Page 2 - PROFINET/Industrial Ethernet; Active network components; Siemens IK PI News · July 2007; Overview
PROFINET/Industrial Ethernet Active network components Overview 2/2 Siemens IK PI News · July 2007 2 ■ Overview Industrial Ethernet Switches SCALANCE X is the product range of Industrial Ethernet switches from SIMATIC NET. Switches are active network com-ponents that specifically distribute data to ...
Page 3 - Industrial Ethernet switches; Overview of the Industrial Ethernet switches; Modular; Entry Level
PROFINET/Industrial Ethernet Industrial Ethernet switches Overview 2/3 Siemens IK PI News · July 2007 2 ■ Overview Overview of the Industrial Ethernet switches X414-3E X204IRT X202-2IRT X208PRO X208 X204-2/ X204-2LD X206-1/ X206-1LD X104-2 X106-1 X108 X-400 X-200 X-100 X005 X005 X200-4P IRT G_IK10_X...
Page 4 - Gigabit Ethernet; Type of; Type and number of ports
PROFINET/Industrial Ethernet Industrial Ethernet switches Overview 2/4 Siemens IK PI News · July 2007 2 ■ Overview (continued) Overview of the functions of the SCALANCE X Industrial Ethernet switches TP X414-3E X202-2IRT X204IRT X206-1LD X204-2LD X208PRO X116 X106-1 X104-2 8 12 3) 12 3) 4 1) 2 2 1 2...
Page 5 - SCALANCE X-100 unmanaged
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-100 unmanaged 2/5 Siemens IK PI News · July 2007 2 ■ Overview • The unmanaged Industrial Ethernet switches of the SCALANCE X-100 product line are optimized for installing Industrial Ethernet networks with 10/100 Mbit/s in a line an...
Page 6 - Design; 00BaseFX, BFOC connection technique; Function; Star-shaped network topology with SCALANCE X124
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-100 unmanaged 2/6 Siemens IK PI News · July 2007 2 ■ Design The SCALANCE Industrial Ethernet switches with a rugged metal housing are optimized for mounting on a standard rail and an S7-300 rail. Direct wall mounting in various pos...
Page 7 - Optical line topology with SCALANCE X104-2; PROFIBUS
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-100 unmanaged 2/7 Siemens IK PI News · July 2007 2 ■ Function (continued) Electrical and optical line topology with SCALANCE X108, SCALANCE X112-2 and SCALANCE X104-2 Optical line topology with SCALANCE X104-2 G_IK10_XX_10203 ET 20...
Page 8 - Optical star topology with SCALANCE X106-1; Diagnostics; The following information is displayed by LEDs on site:; SCALANCE; Fiber Optic
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-100 unmanaged 2/8 Siemens IK PI News · July 2007 2 ■ Function (continued) Optical star topology with SCALANCE X106-1 Diagnostics The following information is displayed by LEDs on site: • Power • Port status • Data traffic The Indus...
Page 9 - Technical specifications; Type
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-100 unmanaged 2/9 Siemens IK PI News · July 2007 2 ■ Technical specifications Type SCALANCE X104-2 SCALANCE X106-1 SCALANCE X108 Data transmission rates 10/100 Mbit/s 10/100 Mbit/s 10/100 Mbit/s Interfaces • Communication connectio...
Page 11 - Ordering data; Accessories
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-100 unmanaged 2/11 Siemens IK PI News · July 2007 2 ■ Ordering data Order No. Order No. Industrial Ethernet switches SCALANCE X-100 Industrial Ethernet switches for 10/100 Mbit/s • SCALANCE X104-2 with four 10/100 Mbit/s RJ45 ports...
Page 12 - SCALANCE X-200 managed
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed 2/12 Siemens IK PI News · July 2007 2 ■ Overview • The managed Industrial Ethernet switches of the SCALANCE X-200 product line are optimized for installing Industrial Ethernet networks with 10/100 Mbit/s in a line, star...
Page 13 - Application
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed 2/13 Siemens IK PI News · July 2007 2 ■ Application The SCALANCE X-200 Industrial Ethernet switches permit cost-effective configuration of Industrial Ethernet line, star or ring topologies with switching functionality f...
