  • Page 2 – SITRANS T measuring instruments for temperature; Transmitters for rail mounting; SITRANS TW; Integration; System configuration; Technical specifications; Input
  • Page 3 – Output
  • Page 5 – Digital error
  • Page 6 – Ordering examples; • Operating data already set in factory to default values:; der code
  • Page 7 – Further designs; Selection and Ordering data; Accessories
  • Page 8 – List of parameterizable operating data (Order codes A
  • Page 9 – List of parameterizable operating data (Order codes F
  • Page 10 – Special operating data
  • Page 11 – Schematics; Sensor input connections
  • Page 12 – Relay output; Dimensional drawings; Connected terminals
Loading the manual

SITRANS T measuring instruments for temperature

Transmitters for rail mounting

SITRANS TW
four-wire system, universal, HART

3/38

Siemens FI 01 · 2010

3

Overview

The user-friendly transmitters for the control room

The SITRANS TW universal transmitter is a further development
of the service-proven SITRANS T for the 4-wire system in a
mounting rail housing. With numerous new functions it sets new
standards for temperature transmitters.

With its diagnostics and simulation functions the SITRANS TW
provides the necessary insight during commissioning and oper-
ation. And using its HART interface the SITRANS TW can be
conveniently adapted with SIMATIC PDM to every measurement
task.

All SITRANS TW control room devices are available in a non-
intrinsically safe version as well as in an intrinsically safe version
for use with the most stringent requirements.

Application

The SITRANS TW transmitter is a four-wire rail-mounted device
with a universal input circuit for connection to the following sen-
sors and signal sources:

• Resistance thermometers

• Thermocouple elements

• Resistance-based sensors/potentiometers

• mV sensors

• As special version:

- V sources
- Current sources

The 4-wire rail-mounted SITRANS TW transmitter wire is de-
signed for control room installation. It must not be mounted in
potentially explosive atmospheres.

All SITRANS TW control room devices are available in a non-
intrinsically safe version as well as in an intrinsically safe version
for use with the most stringent requirements.

Function

Features

• Transmitter in four-wire system with HART interface

• Housing can be mounted on 35 mm rail or 32 mm G rail

• Screw plug connector

• All circuits electrically isolated

• Output signal: 0/4 to 20 mA or 0/2 to 10 V

• Power supplies: 115/230 V AC/DC or 24 V AC/DC

• Explosion protection [EEx ia] or [EEx ib] for measurements

with sensors in the hazardous area

• Temperature-linear characteristic for all temperature sensors

• Temperature-linear characteristic can be selected for all tem-

perature sensors

• Automatic correction of zero and span

• Monitoring of sensor and cable for open-circuit and short-cir-

cuit

• Sensor fault and/or limit can be output via an optional sensor

fault/limit monitor

• Hardware write protection for HART communication

• Diagnostic functions

• Slave pointer functions

Mode of operation

The signal output by a resistance-based sensor (two-wire, three-
wire, four-wire system), voltage source, current source or ther-
mocouple is converted by the analog-to-digital converter
(1, function diagram) into a digital signal. This is evaluated in the
microcontroller (2), corrected according to the sensor character-
istic, and converted by the digital-to-analog converter (6) into an
output current (0/4 to 20 mA) or output voltage (0/2 to 10 V). The
sensor characteristics as well as the electronics data and the
data for the transmitter parameters are stored in the non-volatile
memory (3).

AC or DC voltages can be used as the power supply (13). Any
terminal connections are possible for the power supply as a re-
sult of the bridge rectifier in the power supply unit. The PE con-
ductor is required for safety reasons.

A HART modem or a HART communicator permit parameteriza-
tion of the transmitter using a protocol according to the HART
specification. The transmitter can be directly parameterized at
the point of measurement via the HART output terminals (10).

The operation indicator (4) identifies a fault-free or faulty operat-
ing state of the transmitter. The limit monitor (9) enables the sig-
naling of sensor faults and/or limit violations. In the case of a cur-
rent output, the current can be checked on a meter connected
to test socket (12).

Diagnosis and simulation functions

The SITRANS TW comes with extensive diagnosis and simula-
tion functions.

Physical values can be defined with the simulation function. It is
thus possible to check the complete signal path from the sensor
input to Inside the control system without additional equipment.
The slave pointer functions are used to record the minimum and
maximum of the plant’s process variable.

HART modem/
communicator

Current test
0/4 ... 20 mA

Output
U or I

Power
sup-
ply

unit

EEPROM

7

3

13

U

H

A

D

6

5

µC

A

12

11

10

A

D

RTD

TC

1

2

9

4

8

© Siemens AG 2009

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - SITRANS T measuring instruments for temperature; Transmitters for rail mounting; SITRANS TW; Integration; System configuration; Technical specifications; Input

SITRANS T measuring instruments for temperature Transmitters for rail mounting SITRANS TW four-wire system, universal, HART 3/39 Siemens FI 01 · 2010 3 ■ Integration System configuration Possible system configurations The SITRANS TW transmitter as a four-wire rail-mounted device can be used in a num...

Page 3 - Output

SITRANS T measuring instruments for temperature Transmitters for rail mounting SITRANS TWfour-wire system, universal, HART 3/40 Siemens FI 01 · 2010 3 Thermocouple elements Measured variable Temperature Measured range Parameterizable Measured span Min. 50 °C (32.22 °F) x 1/scaling factor Measuring r...

Page 5 - Digital error

SITRANS T measuring instruments for temperature Transmitters for rail mounting SITRANS TWfour-wire system, universal, HART 3/42 Siemens FI 01 · 2010 3 Digital error Resistance thermometer Resistance-based sensors Thermocouple elements Voltage/current sources Input Measured range Max. permissi-ble li...

Other Siemens Models