Table of Contents:

  • Page 2 – Johnson Controls Unitary Products; DIMENSIONS & DUCT CONNECTION DIMENSIONS; Dimensions
  • Page 3 – COOLING CAPACITY; Models; For notes see Page 4.
  • Page 5 – APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM
  • Page 9 – TYPICAL APPLICATIONS; TXV Kits; - TXV kits are available for “Flex-coil” applications and; LIMITATIONS; Voltage limits are as follows:; Air Handler Voltage; Entering Air Temperature Limits
  • Page 10 – TYPICAL THERMOSTAT CONNECTION
  • Page 12 – AIR FLOW; NA
  • Page 14 – Copyright
Loading the manual

TECHNICAL GUIDE

SINGLE PIECE STANDARD ECM
AIR HANDLERS

FOR USE WITH SPLIT-SYSTEM
COOLING & HEAT PUMPS

MODELS: AHE18 THRU 60*

Due to continuous product improvement,
specifications are subject to change without notice.

Visit us on the web at:

www.york.com

Additional rating information can be found at:

www.ahridirectory.org

WARRANTY

Standard 5-year limited parts warranty.

Extended 10-year limited parts warranty when product is
registered online within 90 days of purchase for replace-
ment or closing for new home construction.

ISO 9001

Certified Quality

Management System

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

680210-YTG-B-0311

DESCRIPTION

The Air Handler line offers the ultimate in comfort, sound and
application flexibility. The air handler is shipped ready to be
installed in upflow, horizontal left or right position, with minor
adjustments. No special kits are required to install this deluxe
product.

All JCI Unitary Products air handlers and coils use a TXV to pro-
vide our customers with the optimum performance and refriger-
ant control. Air handlers are shipped with “Flex-coils” without a
factory installed metering device. For added flexibility, an R-22
or R-410A TXV or orifice can be field installed to meet your
refrigerant choice.

FEATURE

Thermal Expansion Valve

- Provides the ultimate refrigerant

control required for today’s high efficient product. The UPG bolt-
on TXV provides easy installation to convert the air handler to
the required refrigerant, which is a true bolt-on design that does
not require brazing to replace or install.

Insulated Cabinet

- All air handler cabinets are thermally insu-

lated with 3/4” foil faced insulation to prevent sweating.

Factory Sealed -

Achieves 2% or less total airflow leakage rate

at duct blaster field test conditions for system airflow verifica-
tion.

Durable Finish Inside and Out

- Air handler casings are made

of pre-painted galvanized steel which provides a better paint to
steel bond that resists corrosion and rust creep. All internal coil
sheet metal parts are made of G60 galvanized or prepainted
G30 galvanized.

Filters -

All models have internal filter racks provided for use

with 1” thick standard size filters.

Electric Heat Kits -

New 6HK series of field installed electric

heat kits are available for installation friendly and easy service
applications. These 6HK kits are unique to these new models.

High Efficiency Blowers -

All models use high efficiency

brushless DC motors to provide cooling SEER rating enhance-
ment.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Johnson Controls Unitary Products; DIMENSIONS & DUCT CONNECTION DIMENSIONS; Dimensions

2 Johnson Controls Unitary Products 680210-YTG-B-0311 DIMENSIONS & DUCT CONNECTION DIMENSIONS J D BlowerCompartment Circuit Breaker Panel Drain Pan Connectionsfor Horizontal Applications RefrigerantConnections Drain Connections for Upflow Applications 7-11/32” B A K C 1-1/2” Top Outlet Dimension...

Page 3 - COOLING CAPACITY; Models; For notes see Page 4.

Johnson Controls Unitary Products 3 680210-YTG-B-0311 COOLING CAPACITY Models Rated CFM Entering Air °F (Dry/Wet Bulb) MBH@ Evaporator Temperature and Corresponding Pressure °F/PSIG 35/61.5 40/68.5 45/76.0 50/84.0 FULL-CASED “A” TYPE MULTI-POSITION AHE18B3XH21 610 72 37.9 33.7 28.3 23.3 67 31.8 27.0...

Page 5 - APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM

Johnson Controls Unitary Products 5 680210-YTG-B-0311 APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM % Of Rated Airflow (CFM) 80% 90% 100% 110% 120% Capacity Factor 0.96 0.98 1.00 1.02 1.03 PHYSICAL & ELECTRICAL DATA - COOLING ONLY (60 Hz) Models AHE18B AHE24B AHE30B AHE36C AHE42D AHE48D AHE60D ...

Other York Models