Page 14 - Diagnostics access over SNMP and Web browser with SCALANCE X208; Switching
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed 2/14 Siemens IK PI News · July 2007 2 ■ Application (continued) Diagnostics access over SNMP and Web browser with SCALANCE X208 ■ Design The SCALANCE X-200 Industrial Ethernet switches with a rug-ged metal housing are o...
Page 16 - Star topology with SCALANCE X224; Mobile Panel; PROFINET
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed 2/16 Siemens IK PI News · July 2007 2 ■ Function (continued) Star network topology with SCALANCE X208PRO outside the control cabinet and 230 V AC power supply Star topology with SCALANCE X224 Mobile Panel 277 IWLAN SCAL...
Page 23 - IE M12 Plug PRO
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed 2/23 Siemens IK PI News · July 2007 2 ■ Ordering data Order No. Order No. Industrial Ethernet Switches SCALANCE X-200 Industrial Ethernet switches with integral SNMP access, online diagnostics, copper cable diagnostics ...
Page 24 - SCALANCE X-300 managed plus
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-300 managed plus 2/24 Siemens IK PI News · July 2007 2 ■ Overview • The SCALANCE X-300 product line consists of compact Industrial Ethernet switches for establishing electrical and/or optical line, ring and star topologies at 10/10...
Page 25 - Electrical star topology with SCALANCE X310; Industrial Ethernet
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-300 managed plus 2/25 Siemens IK PI News · July 2007 2 ■ Application SCALANCE X-300 products enable the establishment of switched networks both at the field level and at the control level where high data transfer speeds are require...
Page 30 - IE FC RJ45 Modular Outlet; • German
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-300 managed plus 2/30 Siemens IK PI News · July 2007 2 ■ Ordering data Order No. Order No. SCALANCE X-300Industrial Ethernet switches Managed plus Industrial Ethernet switches; RJ45 ports for establishing electrical and/or optical ...
Page 31 - SCALANCE X-400 modular
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular 2/31 Siemens IK PI News · July 2007 2 ■ Overview • The SCALANCE X-400 product range comprises modular Industrial Ethernet switches expandable by various media modules and partially by extenders. It supports 10/100/1000-...
Page 33 - • Simple user connection via twisted pair; Possible applications of the media modules with SCALANCE X408-2
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular 2/33 Siemens IK PI News · July 2007 2 ■ Design (continued) SCALANCE X-400 extender module (EM), only for SCALANCE X414-3E An optional extender module with up to 8 further Fast Ethernet ports can be mounted next to the e...
Page 36 - Ethernet
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular 2/36 Siemens IK PI News · July 2007 2 ■ Function (continued) Redundant coupling with an Office network and industrial network on Layer 2 and Layer 3 Network topology and network configuration The network topology can ea...
Page 37 - Fault-tolerant system with SCALANCE X-400; Industrial
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular 2/37 Siemens IK PI News · July 2007 2 ■ Function (continued) Network management The network management provides the following functions: • Password-protected dial-up for "Administrator" (read and write authoriza...
Page 38 - Integration; • SCALANCE X-400 switches without extenders are used for
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular 2/38 Siemens IK PI News · July 2007 2 ■ Integration (continued) Use of the SCALANCE X-400 switches in a process control system, e.g. PCS 7 In the control room, two SCALANCE X-400 switches are used on the terminal bus. W...
Page 41 - Replacement parts; Label sheet; Straight, with locking lug
PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular 2/41 Siemens IK PI News · July 2007 2 ■ Ordering data Order No. Order No. Industrial Ethernet Switches SCALANCE X-400 Modular Industrial Ethernet switches with integral RJ45 ports for constructing electrical and/or opti...
Page 42 - For operation of the CPU, a micro memory card is required.; Supply voltages
PROFINET/Industrial Ethernet CPUs for SIMATIC S7-300 CPU 319F-3 PN/DP 2/42 Siemens IK PI News · July 2007 2 ■ Overview • The fail-safe CPU with high-performance command process- ing, large program memory and large quantity structure for demanding applications • For constructing a fail-safe automatio...
Page 43 - Data areas and their remanence
PROFINET/Industrial Ethernet CPUs for SIMATIC S7-300 CPU 319F-3 PN/DP 2/43 Siemens IK PI News · July 2007 2 ■ Technical specifications (continued) 6ES7 318-3FL00-0AB0 Times/counters and their remanence S7 counter • Number 2,048 • Remanence - adjustable Yes • Counting range - adjustable Yes - lower l...
