Page 2 - Systems; Introduction; Overview; Page
Systems Introduction 2/2 Siemens LV 1 · 2007 2 ■ Overview Order No. Page AS-Interface / ASIsafe ASIsafe enables the integration of safety-oriented components in an AS-Interface network, for example: • EMERGENCY-STOP pushbuttons • Protective door switches • Safety light arrays The simple wiring of AS...
Page 3 - Masters; Masters for SIMATIC
Systems Introduction 2/3 Siemens LV 1 · 2007 2 Order No. Page EMERGENCY-STOP front plate AS-Interface EMERGENCY-STOP pushbuttons • Degree of protection IP65/IP67 • EMERGENCY-STOP directly on AS-Interface using integrated modules • Metal or plastic version Your advantage: Easy direct connection of se...
Page 4 - Cabinet modules
Systems Introduction 2/4 Siemens LV 1 · 2007 2 Order No. Page AS-Interface / Slaves Slaves contain the AS-Interface electronics and connection options for sensors and actuators in the field and in the cabinet. A total of up to 62 slaves can be connected to one bus. The slaves then exchange their dat...
Page 6 - Power supply units; AS-Interface shaped cables
Systems Introduction 2/6 Siemens LV 1 · 2007 2 Order No. Page Pushbuttons Pushbuttons and indicator lights • Modular construction according to individual requirements • Metal and plastic version • A/B technology • With LEDs or incandescent lamps Your advantage: Complete 3SB3 operating system with si...
Page 7 - AS-Interface / System components and accessories; Repeater/extender and extension plug
Systems Introduction 2/7 Siemens LV 1 · 2007 2 Order No. Page AS-Interface / System components and accessories Accessories comprise tools for mounting, installation and operation as well as individual components. Repeaters (6GK1 210-0SA00) Extension plug Repeater/extender and extension plug • Extens...
Page 8 - ECOFAST System
Systems Introduction 2/8 Siemens LV 1 · 2007 2 Order No. Page ECOFAST System • Modular construction • Flexible expansion • Graded range of motor starters and frequency converters • Diagnostics capability • Communication using standardized field bus systems • Standardized connection method • Energy s...
Page 9 - Transmission technology; Operating modes; Analog value transfer
AS-Interface Introduction Transmission technology 2/9 Siemens LV 1 · 2007 2 ■ Overview AS-Interface is an open, international standard according to EN 50295 and IEC 62026-2 for process and field communica-tion. Leading manufacturers of actuators and sensors all over the world support the AS-Interfac...
Page 10 - Communication overview; System components; More information; SIMATIC C7
AS-Interface Introduction Communication overview 2/10 Siemens LV 1 · 2007 2 ■ Overview System components Numerous system components are offered for implementing the communication. The key elements of a system installation are: • Master interface modules for central control units such as SIMATIC S5 a...
Page 11 - AS-Interface specification; System limitations of AS-Interface specification; ASIsafe; lexibilit
AS-Interface Introduction AS-Interface specification 2/11 Siemens LV 1 · 2007 2 ■ Overview Technology development of the AS-Interface System limitations of AS-Interface specification Expansions of AS-Interface Specification 2.1 • AS-Interface Specification 2.1 enables the number of network stations ...
Page 12 - Selection and ordering data; Communication cycle; Selection and Ordering Data; Benefits; AS-Interface Specification
AS-Interface Introduction AS-Interface specification 2/12 Siemens LV 1 · 2007 2 AS-Interface master To be able to operate A/B slaves on an AS-Interface network you must also use master modules that meet the minimum require-ments of Specification 2.1. A/B technology is supported by the masters of the...
Page 13 - Safety is included
AS-Interface ASIsafe Introduction 2/13 Siemens LV 1 · 2007 2 ■ Overview Master information (through regular I/O transfer) Safety is included The ASIsafe concept supports the direct integration of safety-related components, such as emergency stop switches, protec-tive door switches or safety light ar...
Page 14 - AS-Interface safety monitors; The monitor comes in two expansion levels:; Basic safety monitor; with starter set of modules and basic; Expanded safety monitor; with expanded features and func-; * You can order this quantity or a multiple thereof.
AS-Interface ASIsafe AS-Interface safety monitors 2/14 Siemens LV 1 · 2007 2 ■ Overview The safety monitor is the centerpiece of ASIsafe. A safe applica-tion is configured using a PC and the safety monitor. Various ap-plication-specific operating modes can be selected for this. They include, for exa...
