Page 3 - Introduction; NSTALLATION; Unpack; UK customers; Rail Installation
1 Introduction The APC Uninterruptible Power Supply (UPS) is designed to prevent blackouts, brownouts, sags, and surges from reaching your equipment. The uninterruptible power supply (UPS) filters small util-ity line fluctuations and isolates your equipment from large disturbances by internally disc...
Page 4 - Mount the UPS in a Rack
2 Mount the UPS in a Rack Your UPS model may vary from the examples depicted in this manual. Install brackets as shown, or at a 5 in (12.7 cm) setback. Remove the battery module to lighten the UPS during installation. Note: The module is heavy. Install the UPS at or near the bottom of the rack. Rein...
Page 5 - Connect Equipment and Power to the UPS; Startup
3 Connect Equipment and Power to the UPS Startup 1. Connect equipment to the UPS. A laser printer draws significantly more power than other types of equipment and may overload the UPS. 2. Add optional accessories to the Smart-Slot. 3. Plug the UPS into a two-pole, three-wire, grounded receptacle onl...
Page 6 - Basic Connectors; Serial and USB Ports cannot be used simultaneously.
4 Basic Connectors Serial Port USB Port TVSS Screw Use only interface kits approved by APC. Use only the supplied cable to connect to the Serial Port. A standard serial interface cable is incompatible with the UPS. Serial and USB Ports cannot be used simultaneously. The UPS features a transient volt...
Page 7 - PERATION; Front Display Panel; ing
5 2: O PERATION Front Display Panel I NDICATOR D ESCRIPTION Online The UPS is supplying utility power to the connected equipment (see Troubleshoot- ing ). AVR Trim The UPS is compensating for a high utility voltage. AVR Boost The UPS is compensating for a low utility voltage. On Battery The UPS is s...
Page 8 - Press and hold the; Battery Operation; Press the
6 F EATURE F UNCTION Self-Test Automatic: The UPS performs a self-test automatically when turned on, and every two weeks thereafter, (by default). During the self-test, the UPS briefly operates the connected equipment on battery. Manual: Press and hold the button for a few seconds to initiate the se...
Page 9 - high
7 3: U SER C ONFIGURABLE I TEMS N OTE : S ETTINGS ARE ADJUSTED THROUGH P OWER C HUTE SOFTWARE OR OPTIONAL S MART S LOT ACCESSORY CARDS . F UNCTION F ACTORY D EFAULT U SER S ELECTABLE C HOICES D ESCRIPTION Automatic Self-Test Every 14 days (336 hours) Every 7 days (168 hours), On Startup Only, No Sel...
Page 11 - Storage; The UPS battery life differs based on usage and environment.; Transporting; Shut down and disconnect any equipment attached to the UPS.
9 4: S TORAGE , M AINTENANCE , T RANSPORTING , AND S ERVICE Storage Store the UPS covered in a cool, dry location, with the batteries fully charged. At -15 to +30 ° C (+5 to +86 ° F), charge the UPS battery every six months. At +30 to +45 ° C (+86 to +113 ° F), charge the UPS battery every three mon...
Page 12 - Service; Troubleshooting; Contact Information; Support
10 Service If the UPS requires service do not return it to the dealer. Follow these steps: 1. Review the problems discussed in Troubleshooting to eliminate common problems. 2. If the problem persists, contact APC Customer Service through the APC web site, www.apc.com/support . Note the model number ...
Page 13 - ROUBLESHOOTING; with complex UPS problems.; Check that the battery connector is fully snapped into position.
11 5: T ROUBLESHOOTING Use the chart below to solve minor UPS installation and operation problems. Refer to www.apc.com with complex UPS problems. P ROBLEM AND / OR P OSSIBLE C AUSE S OLUTION UPS WILL NOT TURN ON Battery not connected prop-erly. Check that the battery connector is fully snapped into...
Page 14 - Specifications
12 P ROBLEM AND / OR P OSSIBLE C AUSE S OLUTION THE OVERLOAD LED IS ILLUMINATED AND THE UPS EMITS A SUSTAINED ALARM TONE The UPS is overloaded. The connected equipment exceeds the “maximum load,” as de-fined in Specifications at www.apc.com. The alarm remains on until the overload is removed. Discon...
Page 15 - Operation
13 P ROBLEM AND / OR P OSSIBLE C AUSE S OLUTION UPS OPERATES ON BATTERY ALTHOUGH LINE VOLTAGE EXISTS The UPS input circuit breaker tripped. Reduce the load on the UPS by unplugging equipment. Reset the breaker. Very high, low, or distorted line voltage. Move the UPS to a different outlet on a differ...
Page 16 - Regulatory Agency Approvals and Radio Frequency Warnings
14 6: R EGULATORY AND W ARRANTY I NFORMATION Regulatory Agency Approvals and Radio Frequency Warnings 120/208 V models 230 V models BSMI This equipment has been tested and found to com-ply with the limits for a Class A digital device, pur-suant to part 15 of the FCC Rules. These limits are designed ...