Page 3 - Chapter 1 General Information; Safety; Changes and modifications to this unit not expressly; Do not work alone under hazardous conditions.
1 Chapter 1 General Information The CTFLP Series provides an uninterruptible power source for broadband cable operations. The enclosure is designed for mounting on either a pole or wall. Safety This Safety Guide contains important instructions that should be followed during installation and maintena...
Page 4 - Specifications; Environmental Specifications
2 Specifications Environmental Specifications Operating Temperature -40º F to 158º F (-40º C to 70º C) Humidity 5% to 95% noncondensing within enclosure Physical Specifications Characteristic Specification Height X Width X Depth 11.4” X 8.5” X 7.1” (29 cm X 22 cm X 18 cm ) Weight 36 lbs (16 kg) Elec...
Page 5 - Chapter 2 Installation and Maintenance; Unpacking; CTFLP Enclosure; Model Number; Mounting Bracket
3 Chapter 2 Installation and Maintenance Only trained service personnel should install and maintain the Power Supply. Prior to installing the Power Supply utility line voltage must be routed to the enclosure. Local, state, federal and/or National Electric Code (NEC) regulations regarding location, p...
Page 6 - INDEX ITEM; Bottom View
4 CTFLP Enclosure Installation Loosen (do not remove), the four .25” (.63 cm) nuts on the bracket assembly. Wall Mount Units: Select fasteners that will accommodate the weight of the unit including the power supply. Wiring 1. Attach conduit to the 1/2 “ hole on the bottom of the unit and wire the in...
Page 8 - Installing the FLM Power Supply; Ensure the CTFLP module circuit breaker is OFF.
6 Installing the FLM Power Supply Ensure the CTFLP module circuit breaker is OFF. 1. Unlock and open the front enclosure door. To remove the front door from the enclosure, squeeze the edges of the enclosure together. This will allow the pins at the top of the door to slip out of the side enclosure p...
Page 10 - Chapter 3 Operation; Initial Startup and Performance Verification; Switch the utility circuit breaker ON.; Shut Down; Switch the utility circuit breaker OFF.; Auxiliary Power Supply; Set up an auxiliary utility generator and calibrate to 60 Hz ± 1 Hz.; For details regarding available options see the APC web site
8 Chapter 3 Operation Initial Startup and Performance Verification 1. Switch the utility circuit breaker ON. 2. Verify that the FLM is switched ON. 3. Measure the voltage at the Coax connector ensuring that 60VAC or 90VAC are present depending on the power supply installed. The green Indicator lamp ...
Page 11 - Chapter 4 Troubleshooting and Maintenance; Troubleshooting Power Supply Failure; Routine Maintenance Schedule; Operation Interval; to Initial Startup and Performance
9 Chapter 4 Troubleshooting and Maintenance Troubleshooting Power Supply Failure Problem Possible Cause Solution No input voltage detected at connector J1, pins 1 and 2. Replace the wiring harness Input voltage present at connector J1, pins 1 and 2. Disconnect power from the supply No input voltage ...
Page 12 - Routine Maintenance Procedures; Visual Inspection; Replacement Procedures; Wiring Harness Replacement
10 Routine Maintenance Procedures • Visual Inspection • Check external surfaces, connectors, indicators and wiring/cable assemblies for signs of dirt, wear, and damage. • Cleaning • Brush dust from controls and receptacles using a small paintbrush. • Wipe surfaces with clean, dry cheesecloth. • Clea...
Page 13 - Indicator Lamp Replacement; Initial Startup and Performance
11 • Replace the quick disconnects on the indicator lamp socket. • Reconnect the utility wires and the stinger lug. • Close the front door of the enclosure. • Reinstall the FLM. Ensure the module is seated properly. Refer to Installing the FLM in this manual. • Switch the FLM and the utility circuit...
Page 14 - Chapter 5 Service, Contact and Warranty Information; Service; Support
12 Chapter 5 Service, Contact and Warranty Information Service APC makes every effort to ensure parts and equipment arrive in working condition. Occasionally, it may be necessary to return parts or equipment that are not in working condition. If the UPS requires service do not return it to the deale...