Page 2 - Important Information
Page ii Important Information Misuse of this equipment can result in property damage or human injury. Because controlled system applications vary widely, you should satisfy yourself as to the acceptability of this equipment for your intended purpose. In no event will Toshiba Corporation be responsib...
Page 3 - Safety Precautions; Hazard Classifications; WARNING; CAUTION
Page iii Safety Precautions This application guide is prepared for users of Toshiba programmable controller PROSEC T2-Series and EX100 Series (hereafter called T2). Read this guide and your PLC's manual thoroughly to use the PLC system safely. Hazard Classifications In this guide, the following two ...
Page 4 - About This Guide
Page iv About This Guide This guide describes how to setup and use the Toshiba EX10-MML11 Modbus module. When used in a Modbus network, the EX10-MML11 module allows any Modbus master to write to/read from the registers in an EX100 or T2 PLC using standard Modbus RTU protocol.
Page 5 - Contents
Page v Contents Important Information................................................................................................................ ii Safety Precautions................................................................................................................... iii About Thi...
Page 7 - Additional References
Page 1 1. Overview The Modbus module (ML11) is used to connect T2E, T2N, or EX100 PLCs to a Modbus Master. The addition of the EX10-MML11 (MODBUS Module) allows the T2E, T2N or EX100 PLC to communicate via standard MODBUS RTU protocol. This allows quick and easy access to the PLC registers by a stan...
Page 8 - System Configuration; to 1 Configuration; T2E PLC; Modbus Module; Modbus Master
Page 2 2. System Configuration From 1 to 32 T2E or T2N PLCs can be connected to a Modbus master using the Modbus module. 1 to 1 Configuration T2 Minimum Configuration T2E PLC RS485 Power Supply T2E CPU Modbus Module I/O Modules Modbus Master 1. Higher Level PLC 2. Distributed Control System 3. Compu...
Page 9 - to N Configuration; Up to 32 Stations
Page 3 1 to N Configuration Modbus Master 1. Higher Level PLC 2. Distributed Control System 3. Computer with SCADA or HMI Program RS485 T2 Maximum Configuration 1 Main Unit 3 Exp. Units Up to 32 Stations For high-speed data transfer, one of Toshiba’s Tosline Data Highway modules is recommended.
Page 10 - External Features and Switch Settings
Page 12 - Modbus Module Operation; MODBUS FUNCTION CODE
Page 6 5. Modbus Module Operation 5.1. Modbus Commands When a MODBUS command is used, the Modbus module translates it to the corresponding T2 register access protocol. MODBUS FUNCTION CODE T2 COMMAND 01 Read Coil Status DR Read Device/Register 02 Read Input Status DR Read Device/Register 03 Read Hol...
Page 13 - Modbus Data Types and T2 Register Mapping; Data Type
Page 7 5.2. Modbus Data Types and T2 Register Mapping This table shows how the different Modbus data types are mapped into T2 registers. In other words, a Modbus master would reference the following Modbus register ranges to access the corresponding T2 PLC registers. For example, Modbus Holding Regi...
Page 14 - Modbus – T2 Address mapping Example:
Page 8 Modbus – T2 Address mapping Example: Modbus Address T2 Address T2 Data Type 30000 XW000 Input Register 40001 YW001 Output Register 44352 D0000 Data Register Note: When dealing with I/O registers, make sure that the Modbus master is attempting to access only the I/O points that physically exis...
Page 15 - Modbus Module Setup; Station number
Page 9 6. Modbus Module Setup The Toshiba Modbus module has been used reliably as a Modbus slave for several years. First it was used on Toshiba’s EX100 Series PLCs and now on the T2 Series PLCs. Before it can function as intended however, all the DIP switches must be properly set and all wiring con...
Page 17 - OFF; ODD; EVEN; ON; ASY and DLY switches:
Page 11 Parity Check: Select the parity check as odd, even or none. Use switches 7 and 8 to set the parity. PARITY PEN (7) EVN (8) NONE OFF ---- ODD ON OFF EVEN ON ON ASY and DLY switches: The ASY and DLY switches are not used on the EX10-MML11, and should be set to the “Off” position.
Page 20 - Wiring Connection to the Modbus Module
Page 14 6.2. Wiring Connection to the Modbus Module Sometimes it is necessary to convert from the standard RS485 to RS232 for connection to a Personal Computer. The wiring between the Modbus module and the converter must be set as follows: RS485 Converter Modbus Module TXA RXA RXA TXA TXB RXB RXB TX...
Page 21 - CPU Setup for the Modbus Module; must be set to
Page 15 7. CPU Setup for the Modbus Module Two lines of ladder logic are necessary to configure a T2 CPU for use with the Modbus module. 1 Communications Priority: To insure uninterrupted communications between the CPU and the Modbus module, the communications priority bit S0158 must be set ON. 2. I...
Page 22 - Trouble Shooting; RXD LED; : Flashes when the Modbus master sends a message to the EX10; TXD LED; : Flashes when that specific EX10-MML11 responds to the master.; If the LED indicators are not flashing, check the following:
Page 16 8. Trouble Shooting The communication status LEDs can be used to verify correct operation of the Modbus module. During normal operation, the LED indicators flash as follows: • RXD LED : Flashes when the Modbus master sends a message to the EX10 -MML11. On a multi slave network, this can also...
Page 23 - Additional References; Instruction Manual - EC300 Series Controller – ECBUS Transmission; Modbus Protocol Reference Guide
Page 17 9. Additional References Toshiba Corporation, Instruction Manual - EC300 Series Controller – ECBUS Transmission Interface Module – ML11 . 6F8A0613 4 th ed. Feb 1995. Tokyo, Japan. Toshiba Corporation, Computer Link Function Operation Manual . UM-TS03-E008, 3 rd ed. Aug. 1977. Tokyo, Japan. G...