827BD, 58...
UL A UL Listed keyswitch is required for fire installations and UL commercial and residential burglar alarm installations. If a keyswitch is used on: • an installation that transmits opening and closing signals, the keyswitch zone must be programmed to send opening and closing signals. • a UL commer...
On-Board Triggers Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally located above the terminal strip. You can use a 4-wire cable as shown. UL If on-board triggers are used, the wiring between the control unit and the UL Listed device must be run in conduit, be ...
UL The 4285 and 4286 modules are UL Listed only for use on residential fire and UL residential burglar alarm installations. Phone Module Problems If no touch tones are produced following access to the security system from on-premises (this problem may arise in rare cases), it may be necessary to rev...
Audio Alarm Verification Connections (AAV, “listen-In”) Refer to the connection diagrams below. One diagram shows connections when a 4285/4286 Phone Module is used, the other shows connections when the 4285/4286 is not used. Connections use one of the on-board triggers. UL UL installations using the...
S E C T I O N 3 Programming Overview • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Programming You can program the system at any time, even at the installer's premises prior to the actual installation. Programming can also be performed remotely from the installer’s of...
Wireless Receiver, Transmitters, and Wireless Keys (keyfobs) Receiver: Set the receiver’s address to “00” using its DIP switches, then set the following options: *22 RF Jam Option † *24 RF House ID Code (if using wireless keypads) *67 Transmitter Low Battery Report Code † *75 Transmitter Low battery...
Zone Type Definitions You must assign a zone type to each zone, which defines the way in which the system responds to faults in that zone. Zone types are defined below. Zone Type Description Type 00 Zone Not Used Program a zone with this zone type if the zone is not used. Type 01 Entry/Exit Burglary...
Mechanics of Programming Data Field Programming Procedures (You must use a 2-line Alpha display keypad) Task Procedure Entering Program Mode A) Press both [ ∗ ] and [#] at the same time within 50 seconds after power is applied to the control, OR B) After power-up, enter [Installer code (4-1-1-2)] + ...
Table of Device Addresses This Device Uses Address Reports as †† Enabled By… RF Receiver 00 100 *56 zone programming: input device type entry Long Range Radio 03 103 automatic if output to long range radio field *29 enabled 4286 Voice Module 04 104 automatic if phone module access code field *28 ena...
S E C T I O N 4 Data Field Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Data Field Programming The following pages provide explanations of this control’s data fields and is intended to be used in conjunction with the Programming Guide . Refer to the Progr...
Zone Sounds & Timing FIELD TITLE and EXPLANATION *31 Single Alarm Sounding Per Zone Select whether or not the system limits alarm sounding to once per arming period for a given zone. VISTA-10PSIA: If “0” selected, “alarm sounding per zone” will be the same as the “number of reports in armed peri...
Dialer Programming FIELD TITLE and EXPLANATION *40 PABX Access Code Enter the PABX code, if used. To clear entries from field, press ∗ 40 ∗ . If fewer than 6 digits need to be entered, exit by pressing [ ∗ ], which advances to the next field. Call Waiting: If the subscriber’s phone service has “call...
*55 Dynamic Signaling Priority UL Installations: For UL Commercial Burglary installations that use a DACT and LRR, the DACT must be programmed for priority (option “0”). Intended for use with Long Range Radio reporting (field ∗ 29 OUTPUT TO LONG RANGE RADIO must be enabled). Select the initial repor...
FIELD TITLE and EXPLANATION *62 AC Loss Report Code Enter the appropriate report code. Timing of this report is random with up to a 4-hour delay. If AC restores before the report goes out, there is no “AC RESTORE” report. UL: Required for UL commercial burglar alarm installations and for residential...
FIELD TITLE and EXPLANATION *76 Test Restore Report Code Enter the appropriate report code, which is sent when the Test mode is exited. UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations. Miscellaneous System Fields FIELD TITLE and EXPLANATION *77...
FIELD TITLE and EXPLANATION *89 Event Log Full Report Code Enter the appropriate report code, which is sent when the event log is 80% full (if an event log enable is made in field ∗ 90). If the log becomes full, new messages overwrite the oldest messages in the log. *90 Event Log Enables Select the ...
FIELD TITLE and EXPLANATION *96 Command to Initialize CSID and Subscriber Account Number This is a command function, not a data field. Use this command, if necessary, to reset all subscriber account numbers and the internal CSID to the factory default values. *97 Command to Reset System to Factory D...
Configurable Zone Type Programming Fields The system allows you to define a custom zone type, based on the options described below. This configurable zone types can be programmed via the downloader or from a keypad using data fields *182-*183 described below. UL installations: Do not configure zones...
Configurable Zone Type Charts ENTRY 1 ENTRY 2 Response when system disarmed and zone is: Intact EOL RF zone normal Open RF zone N/A Shorted RF zn off-normal Auto Restore Vent Zone 0 = normal 1 = alarm 2 = trouble 3 = fault 0 = normal 4 = alarm 8 = trouble 12 = fault see note 4 0 = normal 1 = alarm 2...
