Tripp Lite APSINT2012 - Manual
Tripp Lite APSINT2012 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Inverter
Battery Qty.
Battery Type
(Total Amp Hours, Voltage)
400W
600W
800W
1000W
1200W
1400W
1600W
1800W
2000W
APSINT2012
1
12V 75AH* (or 75AH @ 12VDC total)
84
52
36
28
22
18
15
12
11
APSINT2012
2
12V 75AH* (or 150AH @ 12VDC total)
192
122
87
67
53
43
36
31
27
APSINT2012
3
12V 75AH* (or 225AH @ 12VDC total)
306
197
142
109
88
72
61
52
46
APSINT2012 Estimated Runtime
Load in Watts
APSINT2012
3
12V 75AH (or 225AH @ 12VDC total)
306
197
142
109
88
72
61
52
46
APSINT2012
4
12V 75AH* (or 300AH @ 12VDC total)
420
274
199
154
125
103
87
75
65
APSINT2012
5
12V 75AH* (or 375AH @ 12VDC total)
535
351
257
200
163
135
114
98
86
APSINT2012
6
12V 75AH* (or 450AH @ 12VDC total)
649
429
316
247
201
167
142
123
108
APSINT2012
7
12V 75AH* (or 525AH @ 12VDC total)
763
507
375
294
240
200
170
147
130
APSINT2012
8
12V 75AH* (or 600AH @ 12VDC total)
875
585
434
342
280
233
199
172
152
APSINT2012
9
12V 75AH* (or 675AH @ 12VDC total)
988
662
493
389
319
267
228
198
174
APSINT2012
10
12V 75AH* (or 750AH @ 12VDC total)
1099
740
552
437
359
300
257
223
197
APSINT2012
11
12V 75AH* (or 825AH @ 12VDC total)
1209
817
611
484
399
334
286
249
220
APSINT2012
12
12V 75AH* (or 900AH @ 12VDC total)
1319
893
669
532
438
368
315
275
243
APSINT2012
13
12V 75AH* (or 975AH @ 12VDC total)
1428
969
728
579
478
401
345
301
266
APSINT2012
14
12V 75AH* (or 1050AH @ 12VDC total)
1536
1045
786
626
518
435
374
327
290
APSINT2012
15
12V 75AH* (or 1125AH @ 12VDC total)
1643
1121
844
674
558
469
404
353
313
APSINT2012
16
12V 75AH* (or 1200AH @ 12VDC total)
1749
1196
902
721
597
503
433
379
336
All runtime values are in minutes.
*IMPORTANT
NOTES
‐
Battery set
must
be
professionaly
configured
to
12VDC.
See
manual.
Tripp
Lite
part
number
"98
‐
121"
is
a
single
12V
75AH
sealed
lead
acid
battery.
All
wiring
and
required
fusing
is
user
supplied.
All
runtimes
are
based
on
non
‐
inductive
continuous
loading.
Runtime
is
subject
to
capacity
degradation
over
time.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.