Page 2 - Introduction; It’s Hard To Stop A Trane.
RT-PRC005-EN © 2004 American Standard Inc. All rights reserved Introduction Packaged RooftopAir Conditioners Through the years, Trane has designedand developed the most complete line ofPackaged Rooftop products available inthe market today. Trane was the first tointroduce the Micro—microelectronicun...
Page 3 - Contents; Model Number Description
3 RT-PRC005-EN Contents Introduction Features and Benefits Application Considerations Selection Procedure Model Number Description General Data Performance Data Cooling PerformanceFan PerformanceHeating Performance Controls Electric Power Dimension and Weights Mechanical Specifications 2 4 11 12 14 ...
Page 5 - Quality and Reliability; —prevents the unit from short cycling,; ReliaTel Makes Testing Easy; ReliaTelTM
5 RT-PRC005-EN Easy to Install, Service andMaintain Because today’s owners are very cost-conscious when it comes to service andmaintenance, the Trane Precedent wasdesigned with direct input from servicecontractors. This valuable informationhelped to design a product that would getthe serviceman off ...
Page 8 - Rigorous Testing; VariTracTM
8 RT-PRC005-EN Unit Cabinet The compact cabinet with roundedcorners takes up less room and is lesscostly to ship. The beveled and ribbed topis not only aesthetically pleasing, it isdesigned to prevent water from pooling. VariTrac When Trane’s changeover VAV Systemfor light commercial applications is...
Page 9 - Easy to Install; The units ship in a downflow
9 RT-PRC005-EN Easy to Install Convertible Units – The units ship in a downflow configuration. They can be easilyconverted to horizontal by simplymoving two panels. – Units come complete with horizontal duct flanges so the contractor doesn’thave to field fabricate them. These ductflanges are a time ...
Page 10 - Added Efficiency; Convenience Outlet
10 RT-PRC005-EN Through the Base Electrical withDisconnect Switch Factory installed 3-pole, molded case,disconnect switch with provisions forthrough the base electrical connectionsare available. This option is available onall downflow models. Through the Base Utilities Access An electrical service e...
Page 12 - Air Delivery Selection
12 RT-PRC005-EN Cooling Capacity Step 1 Calculate the building’s total and sensiblecooling loads at design conditions. Usethe Trane calculation methods or anyother standard accepted method. Factors used in unit selection: A Total Cooling Load: 59 MBh B Sensible Cooling Load: 40 MBh C Airflow: 2000 c...
Page 13 - SA; Dehumidification Selection; Plot on psychrometric chart.
13 RT-PRC005-EN MA' MA' SA' SA' RA' RA' OA OA OA OA RA' 68°F DB,67°F WB 75°F DB,52% RH MA' 72.2°F DB65°F WB SA' 47°F DB SA SA REHEAT SA 73°F DB SelectionProcedure Dehumidification Selection Typical 10 ton THC120A2000 cfm Total Supply airflow800 cfm Outside Air (40%)1200 cfm Return Air0.41” External ...
Page 15 - Standard Efficiency; Table GD – 1 — General Data
15 RT-PRC005-EN GeneralData (3 - 5 Ton) Standard Efficiency Table GD – 1 — General Data 3 Ton Convertible Units 4 Ton Convertible Units 5 Ton Convertible Units TSC036A1, A3, A4, AW TSC048A1 TSC048A3, A4, AW TSC060A1 TSC060A3, A4, AW TSC060AK Cooling Performance 1 Gross Cooling Capacity 37,400 50,300...
Page 16 - Table GD – 2— General Data
16 RT-PRC005-EN GeneralData (6 - 10 Ton) Standard Efficiency Table GD – 2— General Data 6 Ton 7½ Ton 8½ Ton 10 Ton Convertible Units Convertible Units Convertible Units Convertible Units TSC072A3, A4, AW, AK TSC090A3,A4,AW, AK TSC092A3, A4, AW TSC102A3, A4, AW, AK TSC120A3, A4, AW, AK Cooling Perfor...