Keypad Programming Fields NOTE: Each keypad must be assigned a unique address. Keypads programmed with the same address will give unpredictable results. Address 16 is reserved for keypad 1, which is automatically set with all sounds enabled. FIELD TITLE and EXPLANATION *190 Keypad 2 Device Address 1...
S E C T I O N 5 Menu Mode Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Zone Programming Overview ( ∗∗∗∗ 56 and ∗∗∗∗ 58 Menu Modes) Use ✱ 56 Zone Programming to program zones, zone types, report codes, enroll 5800 RF Wireless Transmitter seri...
10 Report Code 1st 01 2nd 00 10 Enter the report code for this zone, which consists of 2 hexadecimal digits, each in turn consisting of 2 numerical digits. For example, for a report code of “10,” enter 01 and 00. For Contact ID®, entering any non-zero entry as the first digit enables the report code...
E n t d A 0 2 2 - 4 0 6 3 1 R c v d A 0 2 2 - 4 0 6 4 1 If the serial number transmitted does not match the serial number entered, a display similar to the one shown appears. If the loop number does not match, it will also be displayed. If so, activate the loop input or button on the transmitter onc...
Zn ZT RC IN: L 10 00 10 RF 1 A summary screen with the selected zone’s current programming appears. Begin programming zone information as follows: Enter Zone Type (ZT; see Zone Types listed in *56 Menu Mode “Zone Type” prompt), Report Code (RC), and Input Device Type (IN)* sequentially (Loop Number ...
INPUT S/N L AXXX-XXXX – Manually enter the serial number printed on the label for the wireless key or press and release the button to transmit its serial number. Press [ ∗ ] to accept the serial number. The system will check for duplicate. If necessary, press the [#] key to back up without saving, a...
Output Device Programming Overview (*79/*80 Menu Mode ) Output Devices: The system supports up to 4 relays plus 2 built-in trigger outputs. These “output devices” are assigned to system-wide output numbers (01-04, 17, 18). Relays are identified by the relay module’s device address and the relay posi...
*80 Menu Mode: Defining Output Functions Use this mode to program output function definitions (up to 12 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified by an o...
“ A ” 01 Zn List 1 If zone list was selected, this screen appears. Otherwise skip to the next prompt. Enter the desired zone list number associated with this output number: 01-08 = zone list (Do not use pager zone list 09 in output definitions) Enter the zone list event that will activate this outpu...
Zone List Overview ( ∗∗∗∗ 81 Menu Mode) Zone lists let you group individual zones for use with certain system actions. The following table shows the available zone lists and their purposes: List No. Used for… 1, 2 general purpose 3 chime-by-zone 4 cross zones 5 night stay zones 6 general purpose VIS...
Function Key Programming Overview ( ∗∗∗∗ 57 Menu Mode) The system provides the ability to program each of the four keypad function keys to perform one of 12 system operations. The end user can then activate the function by simply pressing and holding the programmed key for 2 seconds. Typical functio...
About Descriptor Programming Overview ( ∗∗∗∗ 82 Menu Mode) The system lets you assign zone descriptors for protection zones, keypad panics, and RF receiver supervision faults. Each description can be composed of a combination of words (up to 3) selected from a vocabulary of 196 words stored in memor...
✱ Z N 0 1 B A C K D O O R Enter the 3-digit number for the next word. In the example, the word is DOOR, whose number is “057.” See index for entries. [ ∗ ] to continue ✱ Z N 0 1 B A C K D O O R Save second word of descriptor: 6 = save word and go to next word in this descriptor 8 = save word and end...
ALPHA VOCABULARY LIST (For Entering Zone Descriptors) 000 (Word Space) – A – • 001 AIR • 002 ALARM ∗∗∗∗ 004 ALLEY 005 AMBUSH • 006 AREA • 007 APARTMENT • 009 ATTIC ∗∗∗∗ 010 AUDIO – B – • 012 BABY ∗∗∗∗ • 013 BACK ∗∗∗∗ • 014 BAR • 016 BASEMENT ∗∗∗∗ • 017 BATHROOM ∗∗∗∗ • 018 BED • 019 BEDROOM ∗∗∗∗ 020 ...
Programming Installer and User Schedules The system provides 2 schedules (one for the installer, one for the end user), which can be used to control 11 types of system events at pre-defined times. Start Scheduling mode by entering installer code + [#] + [6] [4] while in normal operating mode. NOTE: ...
G R O U P N U M B E R X This prompt appears if event “2” (user access) was selected. Otherwise it is skipped. 1-8 = group number [ ∗ ] to continue to the “Start” prompt S T A R T S M T W T F S H H M M A M 0 0 1 0 0 0 0 Enter the event’s start time and days of the week to occur. 01-12 = hour; 00-59 =...
