Siemens 331-2856 - User Manual

Siemens 331-2856

Siemens 331-2856 – User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
Page: / 12

Table of Contents:

  • Page 2 – Table 1. Product Numbers for No. 6 Pneumatic Damper Actuators.; Product Numbers; Specifications
  • Page 3 – Accessories; TB-128 POWERSTM Controls Damper Shaft Extension; Service Kits
  • Page 4 – Actuator Sizing; Calculate the total torque required to move the damper:; Page 4
  • Page 5 – Operation; Order one of the following and see Table 4 for parts lists:
  • Page 6 – Table 4. Extended Shaft/Frame Mounting Assemblies Components.; Page 6
  • Page 7 – Position the crank driven by the actuator as follows:
  • Page 8 – Follow the steps in; Attached to Frame Mounting Kit 752.; Page 8
  • Page 9 – Attach the mounting plate to the mounting lug as follows:
  • Page 10 – Actuator Mounting
  • Page 11 – Dimensions; Figure 13. Extended Shaft Remote Mounting with Travel Stops.; Depending on
  • Page 12 – RL 147 Positioning Relay Mounting.
Loading the manual



POWERS™ Controls

Technical Instructions

Document No. 155-029P25

AP 331-3

December 3, 2004

No. 6 Pneumatic Damper Actuator

331-2793 Actuator

331-2857 Actuator

with Clevis and Pin

331-3012 Extended Shaft and Frame

Mounting

Description

The POWERS Controls No. 6 Pneumatic Damper Actuator is a heavy-duty, rolling
diaphragm, spring return actuator designed to drive large dampers, centrifugal
refrigeration inlet vanes, and other applications requiring a large, effective diaphragm
area and long stroke.

Features

All metal body construction

Replaceable ozone-resistant, silicone rubber, rolling diaphragm

Pivot mounting for extended shaft or frame mounting

Positioning relay (optional)

Adjustable forward travel stops (optional)

Three spring ranges for sequencing with other control devices

Product Numbers

See Table 1.

Application

The No. 6 Pneumatic Damper Actuator controls outdoor, return air, exhaust, face and
bypass, and fan discharge dampers. It is recommended for heavy-duty applications
using multi-section dampers where either unison or sequence operation is required.

Certain actuators in Table 1 are UL Recognized Components for
fire/smoke applications under category EMKU2. This category covers
pneumatic damper actuators used on fire dampers and leakage rated
dampers.

Siemens Building Technologies, Inc.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Table 1. Product Numbers for No. 6 Pneumatic Damper Actuators.; Product Numbers; Specifications

Technical Instructions POWERS™ Controls No. 6 Pneumatic Damper Actuator Document No. 155-029P25 December 3, 2004 Table 1. Product Numbers for No. 6 Pneumatic Damper Actuators. Product Numbers Nominal Spring Range Description Mounting Style 3-8 psi (21-55 kPa) 3-13 psi (21-90 kPa) 8-13 psi (55-90 kPa...

Page 3 - Accessories; TB-128 POWERSTM Controls Damper Shaft Extension; Service Kits

POWERS™ Controls No. 6 Pneumatic Damper Actuator Technical Instructions Document No. 155-029P25 December 3, 2004 Accessories Damper shaft extension kits: 1/2-inch (13-mm) diameter, 2-1/4 inch (57-mm) rod 331-631 (See TB-128 POWERS™ Controls Damper Shaft Extension Technical Bulletin 155-205P25) 1/2-i...

Page 4 - Actuator Sizing; Calculate the total torque required to move the damper:; Page 4

Technical Instructions POWERS™ Controls No. 6 Pneumatic Damper Actuator Document No. 155-029P25 December 3, 2004 Actuator Sizing The quantity of actuators required depends on several torque factors. To determine the quantity of actuators required for the installation: 1. Obtain damper torque ratings...

Other Siemens Models