Page 17 - High Efficiency; Table GD – 3 — General Data
17 RT-PRC005-EN GeneralData (3 - 5 Ton) High Efficiency Table GD – 3 — General Data 3 Ton 4 Ton 5 Ton Convertible Units Convertible Units Convertible Units THC036A1,A3,A4,AW THC048A1,A3,A4,AW THC060A1 THC060A3,A4,AW Cooling Performance 1 Gross Cooling Capacity 38,000 49,800 62,100 62,400 SEER / EER ...
Page 18 - Table GD – 4— General Data
18 RT-PRC005-EN GeneralData (6 - 10 Ton) High Efficiency Table GD – 4— General Data 6 Ton 7½ Ton 8½ Ton 10 Ton Convertible Units Convertible Units Convertible Units Convertible Units THC072A3, A4, AW THC092A3, A4, AW THC102A3, A4. AW THC120A3, A4, AW Cooling Performance 1 Gross Cooling Capacity 73,0...
Page 19 - Ton Single/Three Phase; Ton Single Phase
19 RT-PRC005-EN PerformanceData (3, 4 Ton) Standard Efficiency Table PD-1 — Gross Cooling Capacities (MBH) 3 Ton Single/Three Phase TSC036A1, A3, A4, AW Ambient Temperature (F) 85 95 105 115 Enter.Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH ...
Page 20 - Ton Single/Three Phase; Ton Three Phase
20 RT-PRC005-EN (4, 5 Ton) Standard Efficiency PerformanceData Table PD-4 — Gross Cooling Capacities (MBH) 5 Ton Single/Three Phase TSC060A1, A3, A4, AW, AK Ambient Temperature (F) 85 95 105 115 Enter.Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC ...
Page 21 - 1⁄2 Ton Three Phase Single Compressor TSC090A3, A4, AW, AK
21 RT-PRC005-EN PerformanceData (6, 7½ Ton) Standard Efficiency Table PD-5 — Gross Cooling Capacities (MBH) 6 Ton Three Phase TSC072A3, A4, AW, AK Ambient Temperature (F) 85 95 105 115 Enter.Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MB...
Page 22 - 1⁄2 Ton Three Phase Dual Compressors TSC092A3, A4, AW
22 RT-PRC005-EN PerformanceData (7½, 8½ Ton) Standard Efficiency Table PD-7 — Gross Cooling Capacities (MBH) 7½ Ton Three Phase Dual Compressors TSC092A3, A4, AW Ambient Temperature (F) 85 95 105 115 Enter.Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH...
Page 30 - Ton Three Phase THC072A3, A4, AW– Standard Refrigeration Option
30 RT-PRC005-EN (6 Ton) High Efficiency PerformanceData Table PD-17 — Gross Cooling Capacities (MBH) 6Ton Three Phase THC072A3, A4, AW– Standard Refrigeration Option Ambient Temperature (F) 85 95 105 115 Enter.Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC...
Page 31 - 1⁄2 Ton Three Phase THC092A3, A4, AW– Standard Refrigeration Option
31 RT-PRC005-EN Table PD-18 — Gross Cooling Capacities (MBH) 7½ Ton Three Phase THC092A3, A4, AW– Standard Refrigeration Option Ambient Temperature (F) 85 95 105 115 Enter.Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH S...
Page 32 - or TXV Option
32 RT-PRC005-EN (7½ Ton) High Efficiency PerformanceData Table PD-19 — Gross Cooling Capacities (MBH) 7½ Ton Three Phase THC092A3, A4, AW – Dehumidification (Hot Gas Reheat) or TXV Option Ambient Temperature (F) 85 95 105 115 Enter.Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 ...
Page 33 - 1⁄2 Ton Three Phase THC102A3, A4, AW– Standard Refrigeration Option
33 RT-PRC005-EN PerformanceData (8½ Ton) High Efficiency Table PD-20— Gross Cooling Capacities (MBH) 8½ Ton Three Phase THC102A3, A4, AW– Standard Refrigeration Option Ambient Temperature (F) 85 95 105 115 Enter.Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH S...