Page 15 - AS-Interface safety modules; K45F compact safety modules for operation in the field
AS-Interface ASIsafe AS-Interface safety modules 2/15 Siemens LV 1 · 2007 2 ■ Overview Safety modules for AS-Interface (ASIsafe modules) are available for field use in degree of protection IP67 (K20F, K45F and K60F compact modules) and for the control cabinet (S22.5F SlimLine modules) in degree of p...
Page 17 - CP 142-2 communications processors; Electronic manuals
AS-Interface Masters CP 142-2 2/17 Siemens LV 1 · 2007 2 ■ Overview • Master connection for the ET 200X distributed peripherals system to AS-Interface using 12-pole connector • Easy operation in the input/output address range of the SIMATIC ET 200X • No configuration of the CP for AS-Interface requi...
Page 18 - CP 243-2 communications processors
AS-Interface Masters CP 243-2 2/18 Siemens LV 1 · 2007 2 ■ Overview The CP 243-2 is the AS-Interface master for the innovative SIMATIC S7-200 generation. This communications processor (6GK1 243-2AX01-0AX0) supports the extended AS-Interface Specification V2.1 and performs the following functions: • ...
Page 19 - CP 343-2 communications processors
AS-Interface Masters CP 343-2 2/19 Siemens LV 1 · 2007 2 ■ Overview The CP 343-2 is the AS-Interface master for the SIMATIC S7-300 programmable controller and the ET 200M distributed I/O sta-tion. The communications processor performs the following functions: • Connection of up to 62 AS-Interface sl...
Page 20 - CP 343-2 P communications processors
AS-Interface Masters CP 343-2 P 2/20 Siemens LV 1 · 2007 2 ■ Overview The CP 343-2 P is the AS-Interface master for the SIMATIC S7-300 programmable controller and the ET 200M distributed I/O station. The communications processor performs the follow-ing functions: • Supports the configuration of the ...
Page 21 - Routers
AS-Interface Routers IE/AS-i LINK PN IO 2/21 Siemens LV 1 · 2007 2 ■ Overview • Compact router between Industrial Ethernet (PROFINET IO-Device) and AS-Interface • Single and double AS-Interface master (according to AS-Interface Specification V3.0) for connection of 62 AS-Interface slaves • Performan...
Page 22 - as dual master; PROFINET
AS-Interface Routers IE/AS-i LINK PN IO 2/22 Siemens LV 1 · 2007 2 Integration of AS-Interface on PROFIBUS through IE/AS-i LINK PN IO as single/double master Using an upstream IWLAN client module, e.g. SCALANCE W746-1PRO, an AS-Interface line can be integrated in the PROFINET world by wireless means...
Page 23 - Accessories; Radio cell 2; Interface
AS-Interface Routers IE/AS-i LINK PN IO 2/23 Siemens LV 1 · 2007 2 Wireless communication between Industrial Ethernet and AS-Interface components ■ Selection and ordering data Version DT Order No. Price per PU PU (UNIT, SET, M) PS* PG Weight per PU approx. kg IE/AS-i LINK PN IO Router between Indust...
Page 25 - On use of; Slave; PROFIBUS
AS-Interface Routers DP/AS-i LINK Advanced 2/25 Siemens LV 1 · 2007 2 Integration of AS-Interface on PROFIBUS through DP/AS-i LINK Advanced as single/double master ■ Selection and ordering data Version DT Order No. Price per PU PU (UNIT, SET, M) PS* PG Weight per PU approx. kg DP/AS-i LINK Advanced ...
Page 26 - PROFIBUS DP
AS-Interface Routers DP/AS-Interface Link 20E 2/26 Siemens LV 1 · 2007 2 ■ Overview DP/AS-Interface Link 20E connects PROFIBUS DP to AS-Interface. It performs the following functions: • PROFIBUS DP slave and AS-Interface master • Connection of up to 62 AS-Interface slaves and integrated analog value...
Page 27 - Application
AS-Interface Routers DP/AS-Interface Link 20E 2/27 Siemens LV 1 · 2007 2 ■ Application The DP/AS-Interface Link 20E is a PROFIBUS DP slave (accord-ing to EN 50170) and an AS-Interface master (according to EN 50295). It enables the AS-Interface to be operated on PROFIBUS DP. Single PROFIBUS masters c...
Page 28 - Slaves; Overview of digital compact modules; Technical Specifications
AS-Interface Slaves I/O modules for operation in the fieldIntroduction 2/28 Siemens LV 1 · 2007 2 ■ Overview K60 K45 K20 Three coordinated series of AS-Interface compact modules with digital and analog compact modules and a high degree of pro-tection are available for operation in the field: • Serie...
