Siemens EA 726 Series - User Manual
Siemens EA 726 Series – User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – System overview; Cluster; Syno; Possible extensions for card cage; CPS Fire Safety
- Page 3 – Networking topologies; Building Technologies
- Page 5 – Control panel
- Page 6 – FC726 configuration; Basic equipment
- Page 7 – Technical data
- Page 8 – Details for ordering
FC726
Cerberus
™
PRO
Fire control panel
FS720 series (IP5)
Modular, prefabricated, microprocessor-controlled fire control panel with
integrated user-friendly operating unit for up to max. 1512 addresses
Processes signals from various devices like:
- FD720 devices of the Cerberus PRO series and SynoLOOP devices
Fire control panel can be used as stand-alone version or can be networked
Up to 64 stations (fire control panels and fire terminals) can be connected in
one network
Integrated degraded mode function
Redundant network node, degraded mode operation according to EN54
Fast Ethernet interface for a heterogeneous network
Option of printer, key switches, LED displays
Slots for serial ports and max. 5 extra cards
- Line card C-NET (For migration)
- SynoLOOP line card
Emergency power supply for emergency operating time of up to 72 hours
Detection and automatic reading in (auto configuration) of all Cerberus PRO
devices, ready for operation immediately
Floor repeater devices, alarm devices and mimic displays in detector loop
(C-NET)
Flexible programming of complex applications and controls
Stored data can be uploaded via remote access
Firmware download of all processor controlled control panel components
Building Technologies
CPS Fire Safety
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
System overview Fire control panel FC10 or XC10 Fire detection or Extinguishing control unit collective 4 (8) loops max. 504 adresses 4 inputs 4 outputs FT2010/FT2011 Floor repeater terminal / Floor repeater display 24VDC ext. possible 1 input 2 inputs/outputs optionally Explosion- hazard area Remot...
Networking topologies Up to 32 fire control panels und fire control terminals can be connected in a single clus-ter (C-WEB/SAFEDLINK) or up to 16 stations when the cluster is connected to a dan-ger management system. Using a fiber-optic Backbone (C-WEB/LAN) up to 14 of the above mentioned clusters (...
Application ranges The FC726 is ideally suited for medium-sized applications, e.g. hotels, high schools, office complexes, etc. or when networked as part of much larger applications. The FC726 can be used by the flexible cross-linking possibilities however also for ex-tensive systems. Operation Each...