Page 3 - System General Introduction; AB P; Specification Parameter; —Hardware specification
SH-300 User ’s Manual Hardware Part Page 3 of 103 SH-300 Hardware part 1 1.1 System General Introduction SH-300 is a small Human-Machine interface, mainly being used to be connected with PLC orother intelligent controllers with COM port communication function. It can monitor, setup andmodify the dat...
Page 4 - —Electric specification; —Ambient Requirement; Hardware Structure
SH-300 Text Panel Page 4 of 103 Brightness 60 cd/m 2 Color Monochrome(yellow-green) Contrast Adjustable resistor Background light Long life yellow-green LED Memory 110KB Flash ROM Communication Port PC RS232& PLC RS485/422 & PLC RS232 Function button 14 freely configurable keys Allowable pow...
Page 6 - COM Port
SH-300 Text Panel Page 6 of 103 When using if the contrast of the LCD isn’t fit, revolve the contrast potentiometer on the left sidewith small sized screwdriver till the contract reach the desired degree The display of SH-300 is with LED background light. Press any key, the background light will bet...
Page 7 - Function Key List; In data-setting mode, sign of the modified number will be set.
SH-300 User ’s Manual Hardware Part Page 7 of 103 1.4 Function Key List key Function [←] When modifying the register data, the cursor will be moved one-digit left. [→] When modifying the register data, the cursor will be moved one-digit right. [↑] To jump to the previous screen, whose number is set ...
Page 8 - Installation Dimensions and Guide; Method 1
SH-300 Text Panel Page 8 of 103 1.5 Installation Dimensions and Guide Dimensions of SH-300 (L*W*H): 171.8×98.8×38.6 (Unit: mm)Dimensions of the installation hole: 165×85 (Unit: mm) Method 1 : Embedded installation The installment surface must be up to Standard Type 4, being applicable for indoor or ...
Page 9 - Method 2
SH-300 User ’s Manual Hardware Part Page 9 of 103 Method 2 : DIN rail installation ( standard 35mm DIN rail installation ) Method 3: Screw installation (To install on the motherboard)
Page 10 - Memo
SH-300 Text Panel Page 10 of 103 《 Memo 》 ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ——————————————————...
Page 11 - The basic process chart of using is shown in the following figure:
SH-300 User ’s Manual Software Part Page 11 of 103 SH300 Software Part 2 2.1 SH300 General Introduction SH300 is the special development software of SH-300 Programmable Text Display, which is runon the base of WINDOWS 98/2000/XP platform. SH300 software makes the best use of theabundant graphic inte...
Page 12 - Installation and Uninstallation of SH300; and click it , the following diagram will be shown:; NEXT; to exit the installation program.; YES; to enter the next step. The
SH-300 Text Panel Page 12 of 103 2.3 Installation and Uninstallation of SH300 2.3.1 Installation of SH300 The installation of SH300 is very simple. In the installation process, a prompting dialogue box willappear automatically and you will complete the installation smoothly on the computer under its...
Page 15 - Yes
SH-300 User ’s Manual Software Part Page 15 of 103 2.3.2 Uninstallation of SH300 There are two ways for the uninstallation of SH300:1. Remove from WINDOWS START MENU▲ Under the WINDOWS taskbar, click Start→Program→ARRAY→SH300→Unistall of SH300 As shown in the following diagram: ▲ When a confirm unin...
Page 16 - Operation Interface
SH-300 Text Panel Page 16 of 103 2.4 Operation Interface The window of SH300 software is mainly made up of menu bar, tool bar, distribution bar, editsection, window description section, status bar and property section. Tool bar Create a new project file Open a saved project file Close the current pr...
Page 18 - Menu Name
SH-300 Text Panel Page 18 of 103 2.4.1 File This instruction is mainly used for project file management, including creating, opening, saving etc Menu Name Function New project Create a new project file Open project Open an old project file Save project Save the current project file Save as Save the ...
Page 24 - Operation Instruction (Mitsubishi FX Series as an; Click “Lamp” option under “Object” menu or click; Logic Choice; Positive Logic
SH-300 Text Panel Page 24 of 103 2.5 Operation Instruction (Mitsubishi FX Series as an example) 2.5.1 Indicator Click “Lamp” option under “Object” menu or click in toolbar, there will be a dashed rectangular frame following and moving together with the mouse. Move the mouse to the properposition in ...
Page 26 - ▲Coil
SH-300 Text Panel Page 26 of 103 Screen-Jumping: Action of the key is defined as screen-jumping function.Register Set: Action of the key is defined as register parameter setup function. ▲Coil The number, type and address correspond to the definition of PLC inner relay.ON: to set the designated relay...