Page 29 - I/O modules for operation in the field; • Wall mounting; K60 data couplers
AS-Interface Slaves I/O modules for operation in the field Digital I/O modules, IP67 - K60 2/29 Siemens LV 1 · 2007 2 ■ Overview The K60 digital AS-Interface compact modules are character-ized by optimized handling characteristics and user-friendli-ness. They permit the assembly times and start-up t...
Page 30 - Digital I/O modules IP67 – K60 data couplers; K60 mounting plates
AS-Interface Slaves I/O modules for operation in the fieldDigital I/O modules, IP67 - K60 2/30 Siemens LV 1 · 2007 2 ■ Selection and ordering data Version DT Order No. Price per PU PU (UNIT, SET, M) PS* PG Weight per PU approx. kg 3RK1 400-1DQ00-0AA3 Digital I/O modules, IP67 – K60 • PNP transistor•...
Page 31 - Mounting
AS-Interface Slaves I/O modules for operation in the field Digital I/O modules, IP68 / IP69K - K60R 2/31 Siemens LV 1 · 2007 2 ■ Overview Modules with degree of protection IP67 cannot be used in areas exposed to permanently high levels of humidity, in applications with drilling emulsions and cutting...
Page 33 - AS-Interface M12 feeders; AS-Interface quadruple M12 feeders; M12 addressing cables
AS-Interface Slaves I/O modules for operation in the field Digital I/O modules, IP68 / IP69K - K60R 2/33 Siemens LV 1 · 2007 2 Version DT Order No. Price per PU PU (UNIT, SET, M) PS* PG Weight per PU approx. kg 3RX9 801-0AA00 AS-Interface M12 feeders for flat cable for Cable length Cable end in feed...
Page 34 - Two mounting plates are offered for the K45 compact modules:
AS-Interface Slaves I/O modules for operation in the fieldDigital I/O modules, IP67 - K45 2/34 Siemens LV 1 · 2007 2 ■ Overview The K45 compact modules are the ideal supplement to the K60 large compact modules, which have proven their worth in indus-try. They are the logical consequence for rounding...
Page 35 - K45 mounting plates
AS-Interface Slaves I/O modules for operation in the field Digital I/O modules, IP67 - K45 2/35 Siemens LV 1 · 2007 2 Version DT Order No. Price per PU PU (UNIT, SET, M) PS* PG Weight per PU approx. kg Accessories 3RK1 901–2EA00 K45 mounting plates • For wall mounting } 3RK1 901–2EA00 1 1 unit 121 0...
Page 37 - AS-Interface sealing caps
AS-Interface Slaves I/O modules for operation in the field Digital I/O modules IP67 - K20 2/37 Siemens LV 1 · 2007 2 ■ Selection and ordering data ■ Accessories Version DT Order No. Price per PU PU (UNIT, SET, M) PS* PG Weight per PU approx. kg 3RK2 200-0CT30-0AA3 Digital I/O modules, IP67 – K20 Typ...
Page 38 - M12 Y-shaped coupler plugs
AS-Interface Slaves I/O modules for operation in the fieldDigital I/O modules IP67 - K20 2/38 Siemens LV 1 · 2007 2 For plug-in connectors and cables see Catalog FS 10, chapter "Proximity Switches / Accessories / Plug-in Connectors" or look in the Internet at www.siemens.com/as-interface . 3...
Page 39 - Advantages of the K45 compact modules; User modules
AS-Interface Slaves I/O modules for operation in the field Digital I/O modules, IP67 - user modules 2/39 Siemens LV 1 · 2007 2 ■ Overview The AS-Interface user modules are the first module generation for AS-Interface. Today, innovated and further improved mod-ules are available in the form of the K4...
Page 42 - Further information is available on the Internet at:; Only available to download on the Internet:
AS-Interface Slaves I/O modules for operation in the fieldAnalog I/O modules, IP67 - K60 2/42 Siemens LV 1 · 2007 2 Further information is available on the Internet at: http://mall.ad.siemens.com Version DT Order No. Price per PU PU (UNIT, SET, M) PS* PG Weight per PU approx. kg Accessories Manual, ...
Page 43 - I/O modules for operation in the control cabinet,; • SlimLine S45; Series
AS-Interface Slaves I/O modules for operation in the control cabinet, IP20, Introduction 2/43 Siemens LV 1 · 2007 2 ■ Overview SlimLine S22.5/S45 F90 module Flat module For AS-Interface applications inside cabinets there are various module series for the most diverse requirements: • SlimLine S22.5 •...
