Page 2 - Contents; Programming with the D5200 Programmer .. 25
Bosch | 09/04 | 74-06200-000-F 2 D2071A | Operations & Installation Guide | Contents Contents 1.0 Overview .......................................................................... 4 1.1 Communicator ......................................................... 4 1.2 RFI and Lightning Protection .....
Page 3 - FCC Notice; Reorient the radio or television antenna.; Figures
3 Bosch | 09/04 | 74-06200-000-F D2071A | Operations & Installation Guide | FCC Notice FCC Notice The D2071A Fire Alarm Control Panel (FACP)generates, uses, and can radiate radio frequency energy.If this device is not installed according to themanufacturer’s instructions, it can cause interferen...
Page 4 - Overview; Communicator; Installation literature; Required Materials
Bosch | 09/04 | 74-06200-000-F 4 D2071A | Operations & Installation Guide | 1.0 Overview The D2071A Fire Alarm Control Panel (FACP) is athree-zone digital alarm communicator transmitter(DACT) used in limited stand-alone applications or inoff-premises monitoring of existing FACPs in slaveapplicat...
Page 5 - Item Description
5 Bosch | 09/04 | 74-06200-000-F 1.5.1 Mandatory Connections To comply with the NFPA 72 Central Station Fire or NFPA 72 Remote Station Signaling Service, connect theD2071A as described in Table 2. The Class “A” and Class “B” circuits are mandatory connections for the slave andstand-alone application...
Page 6 - Slave Communicator Applications; Slave Application Power; Receiving Equipment; Fire alarm; D2071A Control Panel Assembly; Terminal Strip
Bosch | 09/04 | 74-06200-000-F 6 D2071A | Operations & Installation Guide | 1.6 Slave Communicator Applications To use the D2071A as a slave communicator that onlyprovides signaling connections, connect the D2071A toan existing UL Listed NFPA 72 FACP. Use the D2071Ain compliance with NFPA standa...
Page 7 - - Phone Line Trouble Buzzer
7 Bosch | 09/04 | 74-06200-000-F D2071A | Operations & Installation Guide | 1.0 Overview 1.8.5 Phone Line Trouble LED This yellow Phone Line Trouble LED (Item 5 in Figure 1)is visible through the top of the enclosure at the upperright corner (Item 6 in Figure 1). This LED lights whenthe control ...
Page 8 - Installation; Stand-Alone Installation
Bosch | 09/04 | 74-06200-000-F 8 D2071A | Operations & Installation Guide | 2.0 Installation Some terminals are wired differently for the stand-alone (Figure 2) and slave applications (Figure 3 on page 9). W hen you are using the D2071AC, mount the D4103R Enclosure and have a qualified electrici...
Page 9 - Do not connect earth ground when connected to a 24 VDC power supply.; - Alternate power supply
9 Bosch | 09/04 | 74-06200-000-F D2071A | Operations & Installation Guide | 2.0 Installation 1. Do not connect earth ground when connected to a 24 VDC power supply. 2. Do not connect a battery when connected to a 24 VDC power supply (maximum charging current of 300 mA). 1 8 5 7 4 10 11 2 6 9 3 1...
Page 10 - Class “A” Circuit Parameters
Bosch | 09/04 | 74-06200-000-F 1 0 D2071A | Operations & Installation Guide | 2.1 Earth Ground Wiring Only use Terminal 3, not telephone or electrical ground, for earth ground connections. 2.1.1 12 VAC Mode To prevent damage from electrostatic charges or othertransient electrical surges, use 16 ...
Page 11 - NC; Mode 1 Class “B” Wiring
1 1 Bosch | 09/04 | 74-06200-000-F • If the time specified in the retard time accumulates inone or more successive alarm activations, theD2071A transmits an Alarm Zone 1 Report andactivates the Alarm Relay. • The retard timer resets to zero only when the circuitremains in a non-alarm condition (rest...
Page 12 - Mode 3 Class “B” Wiring; Initiating Circuit Alarm Relay
Bosch | 09/04 | 74-06200-000-F 1 2 D2071A | Operations & Installation Guide | 2.3.3 Mode 3 Mode 3 (Figure 6) uses a 1.8 k Ω EOL resistor at the end of the loops. Trouble Reports are sent on an opencircuit. This mode is required for sprinkler supervisionin NFPA 72 central station and remote stati...
Page 13 - Wiring; Phone Line Trouble Relay; Phone Line Trouble Buzzer on page 7; Primary Power Supply; Parallel Activation on Powerup:; Relay Sockets
1 3 Bosch | 09/04 | 74-06200-000-F 2.4.2 Wiring Connect only low voltage power sources and devices toTerminals 16, 17, and 18. Do not use the D2071AStandby Battery to provide a power output for thecircuit. 2.5 Phone Line Trouble Relay Use Terminals 13, 14, and 15 for Phone Line TroubleRelay connecti...
Page 15 - Telephone Connections; Telephone Cord Installation; - Full modular phone jack
1 5 Bosch | 09/04 | 74-06200-000-F Restoral ZN 9 Exceptions: If a battery is not connected to the D2071A when AC power is connected, the controlpanel sends a RESTORAL ZN 9 Report to the receiver.A RESTORAL ZN 9 is also sent after the programmerdisconnects from the D2071A. Charging Circuit The D2071A...