Page 44 - Test commissioning functions
PROFINET/Industrial Ethernet CPUs for SIMATIC S7-300 CPU 319F-3 PN/DP 2/44 Siemens IK PI News · July 2007 2 ■ Technical specifications (continued) 6ES7 318-3FL00-0AB0 Test commissioning functions Status/control • Status/control variable Yes • Number of variables, max. 30 • of which status variable, ...
Page 45 - st interface
PROFINET/Industrial Ethernet CPUs for SIMATIC S7-300 CPU 319F-3 PN/DP 2/45 Siemens IK PI News · July 2007 2 ■ Technical specifications (continued) 6ES7 318-3FL00-0AB0 1st interface isolated Yes Power supply to interface (15 to 30 V DC), max. 150 mA Functionality • MPI Yes • DP master Yes • DP slave ...
Page 46 - rd interface
PROFINET/Industrial Ethernet CPUs for SIMATIC S7-300 CPU 319F-3 PN/DP 2/46 Siemens IK PI News · July 2007 2 ■ Technical specifications (continued) 6ES7 318-3FL00-0AB0 DP slave • Services - PG/OP communication Yes - Routing Yes - Global data communication No - S7 basic communication Yes - S7 communic...
Page 48 - PROFIBUS bus components; RS 485 repeater for PROFIBUS; PROFINET bus components; IE FC RJ45 Plugs
PROFINET/Industrial Ethernet CPUs for SIMATIC S7-300 CPU 319F-3 PN/DP 2/48 Siemens IK PI News · July 2007 2 ■ Ordering data Order No. Order No. PROFIBUS bus components PROFIBUS DP bus connector RS 485 • With 90° cable outlet, max. transmission rate 12 Mbit/s - Without PG interface 6ES7 972-0BA12-0XA...
Page 49 - • CPUs for high demands in the mid-level performance range; Product status
PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 414-3 PN/DP 2/49 Siemens IK PI News · July 2007 2 ■ Overview • CPUs for high demands in the mid-level performance range • Applicable for plants with additional demands on program- ming scope and processing speed • Integrated PROFINET functions...
Page 51 - S7 message functions
PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 414-3 PN/DP 2/51 Siemens IK PI News · July 2007 2 ■ Technical specifications (continued) 6ES7 414-3EM05-0AB0 S7 message functions Number of login stationsfor message functions, max. 31; Max. 31 with alarm_S and alarm_D (OP’s); max. 8 with alar...
Page 53 - Isochronous mode
PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 414-3 PN/DP 2/53 Siemens IK PI News · July 2007 2 ■ Technical specifications (continued) 6ES7 414-3EM05-0AB0 DP master • Number of connections, max. 16 • Services - PG/OP communication Yes - Routing Yes - Global data communication No - S7 basi...
Page 56 - • High-performance CPUs in the high-end performance range
PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416-3 PN/DP 2/56 Siemens IK PI News · July 2007 2 ■ Overview • High-performance CPUs in the high-end performance range • Applicable for plants with high requirements in the high-end performance range • Integrated PROFINET functions in CPU 416-...
Page 59 - nd interface
PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416-3 PN/DP 2/59 Siemens IK PI News · July 2007 2 ■ Technical specifications (continued) 6ES7 416-3ER05-0AB0 MPI • Number of connections 44 • Services - PG/OP communication Yes - Routing Yes - Global data communication Yes - S7 basic communica...
Page 61 - SIMATIC Manual Collection
PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416-3 PN/DP 2/61 Siemens IK PI News · July 2007 2 ■ Ordering data Order No. Order No. Manual "Communication for SIMATIC S7-300/-400" • German 6ES7 398-8EA00-8AA0 • English 6ES7 398-8EA00-8BA0 • French 6ES7 398-8EA00-8CA0 • Spanish 6ES7...
Page 62 - More information; For technical documentation to SIPLUS see:; Ambient conditions
PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 SIPLUS CPU 416-3 PN/DP 2/62 Siemens IK PI News · July 2007 2 ■ Overview • High-performance CPUs in the high-end performance range • Applicable for plants with high requirements in the high-end performance range • Integrated PROFINET functions in C...