Page 44 - SlimLine modules of the S22.5 and S45 series; • Counter module
AS-Interface Slaves I/O modules for operation in the control cabinet, IP20, SlimLine 2/44 Siemens LV 1 · 2007 2 ■ Overview SlimLine modules of the S22.5 and S45 series The AS-Interface series of modules for the "SlimLine" cabinet with degree of protection IP20 creates space in the control ca...
Page 45 - S22.5 SlimLine modules; Sealable covers
AS-Interface Slaves I/O modules for operation in the control cabinet, IP20, SlimLine 2/45 Siemens LV 1 · 2007 2 ■ Selection and ordering data Version DT Order No. Price per PU PU (UNIT, SET, M) PS* PG Weight per PU approx. kg 3RK1 200-0CE00-0AA2 S22.5 SlimLine modules Inputs: PNP transistor Type Con...
Page 46 - Combicon connector sets
AS-Interface Slaves I/O Modules for operation in the control cabinet, IP20, F90 modules 2/46 Siemens LV 1 · 2007 2 ■ Selection and ordering data ■ Selection and ordering data Version DT Order No. Price per PU PU (UNIT, SET, M) PS* PG Weight per PU approx. kg 3RG9 002-0DB00 Modules F90 Standard slave...
Page 47 - Special integrated solutions; puts are not short-circuit and overload resistant if
AS-Interface Slaves Special integrated solutions AS-Interface communications modules 2/47 Siemens LV 1 · 2007 2 ■ Overview 3RK1 400-0CD00-0AA3AS-Interface communications module for printed circuit board installation With the 4I/4O module for printed circuit board mounting it is possible for up to fo...
Page 48 - Connection
AS-Interface Slaves Special integrated solutionsAS-Interface communications modules 2/48 Siemens LV 1 · 2007 2 3RK1 400-1CD00-0AA2 AS-Interface communications module for printed circuit board installation 1) Note: Pad numbering, see section Dimensional Drawings in the LV1 T "Technical Informatio...
Page 49 - Modules with special functions; : maximum possible transmission time from the slave to the; Counter modules
AS-Interface Slaves Modules with special functions Counter modules 2/49 Siemens LV 1 · 2007 2 ■ Overview This module is used to send hexadecimally coded count values (LSB=D0, MSB=D3) to a higher level controller. The count value is increased by one for each valid count pulse at terminal 8. Be-ginnin...
Page 50 - The following ground faults are detected:; Rated discharge current; Protection level U; Ground-fault detection modules
AS-Interface Slaves Modules with special functionsGround-fault detection modules 2/50 Siemens LV 1 · 2007 2 ■ Overview "... Ground faults in control circuits must not result in a machine's unintentional starting or hazardous movements, nor must they prevent it from stopping (EN 60204, Part 1 or ...
Page 51 - Configuration guidelines; Sample application; Overvoltage protection modules
AS-Interface Slaves Modules with special functions Overvoltage protection modules 2/51 Siemens LV 1 · 2007 2 Configuration guidelines Configuration guidelines for overvoltage protection modules The grounding of protection modules and the units to be pro-tected must be effected through a shared groun...
Page 53 - Power Supply Units; More Information
AS-Interface Power Supply Units AS-Interface power supplies, IP20 2/53 Siemens LV 1 · 2007 2 ■ Overview AS-Interface power supplies are an essential and functionally important part of an AS-Interface network. They supply the elec-tronics of the network (AS-Interface modules and AS-Interface masters)...
Page 54 - Conversion table; Previous type
AS-Interface Power Supply Units AS-Interface power supplies, IP20 2/54 Siemens LV 1 · 2007 2 ■ More information Conversion table Previous type New type Order No. Version Number Order No. Version 3RX9 307-0AA00 Single outputIP202.4 A 1 3RX9 501-0BA00 Single outputIP20 with ground fault detection3 A 3...
Page 55 - Transmission Media
AS-Interface Transmission Media AS-Interface shaped cables 2/55 Siemens LV 1 · 2007 2 ■ Overview The actuator-sensor interface - the networking system used for the lowest field area - is characterized by very easy mounting and installation. A new connection method was developed specially for AS-Inte...