Page 35 - 0 Ton Three Phase THC120A3, A4, AW– Standard Refrigeration Option
35 RT-PRC005-EN Table PD-22 — Gross Cooling Capacities (MBH) 10 Ton Three Phase THC120A3, A4, AW– Standard Refrigeration Option Ambient Temperature (F) 85 95 105 115 Enter.Dry Entering Wet Bulb (F) CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH S...
Page 37 - Table PD-24— Direct Drive Evaporator Fan Performance
37 RT-PRC005-EN PerformanceData (3, 4, 5 Ton) Standard Efficiency Table PD-24— Direct Drive Evaporator Fan Performance 3, 4 and 5 Ton TSC036A, TSC048A, TSC060A External Static Pressure (Inches of Water) & Motor Power (Bhp) 1 Standard Motor Oversized Motor Unit High Speed Low Speed High Speed Low...
Page 38 - Table PD-25 — Continued
38 RT-PRC005-EN (3 Ton) Standard Efficiency PerformanceData For Standard Evaporator Fan Speed (RPM), reference Table PD-56.Notes:Data includes pressure drop due to standard filters and wet coils.No accessories or options are included in pressure drop data.Refer to Table PD-61 to determine additional...
Page 39 - Table PD-27 — Continued
39 RT-PRC005-EN (4 Ton) Standard Efficiency PerformanceData Table PD-27 — Belt Drive Evaporator Fan Performance — 4 Ton — TSC048A3,A4,AW — Downflow Airflow External Static Pressure (Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP ...
Page 40 - Table PD-29 — Continued
40 RT-PRC005-EN (5 Ton) Standard Efficiency PerformanceData For Standard Evaporator Fan Speed (RPM), reference Table PD-56.Notes:Data includes pressure drop due to standard filters and wet coils.No accessories or options are included in pressure drop data.Refer to Table PD-61 to determine additional...
Page 41 - Table PD-31 — Continued
41 RT-PRC005-EN PerformanceData (6 Ton) Standard Efficiency For Standard Evaporator Fan Speed (RPM), reference Table PD-56.Notes:Data includes pressure drop due to standard filters and wet coils.No accessories or options are included in pressure drop data.Refer to Table PD-61 to determine additional...
Page 42 - Table PD-33 — Continued
42 RT-PRC005-EN (6 Ton) Standard Efficiency PerformanceData For Standard Evaporator Fan Speed (RPM), reference Table PD-56.Notes:Data includes pressure drop due to standard filters and wet coils.No accessories or options are included in pressure drop data.Refer to Table PD-61 to determine additional...
Page 43 - Table PD-35 — Continued; Table PD-36 — Continued
43 RT-PRC005-EN (7½ Ton) Standard Efficiency PerformanceData For Standard Evaporator Fan Speed (RPM), reference Table PD-56.Notes:Data includes pressure drop due to standard filters and wet coils.No accessories or options are included in pressure drop data.Refer to Table PD-61 to determine additiona...
Page 44 - Table PD-37 — Continued
44 RT-PRC005-EN (8½ Ton) Standard Efficiency PerformanceData For Standard Evaporator Fan Speed (RPM), reference Table PD-56.Notes:Data includes pressure drop due to standard filters and wet coils.No accessories or options are included in pressure drop data.Refer to Table PD-61 to determine additiona...
Page 45 - Table PD-40 — Continued
45 RT-PRC005-EN (10 Ton) Standard Efficiency PerformanceData For Standard Evaporator Fan Speed (RPM), reference Table PD-56.Notes:Data includes pressure drop due to standard filters and wet coils.No accessories or options are included in pressure drop data.Refer to Table PD-61 to determine additiona...
Page 46 - Table PD-41— Direct Drive Evaporator Fan Performance
46 RT-PRC005-EN PerformanceData (3, 4, 5 Ton) High Efficiency Table PD-41— Direct Drive Evaporator Fan Performance — 3, 4, and 5 Ton — THC036A, THC048A, THC060A External Static Pressure (Inches of Water) & Motor Power (Bhp) 1 Standard Motor Oversized Motor Unit High Speed Low Speed High Speed Lo...