Page 16 - Cable Tie Installation; Call Routing Assignments
Bosch | 09/04 | 74-06200-000-F 1 6 D2071A | Operations & Installation Guide | Refer to Section 6.0 Troubleshooting on page 24 for help in determining the cause of telephone line problems. The buzzer, light, and relay can remain activated for upto 24 h if the communications failure did not result...
Page 17 - Screw Mounting; Figure 10: Securing Cable Tie and Wires; Adhesive Strip Mounting; End User Instruction Label
1 7 Bosch | 09/04 | 74-06200-000-F 2.9.1 Screw Mounting 1. Select the mounting location in the enclosure. 2. Position the D2071A in the desired location. 3. Use a pencil to mark the mounting tab holes. 4. Drill holes (1/8 in. [3.18 mm]) for the screws provided. 5. Mount the D2071A using the two # 8 ...
Page 18 - Programming; D5200 Programmer Operation Manual fo; Navigating Handler and Program Records; Access program items by navigating the programmer groups.; - Password display
Bosch | 09/04 | 74-06200-000-F 1 8 D2071A | Operations & Installation Guide | 3.0 Programming The information in this section is not intended to be a substitute for the D5200 Programmer Operation Manual (P/N: 74-06176-000). Become familiar with the D5200 Programmer Operation Manual before progra...
Page 19 - Function Keys
1 9 Bosch | 09/04 | 74-06200-000-F D2071A | Operations & Installation Guide | 3.0 Programming 3.2 Function Keys Table 7 identifies the six function keys that simplifyusing the programmer. 3.3 Data Keys Use the white keys on the keyboard for data entry. 3.4 Tones The D5200 Programmer emits four d...
Page 20 - PRODUCT HANDLERS; Transmit BFSK; Program Record
Bosch | 09/04 | 74-06200-000-F 2 0 D2071A | Operations & Installation Guide | 3.8 Program Modules Unlike larger Bosch products, the D2071 ProductHandler does not group program items in programmodules. When you enter the 2071 program, you are inthe Program Item Level. 3.9 Editing the Program Reco...
Page 21 - AltPri; Blank; Use to enable either the 12 V Mode or 24 V Mode.; Class B Mode; Refer to; Special Dialing Characters
2 1 Bosch | 09/04 | 74-06200-000-F PriPh# Default: Blank Selections: 0 to 9, B to F, or Blank Use to select the primary receiver telephone number.You can enter up to seven characters. Refer to Table 9 forother dialing character selections. When programming the primary and alternate telephone numbers...
Page 22 - Reset Time; Selections: 0 to 90; Hrs Til Rpt; Selections: 0 to 25; If both Hrs Til Rpt and Min Til Rpt; Mins Til Rpt; Selections: 0 to 59; Test Timer Default Delay:
Bosch | 09/04 | 74-06200-000-F 2 2 D2071A | Operations & Installation Guide | Reset Time Default: 0 Selections: 0 to 90 Use to program the reset timer for the Class “A” AlarmInitiating Circuit (Zone 1). Enter the number of secondsyou want for the reset time. Before the retard timer setsto zero, ...
Page 23 - Receiver Reports
2 3 Bosch | 09/04 | 74-06200-000-F 5.0 Receiver Reports D2071A | Operations & Installation Guide | 5.0 Receiver Reports Title Description ALARM ZN 1 Closure or short between the two loops of the Class “A” Alarm Initiating Circuit. This report is delayed by the time specified in Retard Time (for ...
Page 24 - Phone Line Trouble; Troubleshooting
Bosch | 09/04 | 74-06200-000-F 2 4 D2071A | Operations & Installation Guide | 6.0 Troubleshooting To help prevent problems, read the preceding sections ofthis guide and confirm the control panel is correctlyinstalled and programmed. 6.1 Phone Line Trouble Buzzer, LED, andRelay Activated The Phon...
Page 25 - Trouble Zone E; Supervisory Circuits on page 11.
2 5 Bosch | 09/04 | 74-06200-000-F 6.3 Trouble Zone E Refer Table 10 on page 23 for the causes of theTROUBLE ZN E Report. If TROUBLE ZN E Reports regularly accompany otherreports: • After two attempts to reach the receiver, a D2071Aswitches to the alternate phone line for the thirdattempt. Confirm t...
Page 26 - Zone Problems
Bosch | 09/04 | 74-06200-000-F 2 6 D2071A | Operations & Installation Guide | 6.5 Zones Problems 6.6 Trouble Zone 9 A TROUBLE ZN 9 Report tells you there is a problemwith the battery when the D2071A is in 12 VAC Mode.It also indicates there is a problem with the powersupply in the 24 VDC Mode. 6...
Page 27 - Specifications
2 7 Bosch | 09/04 | 74-06200-000-F D2071A | Operations & Installation Guide | 7.0 Specifications 7.0 Specifications Power Input 12 VAC, 20 VA with 12 VDC battery 24 VDC Specification 12 VAC Mode 24 VAC Mode Idle Current 29.5 mA 30.0 mA Battery Charging 51.0 mA N/A Alarm with Relay 50.0 mA or 110...