Page 28 - Click “Register” option under “Object” menu, or click
SH-300 Text Panel Page 28 of 103 If the value of D100 is 60, the “motor speed is normal” will be displayed as follows: If the value of D100 is 80, the “motor speed is too rapid” will be displayed as follows: 2.5.5 Register Click “Register” option under “Object” menu, or click in toolbar, there will ...
Page 30 - Register
SH-300 Text Panel Page 30 of 103 Caution! There may be some error in the conversion because of the limit of the operation precisionof the floating number. For example: Design requirements: Screen 2 is two groups of the main property parameter of therelated PLC, the rotate speed of principal axis and...
Page 32 - once in
SH-300 Text Panel Page 32 of 103 This bar graph can be used to monitor the data in register D0. If the bar graph is fully displayed,it means the value in register D0 is 100. And when the bar graph is 20% displayed, it means thevalue in register D0 is 20. 2.5.7 Trend Graph Click “Trend Graph” option ...
Page 33 - Note: A trend line component can only display one line.; Bitmap
SH-300 User ’s Manual Software Part Page 33 of 103 ▲ Size Set the height and width of the trend graph. ▲ Display Full amount: 100% trend line will display the corresponding register value Empty amount: 0% trend line will display the corresponding register valueDate dots: the total sample number in t...
Page 34 - Message display
SH-300 Text Panel Page 34 of 103 ▲ Position Property: X Position: specifying the horizontal position of the componentY Position: specifying the vertical position of the componentNote: The grid origin is at the top left corner of the screen. ▲ Size To adjust the height and width of the bitmap ▲ Rever...
Page 35 - ▲ Style; Alarm List; ” option under “; Window; ” or click
SH-300 User ’s Manual Software Part Page 35 of 103 ▲ Position Property:X Position: specifying the horizontal position of the componentY Position: specifying the vertical position of the componentNote: The grid origin is at the top left corner of the screen. ▲ Coil PropertyStation number, type and th...
Page 36 - Add; ” button or press; Enter; third line and input “ Power supply fault”.
SH-300 Text Panel Page 36 of 103 Each project file of SH-300 can set a group of alarm list information. And each piece of informationcorresponds to a relay. The definition numbers of all the relays are continuous. And the firstaddresses of all the relays are set by the users according to the actual ...
Page 37 - User-defined SH300 system information; Immanent; ” of the menu “; Tool; Click “; Immanent resource; “, then the following diagram will be shown:
SH-300 User ’s Manual Software Part Page 37 of 103 When SH-300 is working normally, if there is any failure alarm or M0 and M2 are ON, the flashingalarm screen will prompt automatically on SH-300 as in the following: If the alarm failure is not corrected, the failure alarm information will flash and...
Page 38 - default; ” and then doubt click “; message; ” on the left column. The seven information; user menu; displayed as the following:
SH-300 Text Panel Page 38 of 103 Click “ default ” and then doubt click “ message ” on the left column. The seven information submenu “No response”, “Password menu”, “Input Password”, “Login OK”, “Password error”,“Logout OK”, “No alarm information” will be displayed as in the following diagram: Clic...
Page 39 - Example; Modify the coordinate position
SH-300 User ’s Manual Software Part Page 39 of 103 In this property frame, user can modify the X and Y coordinate position of the menu information (atthe top left corner, it is the original coordinate position (0, 0) of X and Y) and the contents of thetext information of the text frame (supporting m...
Page 40 - user menu setting; ” check box and doubt click the text needed to be changed,
SH-300 Text Panel Page 40 of 103 The password set interface includes “LOGIN”, “LOGOUT”, “ESC EXIT” (default information).If the text of the information in the screen need to be changed and the position need not to bechanged, cross “ user menu setting ” check box and doubt click the text needed to be...
Page 41 - : Substitute the text “ENTER” for “LOGIN”, “QUIT” for “LOGOUT” and “RETURN” for; Input password; ” submenu, then the password input interface will be displayed as in
SH-300 User ’s Manual Software Part Page 41 of 103 Example : Substitute the text “ENTER” for “LOGIN”, “QUIT” for “LOGOUT” and “RETURN” for “EXIT”. Click “OK”, the following diagram will be displayed. Click the “ Input password ” submenu, then the password input interface will be displayed as in the ...
Page 42 - position Y is fixed. Click “; OK; ”, the following diagram will be displayed:; Login OK; displayed as in the following diagram:; following prompting frame will be displayed as the following:
SH-300 Text Panel Page 42 of 103 Example : substitute the text “password” for “Input password”, modify the position X to 0 and the position Y is fixed. Click “ OK ”, the following diagram will be displayed: Click the “ Login OK ” submenu, then the password being successfully input interface will be ...