Page 47 - Table PD-42 — Continued; Table PD-43— Continued
47 RT-PRC005-EN PerformanceData (3 Ton) High Efficiency For Standard Evaporator Fan Speed (RPM), reference Table PD-56.Table includes Dehumidification (Hot Gas Reheat Option). *Unit applications below 960 CFM• Electric heaters restricted on applications below 960 CFM. • Dehumidification (Hot Gas Reh...
Page 48 - Table PD-44 — Continued; Table PD-45 — Continued
48 RT-PRC005-EN PerformanceData (4 Ton) High Efficiency For Standard Evaporator Fan Speed (RPM), reference Table PD-56.Table includes Dehumidification (Hot Gas Reheat Option). *Unit applications below 1280 CFM• Electric heaters restricted on applications below 1280 CFM. • Dehumidification (Hot Gas R...
Page 49 - Table PD-47 — Continued; Table PD-46 — Continued
49 RT-PRC005-EN PerformanceData (5 Ton) High Efficiency Table PD-47 — Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Horizontal Airflow External Static Pressure (Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RP...
Page 50 - Table PD-48 — Continued; Table PD-49 — Continued
50 RT-PRC005-EN (6 Ton) High Efficiency PerformanceData Table PD-48— Belt Drive Evaporator Fan Performance — 6 Ton — THC072A3,A4,AW* — Downflow Airflow— Standard Refrigeration System External Static Pressure (Inches of Water) .10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 CFM RPM BHP RPM BHP RPM BHP RPM B...
Page 51 - Table PD-50— Continued
51 RT-PRC005-EN (7½ Ton) High Efficiency PerformanceData For Standard Evaporator Fan Speed (RPM), reference Table PD-56.Table includes Dehumidification (Hot Gas Reheat Option). *Unit applications below 2400 CFM• Electric heaters restricted on applications below 2400 CFM. • Dehumidification (Hot Gas ...
Page 52 - Table PD-51 — Continued
52 RT-PRC005-EN (7½ Ton) High Efficiency PerformanceData For Standard Evaporator Fan Speed (RPM), reference Table PD-56.Table includes Dehumidification (Hot Gas Reheat Option). *Unit applications below 2400 CFM• Electric heaters restricted on applications below 2400 CFM. • Dehumidification (Hot Gas ...
Page 53 - Table PD-52 — Continued
53 RT-PRC005-EN (8½ Ton) High Efficiency PerformanceData For Standard Evaporator Fan Speed (RPM), reference Table PD-56.Table includes Dehumidification (Hot Gas Reheat Option). *Unit applications below 2720 CFM• Electric heaters restricted on applications below 2720 CFM. • Dehumidification (Hot Gas ...
Page 54 - Table PD-53 — Continued
54 RT-PRC005-EN (8½ Ton) High Efficiency PerformanceData For Standard Evaporator Fan Speed (RPM), reference Table PD-56.Table includes Dehumidification (Hot Gas Reheat Option). *Unit applications below 2720 CFM• Electric heaters restricted on applications below 2720 CFM. • Dehumidification (Hot Gas ...
Page 55 - Table PD-54 — Continued
55 RT-PRC005-EN (10 Ton) High Efficiency PerformanceData For Standard Evaporator Fan Speed (RPM), reference Table PD-56.Table includes Dehumidification (Hot Gas Reheat Option). *Unit applications below 3200 CFM• Electric heaters restricted on applications below 3200 CFM. • Dehumidification (Hot Gas ...
Page 56 - Table PD-55 — Continued
56 RT-PRC005-EN (10 Ton) High Efficiency PerformanceData For Standard Evaporator Fan Speed (RPM), reference Table PD-56.Table includes Dehumidification (Hot Gas Reheat Option). *Unit applications below 3200 CFM• Electric heaters restricted on applications below 3200 CFM. • Dehumidification (Hot Gas ...