Page 56 - System Components and Accessories; Extension plug; Configuration; AS-Interface extension plugs
AS-Interface System Components and Accessories Extension plug 2/56 Siemens LV 1 · 2007 2 ■ Overview With the extension plug / extension plug plus it is possible to double the cable length possible in an AS-Interface segment from 100 to 200 m. The extension plug / extension plug plus is a passive com...
Page 57 - Addressing units; • offline by means of an addressing unit or; AS-Interface addressing units; Addressing cables, with M12 socket
AS-Interface System Components and Accessories Addressing units 2/57 Siemens LV 1 · 2007 2 ■ Overview To be able to participate in data exchange with the master, all stations have to be addressed before the AS-Interface network is configured. This can be done • offline by means of an addressing unit...
Page 58 - AS-Interface analyzers; Online statistics
AS-Interface System Components and Accessories AS-Interface analyzers 2/58 Siemens LV 1 · 2007 2 ■ Overview The AS-Interface analyzer is used to test AS-Interface networks. It enables systematic troubleshooting and permanent monitor-ing. Installation errors, e.g. loose contacts or EMC interference u...
Page 59 - Data mode
AS-Interface System Components and Accessories AS-Interface analyzers 2/59 Siemens LV 1 · 2007 2 Data mode In this mode the analyzer now shows not only the digital input/ output values but also the current analog values and the input status of the safety slaves. Trace mode The presentation of messag...
Page 61 - Miscellaneous accessories
AS-Interface System Components and Accessories Miscellaneous accessories 2/61 Siemens LV 1 · 2007 2 ■ Selection and ordering data Version DT Order No. Price per PU PU (UNIT, SET, M) PS* PG Weight per PU approx. kg 3RK1 901-1NN00 AS-Interface standard distributors, for AS-Interface flat cables • Curr...
Page 62 - • See Catalog FS 10 / chapter
AS-Interface System Components and Accessories Miscellaneous accessories 2/62 Siemens LV 1 · 2007 2 Other accessories: • See Catalog FS 10 / chapter Proximity Switches / section Accessories / Plug-in Connectors • See A&D-Mall / section Sensors, Measurement and Testing Systems / Proximity Switche...
Page 63 - System overview
ECOFAST System System overview 2/63 Siemens LV 1 · 2007 2 ■ Overview SIRIUS motor starter applications is a system solution for the flexible and uniform decentralization of drive technology in the field. It is centered on the extensive decentralization and modu-larization of fusing, switching and co...
Page 64 - ECOFAST: The system solution for cabinet-free automation
ECOFAST System System overview 2/64 Siemens LV 1 · 2007 2 ■ Application SIMATIC ET 200S: The flexible and modular system with degree of protection IP20 The SIMATIC ET 200S system for PROFIBUS DP and PROFINET offers a range of I/O modules (digital and analog), motor starters (mechanical and solid-sta...
Page 65 - Product
ECOFAST System System overview 2/65 Siemens LV 1 · 2007 2 ■ More information Product For further information see SIMATIC ET 200S • A&D Mall: Section Automation Systems / SIMATIC Industrial Automation Systems / Distributed Peripherals / ET 200S • Catalog IK PI, Chapter "SIMATIC ET 200 Distrib...
Page 66 - SIRIUS Safety Integrated
SIRIUS Safety Integrated System overview 2/66 Siemens LV 1 · 2007 2 ■ Overview In spite of the steadily increasing complexity in industrial automation, many applications are restricted to specific areas. However simple the requirements may be, it is important to have a reliable partner for these cas...
Page 67 - Cost efficiency; Safe sensing; Hinge switches
SIRIUS Safety Integrated System overview 2/67 Siemens LV 1 · 2007 2 ■ Benefits Integration of safety technology in standard automation means less work for you and greater cost effectiveness. Cost efficiency • A single system for standard and safety automation reduces the diversity of equipment • One...
Page 68 - Safe instructing and reporting; Cable-operated switches Two-hand operation; ASIsafe safety monitors
SIRIUS Safety Integrated System overview 2/68 Siemens LV 1 · 2007 2 Safe instructing and reporting When things become critical, you must be able to intervene quickly and easily in order to bring machines and plants to a safe standstill. For such moments we offer a complete range of reli-able command...
Page 69 - Starting and safe shutting down; You can find more information on the Internet at:; Safe load feeders
SIRIUS Safety Integrated System overview 2/69 Siemens LV 1 · 2007 2 Starting and safe shutting down The new failsafe motor starters of the SIMATIC ET 200S provide failsafe stopping and shut-down for safety-oriented applications which are realized at control level. They can be used as island solution...