Page 63 - PROFI
PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416F-3 PN/DP 2/63 Siemens IK PI News · July 2007 2 ■ Overview • For constructing a fail-safe automation system for plants with increased safety requirements • High-performance CPU in the top-end performance range • Satisfies safety requirement...
Page 69 - System interfacing for SIMATIC and SINUMERIK
PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 343-1 Lean 2/69 Siemens IK PI News · July 2007 2 ■ Overview • Interface for the SIMATIC S7-300 to Industrial Ethernet (not for SINUMERIK) - 2 x RJ45 interface for 10/100 Mbit/s full/half duplex connec- tion (with Autosensin...
Page 71 - Performance data; S7 communication
PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 343-1 Lean 2/71 Siemens IK PI News · July 2007 2 ■ Integration Line structure with CP 343-1 Lean with integrated real-time switch as a PROFINET IO device Example configuration of CP 343-1 Lean as PROFINET IO device ■ Techni...
Page 74 - PROFINET IO controller
PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 343-1 2/74 Siemens IK PI News · July 2007 2 ■ Design The CP 343-1 offers all the advantages of SIMATIC S7-300 system design: • Compact design; on the front, the rugged plastic housing features: - Two RJ45 sockets for connec...
Page 75 - IO controller; IO devices
PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 343-1 2/75 Siemens IK PI News · July 2007 2 ■ Integration Line structure with CP 343-1 with integrated real-time switch as a PROFINET IO controller or IO device Interfacing to higher-level network with CP 343-1 as PROFINET ...
Page 81 - • Single license for 1 installation
PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 443-1 2/81 Siemens IK PI News · July 2007 2 ■ Ordering data Order No. ■ More information The configuration software NCM S7 for Industrial Ethernetis supplied with STEP 7 V5.2. SOFTNET-S7 Lean Edition 2006 for Industrial Eth...
Page 82 - SICLOCK time synchronization; Time synchronization concepts; SICLOCK TM
PROFINET/Industrial Ethernet Accessories SICLOCK time synchronization 2/82 Siemens IK PI News · July 2007 2 ■ Overview • SICLOCK TC 400 or SICLOCK TM/TS central plant clock as the central component for time synchronization of a plant over Ethernet • SICLOCK TC 400; - Four independent Ethernet interf...
Page 83 - SICLOCK TC 400 central plant clock
PROFINET/Industrial Ethernet Accessories SICLOCK time synchronization 2/83 Siemens IK PI News · July 2007 2 ■ Ordering data Order No. Order No. SICLOCK TC 400 central plant clock SICLOCK TM central plant clock SICLOCK TM central plant clock (continued) SICLOCK TS central plant clock SICLOCK TC 400 p...
Page 84 - DCF radio clocks; Accessories for SICLOCK DCFS7; SICLOCK DCFS7 interface
PROFINET/Industrial Ethernet Accessories SICLOCK time synchronization 2/84 Siemens IK PI News · July 2007 2 ■ Ordering data Order No. Order No. DCF radio clocks GPS radio clocks SICLOCK DCFRS, radio clock, industrial version 2XV9 450-1AR21 DCF radio clock for time syn-chronization of individual PCs ...
Page 85 - SIEMENS AG; Software; SICLOCK EOPC; Displays
PROFINET/Industrial Ethernet Accessories SICLOCK time synchronization 2/85 Siemens IK PI News · July 2007 2 ■ Ordering data Order No. Accessories ■ More information SIEMENS AG I&S EDM V ERL Frauenauracher Str. 98 91020 Erlangen, Germany SICLOCK hotline Phone: +49 (0)9131 18-82010 Fax: +49 (0)913...
Page 86 - Distributed I/O ET 200S; IM 151-3PN interface module; • Interface module for linking the ET 200S to PROFINET
PROFINET/Industrial Ethernet Distributed I/O ET 200S IM 151-3PN interface module 2/86 Siemens IK PI News · July 2007 2 ■ Overview • Interface module for linking the ET 200S to PROFINET • Handles all data exchange with the PROFIBUS I/O controller • 3 versions: - IM151-3 PN STANDARD- IM151-3 PN HIGH F...
Page 87 - Isolation
PROFINET/Industrial Ethernet Distributed I/O ET 200S IM 151-3PN interface module 2/87 Siemens IK PI News · July 2007 2 ■ Technical specifications (continued) 6ES7 151-3AA22-0AB0 6ES7 151-3BA22-0AB0 6ES7 151-3BB22-0AB0 Status information/alarms/diagnostics Alarms • Alarms Yes Yes Yes Diagnoses • Diag...