Page 59 - Table PD-62— Auxiliary Electric Heat Capacity
59 RT-PRC005-EN Table PD-62— Auxiliary Electric Heat Capacity Total 2 Stage1 Stage 2 Unit kW MBH No. of kW MBH kW MBH Tons Model No. Input 1 Output 1 Stages Input 1 Output 1 Input 1 Output 1 5.00 17.07 1 5.00 17.07 — — T*C036A1 10.00 34.14 2 5.00 17.07 5.00 17.07 13.80 47.11 2 8.80 30.04 5.00 17.07 ...
Page 61 - Table PD-66— Hot Gas Reheat Temperature Rise
61 RT-PRC005-EN PerformanceData Table PD-66— Hot Gas Reheat Temperature Rise 3 Leaving Evaporator Dry Bulb [F] Tons SCFM 35 40 45 50 55 60 65 600 20.3 20.0 19.6 19.2 18.8 18.4 18.0 720 19.4 19.1 18.7 18.3 17.9 17.6 17.2 840 18.5 18.2 17.9 17.5 17.1 16.7 16.3 3 960 17.6 17.3 17.0 16.6 16.2 15.8 15.5 ...
Page 62 - Controls; ReliaTelTM Controlled Units; Zone Sensors; are the building; Manual Changeover; The CO
62 RT-PRC005-EN Controls ReliaTel™ Controlled Units Zone Sensors are the building occupant’s comfort control devices forPrecedent™ units with the Micro control: Manual Changeover Heat, Cool or Off System Switch. FanAuto or Off Switch.One temperaturesetpoint lever. Manual/Automatic Changeover Auto, H...
Page 64 - Table ED-1 — Unit Wiring — Standard Efficiency
64 RT-PRC005-EN ElectricalData Table ED-1 — Unit Wiring — Standard Efficiency Optional Standard Indoor Fan Motor Oversize Indoor Fan Motor Belt Drive Indoor Fan Motor 2 Unit Minimum Maximum Fuse Minimum Maximum Fuse Minimum Maximum Fuse Unit Operating Circuit Size or Maximum Circuit Size or Maximum ...
Page 65 - Table ED-2 — Unit Wiring — High Efficiency
65 RT-PRC005-EN ElectricalData (HighEfficiency) Table ED-2 — Unit Wiring — High Efficiency Optional Standard Indoor Fan Motor Oversize Indoor Fan Motor Belt Drive Indoor Fan Motor 2 Unit Minimum Maximum Fuse Minimum Maximum Fuse Minimum Maximum Fuse Unit Operating Circuit Size or Maximum Circuit Siz...
Page 68 - 75 Volts Three Phase
68 RT-PRC005-EN ElectricalData Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) — 575 Volts — Standard Efficiency, continued Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size or Max Fuse Size or Tons With Model No. kW Rating 1 Stages MCA Max ...
Page 71 - 60 Volts Three Phase
71 RT-PRC005-EN ElectricalData (HighEfficiency) Table ED-5 — Unit Wiring With Electric Heat (Single Point Connection) — 460 Volts — High Efficiency, continued Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size or Max Fuse Size or Tons With Model No. kW Rating 1 St...
Page 76 - Table ED-11— Electrical Characteristics — Power Exhaust
76 RT-PRC005-EN ElectricalData T able ED-10 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency Compressor Motors Condenser Fan Motors Unit Amps 1 Amps 1 Tons Model No. No. Volts Phase HP 2 RPM RLA LRA No. Phase HP FLA LRA THC036A1 1 208-230 1 2.8 3450 16...
Page 77 - Zone Sensors — Typical Number Of Wires; Programmable Night Setback with
77 RT-PRC005-EN JobsiteConnections For specific wiring information, see the installation instructions.All wiring except power wires is low voltage.All customer supplied wiring to be copper and must conform to applicable electrical codes (such as NEC or CEC) and local electrical codes. Wiring shown d...
Page 78 - All dimensions are in inches/millimeters.; Tons High Efficiency
78 RT-PRC005-EN DimensionalData All dimensions are in inches/millimeters. 4 1/4" 108 MM 23 9/16" 598 MM 69 7/8" 1775 MM 42 1/4" 1073 MM 9 5/8" 244 MM 5 5/8" 143 MM 5 9/16" 141 MM 7 5/8" 194 MM 44 1/4" 1124 MM 36 1/4" 921 MM 5 Tons High Efficiency 4 1/4" 10...
