Compact
Universal Controllers
RWF40...
The RWF40... is a universal digital boiler temperature / pressure controller with
functions designed specifically for the control of heat generating plant.
The RWF40... and this Data Sheet are intended for use by OEMs which integrate
the controller in their products!
Mechanical design
The controller is supplied complete with housing for flush panel mounting. The
RWF40... is matched to the controlled variable and the required setpoint range by mak-
ing parameter settings. The control parameters can be set and optimized while the
burner is running. All settings are made with 4 buttons located on the unit front and are
directly displayed.
LEDs on the front indicate the following operating states:
-
Control ON / OFF
-
Positioning pulses ON or OFF for driving the burner´s air damper when using
modulating burner control, or stage I / stage II when using 2-stage burner control
-
«2-stage» operating mode
-
Position of the configurable contact «K6»
-
Manual control ON / OFF
During operation, the digital display above the LEDs shows the setpoint (green), the
actual value (red) and – when making parameter settings – the relevant parameters.
RWF40... complete with housing
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
2/10 Building Technologies CC1N7865en HVAC Products 01.09.2005 Warning notes To avoid injury to persons, damage to property or the environment, the following warning notes should be observed! Do not open, interfere with or modify the controller! • All activities (mounting, installation and service w...
4/10 Building Technologies CC1N7865en HVAC Products 01.09.2005 Technical data Mains voltage AC 110...240 V +10 % / -10 % Mains frequency 48...63 Hz Safety class II to DIN 0631 Mounting position optional Terminals for 2 x 1.5 mm² or 1 x 2.5 mm² Power consumption max. 10 VA Safety extra low-voltage DC...
5/10 Building Technologies CC1N7865en HVAC Products 01.09.2005 Function The RWF40... provides the following functions: - One digital PID controller with a 3-position or analog output (optional) - To control 2-stage burners, the RWF40... can be switched over to provide 2-position control - Automatic ...