Page 2 - DESCRIPTION OF DEVICE FUNCTIONS; controllers
EN2R-9005 0406R3-NE 2 DESCRIPTION OF DEVICE FUNCTIONS Aquastats thermostats Honeywell manufactures a coprehensive range of water temperature thermostats (trade name Aquastat) for controlling and limiting boiler water temperature in hydronic heating systems.These sensitive, fast response devices are ...
Page 3 - DESCRIPTION
3 EN2R-9005 0406R3-NE DESCRIPTION The L41../L61.. series aquastats are sensitive water tempera-ture control, which are provided with a liquid filled sensing sys-tem. The following main types are available: • Single, panel mount immersion Aquastat with remote bulb to select the most favourable positi...
Page 4 - OVERVIEW/SELECTION GUIDE
EN2R-9005 0406R3-NE 4 OVERVIEW/SELECTION GUIDE Application Single Aquastat thermostats Dual Aquastat thermostats Controller or limiter thermostat Controller and limiter thermostat with standard sensing element Direct mount (immersion) L4188A, B, C25 ... 95°C 40 ... 110°C70 ... 140°C L6188A, B, C25 ....
Page 5 - FEATURES
5 EN2R-9005 0406R3-NE FEATURES • 6.3 mm quick connect terminals for receptacles • Mounting either in a horizontal or vertical position. • Housing is provided with two mounting holes which are suitable for M4 thread forming screws, for mounting on a control panel. • Cable entry in the conduit box is ...
Page 6 - APPLICATIONS AND ORDERING INFORMATION
EN2R-9005 0406R3-NE 6 L4188 - L6188 SINGLE AQUASTAT - DIRECT IMMERSION APPLICATIONS AND ORDERING INFORMATION Application L4188 and L6188 are sensitive, immersion-type water temperature thermostats for controlling and limiting boiler water temperature in hydronic heating systems. The thermostat has a...
Page 7 - Specifications; SPDT
7 EN2R-9005 0406R3-NE L4188 - L6188 SINGLE AQUASTAT - DIRECT IMMERSION Specifications Ambient temperature limits 0 ... 70°C Electrical connection 6.3 mm spade terminals Enclosure IP40 Electrical rating 10 A at 250 Vac, resistive load2.5 A at 250 Vac, inductive load15 A at 250 Vac, locked motor250 mA...
Page 9 - SPECIFICATIONS AND DIMENSIONS
9 EN2R-9005 0406R3-NE L4189 - L6189 SINGLE AQUASTAT - PANEL MOUNTING (IMMERSION) SPECIFICATIONS AND DIMENSIONS Specifications Ambient temperature limits 0 ... 70°C Electrical connections 6.3 mm spade terminals Enclosure IP40 Electrical rating 10 A at 250 Vac, resistive load2,5 A at 250 Vac, inductiv...
Page 10 - APPLICATION AND ORDERING INFORMATION
EN2R-9005 0406R3-NE 10 L6190 SINGLE AQUASTAT - SURFACE MOUNTING APPLICATION AND ORDERING INFORMATION Application The L6190 is a sensitive water temperature thermostat designed for surface mounting on domestic hot water cylinders or pipe work. The SPDT switching action is accomplished by a snap-actio...
Page 13 - Ambient temperature limits; Enclosure
13 EN2R-9005 0406R3-NE L4191 - L6191 DUAL AQUASTAT - DIRECT IMMERSION SPECIFICATIONS AND DIMENSIONS Specifications Ambient temperature limits 0 ... 70°C Electrical connection 6.3 mm spade terminals Enclosure IP40 Electrical rating: 10 A at 250 Vac, resistive load2,5 A at 250 Vac, inductive load15 A ...
Page 16 - PERFORMANCE; With well; Without well
EN2R-9005 0406R3-NE 16 PERFORMANCE Fixed switch differential On controls and recycling limits a fixed differential of: 4 ± 1.5°C, 8 ± 3°C or12 ± 3°C is supllied as a standard. Optional are: 7 ± 2.7°F,14 ± 5.4°F15 ± 5.4°F Adjustable switch differential On controllers and recycling limiters an adjusta...
Page 17 - CONSTRUCTION; All aquastats have the following common parts; Dual direct mounted Aquastat needs the following extra parts; Triple direct mounted Aquastat needs the following extra parts
17 EN2R-9005 0406R3-NE CONSTRUCTION All aquastats have the following common parts • Thermoplastic housing of mainly rectangular form. This housing is the carrier of the Micro Switch mechanism, the 6.3 mm quick connect terminals, the lever mechanism and the adjusting mechanism. • Thermoplastic switch...
Page 18 - ACCESSORIES AND SPARE PARTS; Single well assembly
EN2R-9005 0406R3-NE 18 ACCESSORIES AND SPARE PARTS Single well assembly Dual well assembly Description Ordernumber Packing qty (pcs) Spud thread: 1 / 2 ” BSPT Maximum insertion length (including thread): 105 mmSuitable for Ø 5 mm sensor 45.900.409-003 40 Spud thread: 1 / 2 ” BSPT Maximum insertion l...
Page 19 - Miscellaneous
19 EN2R-9005 0406R3-NE Miscellaneous Description Ordernumber Packing qty (pcs) Knob assemblyScale range: 110 ... 230° F, high limit stop: 180°F 45.900.427-002 200 Knob assemblyScale range: 40 ... 110°C , high limit stop: 82°C 45.900.427-003 200 Strap set for L6190 surface mounted aqustatStrap length...
Page 20 - QUALITY ASSURANCE STATEMENT; all; STANDARDS AND APPROVALS; Standards; Approvals
EN2R-9005 0406R3-NE 20 QUALITY ASSURANCE STATEMENT Products are manufactured under an ISO 9001 (1994) based and certified Quality System. The quality system is described in the Honeywell Combustion Controls Center Quality Assurance Programme and its related operational procedures and instructions. T...
Page 21 - ORDERING INFORMATION; When ordering specify
21 EN2R-9005 0406R3-NE ORDERING INFORMATION When ordering specify • Setting point(control and limit if necessary) • Type of contact (SPDT/SPST/ electrical rating) • Number of sensing point (single/dual) • Type of mounting (direct immersion/panel/surface) • Differential (adjustable/fixed/manual reset...