Page 79 - Horizontal Airflow Supply/Return
79 RT-PRC005-EN DimensionalData All dimensions are in inches/millimeters. Horizontal Airflow Supply/Return Downflow Airflow Supply/ReturnThrough the Base Utilities Unit Clearance and Roof Opening (3-5 Tons)
Page 80 - All dimensions are in inches.; Downflow Duct Connections — Field Fabricated
80 RT-PRC005-EN DimensionalData All dimensions are in inches. Downflow Duct Connections — Field Fabricated (3-5 Tons)
Page 82 - -10 Tons — Horizontal Airflow Supply and Return
82 RT-PRC005-EN (6-10 Tons) DimensionalData All dimensions are in inches. 6-10 Tons — Downflow Airflow Supply and Return;Through the Base Utilities 6-10 Tons — Horizontal Airflow Supply and Return 6-10 Tons — Unit Clearance and RoofOpening Supply Return
Page 83 - -10 Tons — Roof Curb
83 RT-PRC005-EN (6-10 Tons) DimensionalData All dimensions are in inches. 6-10 Tons — Roof Curb 857 857 ALL FLANGES 1 1/4” (31 MM) 6-10 Tons — Downflow DuctConnections — Field Fabricated
Page 84 - Economizer , Manual or Motorized Fresh Air Damper; See Page 79 for Through the Base Utilities Information; Barometric Relief Damper Hood
84 RT-PRC005-EN (3-5 Tons Options/Accessories) DimensionalData All dimensions are in inches. Economizer , Manual or Motorized Fresh Air Damper See Page 79 for Through the Base Utilities Information Barometric Relief Damper Hood Swing Diameter for Hinged Doors Option 17 7/8" (454 MM) 16" (406...
Page 85 - -10 Tons — Power Exhaust
85 RT-PRC005-EN DimensionalData (6-10 Tons Options/Accessories) All dimensions are in inches. 6-10 Tons — Economizer and BarometricRelief Damper Hoods 6-10 Tons — Power Exhaust 6-10 Tons — Swing Diameter for HingedDoor(s) Option See Page 82 for Through the Base Utilities Information 21 3/8" 543 ...
Page 86 - Weights
86 RT-PRC005-EN Weights Table W-1— Maximum Unit and Corner Weights (Lbs) And Center of Gravity Dimensions (In.) Unit Maximum Weights (Lbs) Corner Weights (Lbs) 1 Center of Gravity (In.) Tons Model No. Shipping 2 Net A B C D Length Width TSC036A 501 409 132 104 79 94 31 19 3 THC036A 518 426 139 108 8...
Page 87 - inch high downflow
87 RT-PRC005-EN MechanicalSpecifications General The units shall be convertible airflow. Theoperating range shall be between 115°Fand 0°F in cooling as standard from thefactory for units with microprocessorcontrols. Operating range for units withelectromechanical controls shall bebetween 115°F and 4...
Page 88 - Factory Installed Options
88 RT-PRC005-EN Factory Installed Options Black Epoxy Pre-Coated Coils The black epoxy coils have a thermosetvinyl coating that is bonded to thealuminum fin stock prior to the fin-stamping process. The pre-coated coilsare an economical option for protection inmildly corrosive environments. Dehumidif...
Page 89 - The disconnect switch will be sized
89 RT-PRC005-EN MechanicalSpecifications Through the Base Electrical with CircuitBreaker This option is a thermal magnetic, moldedcase, HACR Circuit Breaker withprovisions for through the base electricalconnections. The circuit breaker will beinstalled in a water tight enclosure in theunit with acce...
Page 90 - Field Installed Options
90 RT-PRC005-EN MechanicalSpecifications Field Installed Options CO 2 Sensing The CO 2 sensor shall have the ability to monitor space occupancy levels withinthe building by measuring the parts permillion of CO 2 (Carbon Dioxide) in the air. As the CO 2 levels increase, the outside air damper modulat...