Page 70 - System Overview
PROFIBUS System Overview Introduction 2/70 Siemens LV 1 · 2007 2 ■ Overview • Bus system - For process and field communication in cell networks with few stations and with field devices - For data communication according to IEC 61158/EN 50170 • Provides openness for connecting standard-conform compo-...
Page 71 - Process or field communication; Communication functions; • PROFIBUS DP; SIMATIC; Integral interface
PROFIBUS System Overview Process or field communication 2/71 Siemens LV 1 · 2007 2 ■ Overview Communication functions The process or field communication (PROFIBUS DP, PROFIBUS PA) is used to link field device to an automation, HMI or I&C system. The connection can be established through integrat...
Page 72 - PROFIBUS P
PROFIBUS System Overview Process or field communication 2/72 Siemens LV 1 · 2007 2 PROFIBUS DP/PA is used to connect field devices such as dis-tributed I/O stations or operating mechanisms to automation systems such as SIMATIC S7 or PCs. PROFIBUS DP/PA is selected when I/O stations on a machine or i...
Page 73 - DP device types; • DP master class 1
PROFIBUS System Overview Process or field communication 2/73 Siemens LV 1 · 2007 2 DP device types PROFIBUS DP differentiates between two different classes of master and various DP functionalities: • DP master class 1 The DP master class 1 is the central component of PROFIBUS DP. In a fixed, continu...
Page 74 - Data communication; • PG/OP communication
PROFIBUS System Overview Data communication 2/74 Siemens LV 1 · 2007 2 ■ Overview Communication functions The data communication (e.g. PROFIBUS FMS) is used to ex-change data between automation devices or between an auto-mation device and intelligent partners (PC, computer, etc.). The following comm...
Page 75 - System connections; Automation system
PROFIBUS System Overview Data communication 2/75 Siemens LV 1 · 2007 2 System connections For many terminal devices that are communication processors (CPs) which have implemented the communication functions in the firmware already and as the result relieve the terminal device of having to perform co...
Page 76 - Topologies; Electrical network; PROFIBUS PA
PROFIBUS System Overview Topologies 2/76 Siemens LV 1 · 2007 2 ■ Overview Siemens offers an extensive range of PROFIBUS network components for electrical and optical transmission technology. PROFIBUS is standardized according to IEC 61158/EN 50170 for universal automation (PROFIBUS FMS and PROFIBUS ...
Page 77 - Optical network
PROFIBUS System Overview Topologies 2/77 Siemens LV 1 · 2007 2 Optical network The optical conductor variant of PROFIBUS has the following features: • Transmission path is insensitive to electromagnetic interfer- ence • Suitable for long ranges • Electrical isolation • Uses either plastic or PCF or ...
Page 78 - Mixed network; Control cabinet
PROFIBUS System Overview Topologies 2/78 Siemens LV 1 · 2007 2 Mixed network Mixed structures consisting of an electrical and an optical network are possible. The transition between the two media is effected by an OLM. In the way stations on the bus communicate with each other there is no difference...
Page 79 - Wireless coupling
PROFIBUS System Overview Topologies 2/79 Siemens LV 1 · 2007 2 Wireless coupling With the help of the PROFIBUS infrared link module (ILM), one or more PROFIBUS slaves or slave segments can be coupled by wireless means. With a maximum transmission rate of 1.5 Mbit/s and a maximum range of 15 m, commu...
Page 80 - SIRIUS Modular System; SIRIUS stands for innovation; The new 3RB2 solid-state overload relays
SIRIUS Modular System System overview 2/80 Siemens LV 1 · 2007 2 ■ Overview A perfect team: The SIRIUS modular system for the control cabinet Building switchgear cabinets should be quick, easy, flexible and space-saving. But how can all these requirements be met simul-taneously? The answer lies in t...
Page 81 - The advantages and highlights at a glance
SIRIUS Modular System System overview 2/81 Siemens LV 1 · 2007 2 The new SIRIUS 3RW40 soft starters – for soft starting up to high ratings Two new types of soft starter in compact SIRIUS design provide the answer for the starting of three-phase asynchronous motors with reduced strain on the load and...
Page 82 - Robust and reliable: SIRIUS 3RT contactors
SIRIUS Modular System System overview 2/82 Siemens LV 1 · 2007 2 ■ More information Product For further information see Robust and reliable: SIRIUS 3RT contactors Thanks to the extreme robustness and best contact reliability of our contactors, their switching is extremely precise and reliable. At th...