Page 44 - “PRESS ANY KEY”. Then click “; ”. The following diagram will be displayed:; Logout OK
SH-300 Text Panel Page 44 of 103 In this property frame, user can modify the X and Y coordinate position of the menu information (atthe top left corner, it is the original coordinate position (0, 0) of X and Y) and the contents of thetext information of the text frame (supporting multi language syst...
Page 46 - prompting frame will be displayed as the following:; ALM; ” key, the following diagram will
SH-300 Text Panel Page 46 of 103 If the text and the position of the information in the screen need to be changed, cross “ user menu setting ” check box and double click the text frame “NO ALARM INFORMATION”, the following prompting frame will be displayed as the following: In this property frame, u...
Page 47 - Multi Language Editor; Default reference bar: to display the default English menu bar
SH-300 User ’s Manual Software Part Page 47 of 103 Note: After the modification of the self-defined information menu, click “Save” button and close the information frame, and write the edited program into SH-300, then the modified self-definedinformation will be written into SH-300. 2.7 Multi Langua...
Page 49 - Operation Example; Via SH-300 to set alarm information of abnormal work
SH-300 User ’s Manual Software Part Page 49 of 103 2.8 Operation Example Subject: The Drying Boxes Control SystemControl requirements: ( 1 ) Via SH-300 to monitor the work status of three groups of heating units; ( 2 ) Via SH-300 to observe the actual temperature and change the preset temperature of...
Page 51 - Select “Register” under “Object” menu or click
SH-300 User ’s Manual Software Part Page 51 of 103 Select “Register” under “Object” menu or click in the tool bar. Move the mouse to proper place under “Current” and click the left key of the mouse to confirm. Then set the parameter ofthe register, Address=D1, Digits=4, Decimal=2, Mode=Dec. Don’t se...
Page 56 - Manipulation; configuration computer.; Connect SH-300 to PLC with a communication cable and check the
SH-300 Text Panel Page 56 of 103 Manipulation 3 3.1 Download Window 1. Connect the operating unit interface to the configuration computer using a SH-PC cable. 2. Confirmed SH-300 has added on the DC24V power source. 3. Press and start to download the date, the screen appears the downloading picture ...
Page 57 - Shifting the windows; Window No.1 is a main menu window. Pressing
SH-300 User ’s Manual Manipulation Page 57 of 103 3.3 Shifting the windows Take the project windows of the drying boxes as an example to introduce the manipulation ofSH-300.SH-300 displays window No.1 at first (the initial window is No.1). Window No.1 is a main menu window. Pressing ① switch to the ...
Page 59 - After finished the setting of register, press “
SH-300 User ’s Manual Manipulation Page 59 of 103 3.6 State Monitoring After finished the setting of register, press “ ∧ ” and return to the main menu ,SH-300 is shown as follows: Press ② enter the window of state monitoring (No.3), which is shown as follows: SH-300 will display the state monitoring...
Page 61 - Connection with PLC; Mitsubishi FX Series; select the programming cable of the FX series
SH-300 User ’s Manual Connection with PLC Page 61 of 103 Connection with PLC 4 4.1 Mitsubishi FX Series SH-300 can communicate with the programming port of all types of Mitsubishi FX series PLC orthe FX2N-422BD module of the FX2N series. SH-300 software configuration: Item Content SH-300 COM port 9 ...
Page 65 - Panasonic FP Series; The picture for
SH-300 User ’s Manual Connection with PLC Page 65 of 103 4.5 Panasonic FP Series SH-300 can communicate with Panasonic FP series PLC, the communication port is theprogramming port of PLC or external communication port. SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC CO...
Page 69 - Connection guidance of port 1 special cable
SH-300 User ’s Manual Connection with PLC Page 69 of 103 Connection guidance of port 1 special cable : SH-300 side 2 RXD 3 RXD 9 pin D shapeFemale plug 3 TXD 4 TXD PLC side 5 GND 1 GND ( 6PIN port1 ) ( when SH-300 communicates with ADC DL05 series PLC you are recommended to use the theprogramming ca...
Page 71 - Series
SH-300 User ’s Manual Connection with PLC Page 71 of 103 4.10 Schneider NEZA/TWIDO Series SH-300 can communicate with Schneider NEZA/TWIDO Series PLC through Modbus RTUprotocol, the communication port is the programming port of PLC SH-300 software configuration: Item Content SH-300 COM port RS485 CO...
Page 73 - THINGET XC Series
SH-300 User ’s Manual Connection with PLC Page 73 of 103 4.12 THINGET XC Series SH-300 can communicate with THINGET XC series PLC, the communication port is theprogramming port of PLC SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port Default par...