Page 89 - Terminating module
PROFINET/Industrial Ethernet Distributed I/O ET 200S IM 151-3PN interface module 2/89 Siemens IK PI News · July 2007 2 ■ Ordering data Order No. Order No. Label sheets DIN A4 (10 units) Each sheet contains 60 label strips for peripheral modules and 20 label strips for interface modules • petrol 6ES7...
Page 94 - as an IO device
PROFINET/Industrial Ethernet ET 200M IM 153-4 PN 2/94 Siemens IK PI News · July 2007 2 ■ Overview • To connect ET 200M to PROFINET IO (via copper line, RJ45) as an IO device • Integrated 2-port switch • 12 modules per station • Usable I/O capacity: 192 byte each • Active bus backplane to hot-swap mo...
Page 95 - IM 153-4 PN interface module; Bus modules for ET 200M
PROFINET/Industrial Ethernet ET 200M IM 153-4 PN 2/95 Siemens IK PI News · July 2007 2 ■ Ordering data Order No. Order No. 1) To operate the IM153-4, an MMC is required with at least 64 KB memory. Cards with higher memory capacity may also be used. IM 153-4 PN interface module 6ES7 153-4AA00-0XB0 I/...
Page 96 - SIMOTION Motion Control System; Interfaces; PROFINET version; Compatible panel fronts
PROFINET/Industrial Ethernet SIMOTION Motion Control System SIMOTION P350-3 2/96 Siemens IK PI News · July 2007 2 ■ Overview SIMOTION P350-3 is a PC-based motion control system. The use of an industrial PC platform facilitates the running of the SIMOTION machine application (comprising controller, m...
Page 97 - SIMOTION
PROFINET/Industrial Ethernet SIMOTION Motion Control System SIMOTION P350-3 2/97 Siemens IK PI News · July 2007 2 ■ Integration Overview of the SIMOTION P350-3 connections ■ Technical specifications SIMOTION P350-3 X4 X2 X102 X101 Ethernet PROFIBUS DP PCI-Slot SINAMICS S120 RS 232 More standard PC i...
Page 100 - Functional faults can occur when using longer cables.; Digital inputs
PROFINET/Industrial Ethernet SIMOTION Motion Control System SIMOTION D410 2/100 Siemens IK PI News · July 2007 2 ■ Integration Overview of SIMOTION D410 connections The maximum permissible cable lengths should be taken into account when planning the cable layout. Functional faults can occur when usi...
Page 101 - Further information
PROFINET/Industrial Ethernet SIMOTION Motion Control System SIMOTION D410 2/101 Siemens IK PI News · July 2007 2 ■ Ordering data Order No. ■ More information Further information • on ordering other SINAMICS drive components such as Line Modules, Motor Modules, DRIVE-CLiQ cables, etc., refer to the i...
Page 102 - SINUMERIK CNC automation systems
PROFINET/Industrial Ethernet SINUMERIK CNC automation systems NCU 730.2 PN 2/102 Siemens IK PI News · July 2007 2 ■ Overview The NCU 730.2 PN is the new flagship of the SINUMERIK 840D sl and, with a significantly higher PLC capacity than an NCU 730.1, represents the most advanced configuration withi...
Page 104 - ET 200pro — RFID Systems; PROFINET IO
PROFINET/Industrial Ethernet ET 200pro — RFID Systems SIMATIC RF180C 2/104 Siemens IK PI News · July 2007 2 ■ Overview The SIMATIC RF180C is a communication module for direct con-nection of Siemens RFID systems to PROFINET IO. The readers (SLGs) of the RFID systems MOBY D, U and RF300 can be operate...
Page 106 - Accessories for MOBY; SLG cable for MOBY D; Accessories for connection to the network; PROFINET standard cable 2x2
PROFINET/Industrial Ethernet ET 200pro — RFID Systems SIMATIC RF180C 2/106 Siemens IK PI News · July 2007 2 ■ Ordering data Order No. Order No. 1) This cable is available in different lengths (see Catalog IK PI · 2007 or in the Internet under: http://www.siemens.com/automation/mall ) SIMATIC RF180C ...