S E C T I O N 6 System Communication and Operation • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • System Communication Overview This system accommodates several formats for reporting alarms and other system conditions to the Central Station. The process of a successful trans...
Ademco Contact ID ® The Ademco Contact ID ® Reporting Format comprises the following: 4-digit or 10-digit subscriber number (depending on format selected. 1-digit event qualifier (“new” or “restore”). 3-digit event code. 3-digit zone number, user number, or system status number (see the following pa...
User Security Codes The system supports up to 16 security codes, which can each be assigned one of 4 authority levels. The authority level determines the functions each code can perform as follows: Authority Levels (authority levels can be assigned to users 3-16 only; users 1 and 2 cannot be changed...
Keypad Functions The following is a brief list of system commands. For detailed information, see the User's Manual. Voice Keypads The 6150V/6160V Voice Keypads provide the following features: • Message Center, which lets the user record and playback one message. • Voice Status, which can announce sy...
Panic Keys There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate alarms and send a report to the central station by pressing and holding the appropriate key for at least 2 seconds. Each key can be programmed for 24-hour Silent, 24-hour Audible, Fire, or Perso...
S E C T I O N 7 Testing the System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Test Procedures After the installation is complete, you should perform the following tests: System Test: Checks that all zones have been installed properly and the system properly respond...
NOTES: • All BR type units must physically be activated to clear the display. • When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that transmitter are cleared. This also applies to 5816 and 5817 transmitters, which have multiple loops (zones). • An...
S E C T I O N 8 Specifications & Accessories • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • SECURITY CONTROL Physical: 12-1/2” W x 14-1/2” H x 3” D (318mm x 368mm x 76mm) Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, Ademco No. 1321 (in U.S.A.) RECHAR...
5800 Series Transmitter Input Loop Identification All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four inputs require four programming zones). 5802MN ENROLL AS "UR&...
Compatible 5800 Series Transmitters Table (continued) Model Product Input Type Description 5817 Multi-Point Universal Transmitter RF Has three unique input (loop) codes: one for a “Primary” contact loop with programmable options; the others for two “auxiliary” closed circuit contact loops. 5818 Rece...
S E C T I O N 9 Regulatory Agency Statements • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • RADIO FREQUENCY EMISSIONS Federal Communications Commission (FCC) Part 15 This device complies with part 15 of the FCC rules. Operation is subject to the following two condition...
UL NOTICES 1. Entry Delay No. 1 and No. 2 (fields ✱ 35, ✱ 36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds. 2. F...
S E C T I O N 1 0 Limitations and Warranty • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. ...
– INDEX – 1321 ................................... 1-1, 2-4 24-Hour Audible Alarm .............. 3-3 24-Hour Silent Alarm ................. 3-3 3+1 and 4+1 Standard Formats . 6-1 4204 1-2, 2-5, 2-6, 2-9, 3-1, 5-6, 8-1 4229 ................................... 2-6, 3-1 4285 Phone Module 1-1, 2-12, 5-1...
VISTA-10P-SOC-V2 CLASS 2 PLUG-IN TRANSFORMER 16.5V A C , 25V A (e .g. ADEMCO No . 1321). (USE No . 1321CN IN CANAD A) T O 110V A C UNSWITCHED OUTLET (24HR) + THIS EQ UIPMENT SHOULD BE INST ALLED IN A CCORD ANCE WITH THE NA TIONAL FIRE PR O TECTION ASSOCIA T ION'S ST AND ARD 72, CHAPTER 2 (NA T ION...
LIMITED WARRANTY Honeywell International Inc., acting through its Security & Custom Electronics business ("Seller") 165 Eileen Way, Syosset, New York 11791, warrants its product(s) to be in conformance with its own plans and specifications and to be free from defects in materials and wor...
Honeywell Manuals
-
Honeywell DT8050A
Installation Manual
-
Honeywell DT8050A
Manual
-
Honeywell DT8050A
User Manual
-
Honeywell DT8050
Manual
-
Honeywell DT8050
User Manual
-
Honeywell TPFIT25WK
User Manual
-
Honeywell TPFIT25AWK
User Manual
-
Honeywell TPFIT32WK
User Manual
-
Honeywell TPFIT32AWK
User Manual
-
Honeywell 24DX47
User Manual
-
Honeywell 24DX47
Manual
-
Honeywell TPFIT50PWK
User Manual
-
Honeywell TPFIT50WK
User Manual
-
Honeywell TPFIT50AWK
User Manual
-
Honeywell TPFIT50APWK
User Manual
-
Honeywell 00010
User Manual
-
Honeywell ADVBLEWIFI
Manual
-
Honeywell ADVBLEWIFI
User Manual
-
Honeywell ADVBLE
Manual
-
Honeywell ADVBLE
User Manual