Page 75 - The picture for 6 pin Female plug
SH-300 User ’s Manual Connection with PLC Page 75 of 103 4.14 HITACHI MICRO-EH Series SH-300 can communicate with HITACHI MICRO-EH series PLC, the communication port is theprogramming port of PLC SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port...
Page 77 - Introducing Modbus Protocol
SH-300 User ’s Manual Connection with PLC Page 77 of 103 4.16 MODBUS RTU/ASCII and RTU/ASCII EXTEND protocol 1. Introducing Modbus Protocol SH-300 communicates by using a master–slave technique, in which one SH-300(the master)can send query message. one programmable controller(the slave) responds ac...
Page 78 - codes in Modbus RTU/ASCII Protocol
SH-300 Text Panel Page 78 of 103 4. The list of corresponding relationship between address type of SH-300 and function codes in Modbus RTU/ASCII Protocol 5. The list of corresponding relationship between address type of SH-300 and function codes in Modbus RTU/ASCII EXTEND Protocol Object type Addres...
Page 79 - the first byte; Here is an example of setting coil M15 status; the list of corresponding; the address
SH-300 User ’s Manual Connection with PLC Page 79 of 103 Note: 1. When selecting “3x” as register address type, single or double register only can be read, not to be written. 2. When selecting “4x” as register address type to read or write double register. the first byte contains the high order bit ...
Page 81 - codes in Modbus Protocol”
SH-300 User ’s Manual Connection with PLC Page 81 of 103 6.2.3. Here is an example of displaying and setting Register R1088 According to “ the list of corresponding relationship between the address type and function codes in Modbus Protocol” the address type of reading and writing holding register i...
Page 82 - Communication configuration
SH-300 Text Panel Page 82 of 103 4.17 SH-300 Freedom Protocol 1. Communication configuration SH-300 can communicate with some controllers via freedom protocol. When SH-300communicates with controller via this protocol user need to define own controller freedomcommunication format first. Here SH-300 ...
Page 83 - Connection guidance of special cable
SH-300 User ’s Manual Connection with PLC Page 83 of 103 If Registers are addressed starting at B1, W1,DW1. Allocation map of memory address is shownas following: Registeraddress Doubleword DW1 DW3 …… word W1 W3 W5 W7 …… byte B1 B2 B3 B4 B5 B6 B7 B8 …… Coil address M8 ∣ M15 M16 ∣ M23 M24 ∣ M31 M32 ∣...
Page 84 - The data format of query from SH-300 and response from PLC; a. Make the screen displayed as following, use function key
SH-300 Text Panel Page 84 of 103 3. The data format of query from SH-300 and response from PLC When SH-300 communicates with controller via freedom protocol the Register data and thestatus of inner coils can be set up by SH-300 and displayed on the SH-300 at real time. PC canbe taken as dummy contro...
Page 90 - Array FAB Series PLC
SH-300 Text Panel Page 90 of 103 4.18 Array FAB Series PLC SH-300 can communicate with Array FAB series PLC, and the communication port is theprogramming port of PLC. SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port Default parameter 9600bps 、 ...
Page 92 - And when it is setting the analog parameter,
SH-300 Text Panel Page 92 of 103 FAB program is shown above. If there is a need to set and display the value of the functionblock B1 through SH-300, the operation is shown as following graph: Explanation: As the SH-300 can not identify second, minute and hour when it is displaying and setting the ti...
Page 93 - Array SR Series PLC
SH-300 User ’s Manual Connection with PLC Page 93 of 103 4.19 Array SR Series PLC SH-300 can communicate with Array SR series PLC, and the communication port is theprogramming port of PLC. SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port Defaul...
Page 95 - Array APB Series PLC
SH-300 User ’s Manual Connection with PLC Page 95 of 103 4.20 Array APB Series PLC SH-300 can communicate with ARRAY APB series PLC, and the communication port is PLCprogramming port. SH-300 Software Configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port Default par...
Page 97 - Modify the parameter value of function block B0011.
SH-300 User ’s Manual Connection with PLC Page 97 of 103 2 . Modify the parameter value of function block B0011. a. In APB program, the value of the register DW10 is referenced as the off-delay time for the function block B0011, and the value of the register DW11 is referenced as the hold-ON time.Th...
Page 99 - As B0012 is a function block of count type,
SH-300 User ’s Manual Connection with PLC Page 99 of 103 3. As B0012 is a function block of count type, is selected as the function object to read the current value. It is shown as following graph: a. Click to read current value of the function block B0012, and the address is BR12.0. b. In program, ...