Page 3 - Special Symbols; RISK OF ELECTRIC SHOCK; ON; OFF; PHASE
Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol. CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for additi...
Page 4 - This page intentionally left blank.
Page 5 - Table of Contents; Introduction; Section I – Installation; UPS Installation Plan and Unpacking
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com i Table of Contents 1 Introduction 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 6 - Section II – Operation
TABLE OF CONTENTS EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com ii 5 Installing a Remote Emergency Power-off Control 5-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1 REPO Installation ...
Page 7 - 1 Responding to System Events
TABLE OF CONTENTS EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com iii 10.4 Optional Relay Interface Module 10-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 8 - 4 Product Specifications
TABLE OF CONTENTS EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com iv 14 Product Specifications 14-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14....
Page 9 - List of Figures
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com v List of Figures Figure 1‐1. Typical Powerware 9315 (500–750 kVA) UPS System 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figur...
Page 11 - Chapter 1; The Eaton
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 1-1 Chapter 1 Introduction The Eaton ® Powerware ® 9315 (500–750 kVA) uninterruptible power supply (UPS) is an online power protection system that prevents loss of valuable electronic infor...
Page 12 - UPS Features; The UPS has the following communication features:; Building Alarm Monitoring; – The facility's alarm system contacts can be connected; Summary Alarm Contacts; – Summary alarm contacts are provided for connection to; Computer Interface; – Two serial communication ports are standard on all units, and; Communication Bay; – One communication bay is available on the UPS to
INTRODUCTION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 1-2 1.1 UPS Features The UPS has many standard features that provide cost‐effective and consistentlyreliable power protection. The descriptions in this section provide a brief ...
Page 13 - Options and Accessories; Battery Racks; With Powerware Hot Sync
INTRODUCTION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 1-3 1.2 Options and Accessories Contact your Eaton sales representative for information about the following options: 1.2.1 5% Input Filter The UPS can be equipped with an input...
Page 14 - Monitoring and Communication; eNotify Remote Monitoring and Diagnostic Service; Basic System Configurations
INTRODUCTION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 1-4 1.2.6 Monitoring and Communication The following monitoring and communication options are available: S Remote Monitor Panel (RMP) – An optional RMP contains backlit status ...
Page 15 - Safety Warnings; IMPORTANT SAFETY INSTRUCTIONS; This UPS contains; LETHAL VOLTAGES; . All maintenance and service should be performed by; AUTHORIZED SERVICE PERSONNEL ONLY; Do not operate the UPS system close to gas or electric heat sources.
INTRODUCTION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 1-5 1.4 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS S This manual contains important instructions that should be followed during installation and main...
Page 16 - Conventions Used in This Manual; Italic type; Bold type; Icon; UPS; For More Information; Operation Manual
INTRODUCTION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 1-6 A V E R T I S S E M E N T ! S Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par des courts‐circuits dehaute intensité. Prendre les précauti...
Page 17 - Getting Help; Call your local service representative
INTRODUCTION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 1-7 1.7 Getting Help If you need help with any of the following: S Scheduling initial startup S Regional locations and telephone numbers S A question about any of the informati...
Page 19 - Section I
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 1-1 Section I Installation
Page 21 - Chapter 2; Use the following basic sequence of steps to install the UPS:; NOTE; Creating an Installation Plan; Preparing Your Site; Failure to follow guidelines may void your warranty.
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 2-1 Chapter 2 UPS Installation Plan and Unpacking Use the following basic sequence of steps to install the UPS: 1. Create an installation plan for the UPS system (Chapter 2). 2. Prepare you...
Page 22 - Preparing for Wiring the UPS System; C. If the ambient temperature is greater than 30°; Inspecting and Unpacking Each Cabinet; Figure 2‐1. Cabinet as Shipped with Outer Packaging and Pallet; To unpack the cabinet:
UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 2-2 2.1.3 Preparing for Wiring the UPS System For external wiring requirements, including the minimum AWG size of external wiring,see Table E through Tab...
Page 25 - Chapter 3; Preliminary Installation Information; . All repairs and service should be performed by; AUTHORIZED; Installation should be performed only by qualified personnel.; Refer to the following while installing the UPS system:
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 3-1 Chapter 3 Installing the UPS System This section describes the UPS system installation for single modules andmulti-modules, including: unloading the cabinets, UPS internal and external ...
Page 26 - Unloading the UPS Cabinets from the Pallet; To remove the pallet:; Single Module Installation; Installing UPS Internal Power and Control Wiring
INSTALLING THE UPS SYSTEM EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 3-2 3.2 Unloading the UPS Cabinets from the Pallet W A R N I N G S The UPS cabinets are heavy (see Table A on page A-1). If unpacking instructions are not closely ...
Page 27 - Reinstall the plastic shield to the inverter input section.; Installing UPS External Power and Control Wiring
INSTALLING THE UPS SYSTEM EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 3-3 4. Connect the negative DC Link power wiring to the inverter input. Connect twocables to each inverter. 5. Reinstall the plastic shield to the inverter input s...
Page 28 - Multi‐Module Installation; Reinstall the plastic shield to inverter input section.
INSTALLING THE UPS SYSTEM EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 3-4 NOTE Remove the entire MBC top panel to punch conduit holes. 4. Connect phase A, B, and C power wiring from the bypass source to therespective bypass inputs in...
Page 29 - Refer to the
INSTALLING THE UPS SYSTEM EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 3-5 8. Connect the Output/Inverter 15‐pin control wiring harness connector to theInput/Rectifier 15‐pin control wiring harness connector. See Figure A‐12 onpage A-...
Page 30 - Installing Input/Rectifier Customer Connections; Installing Output/Inverter Customer Connections; To prepare the UPS for wiring to customer connections:; Installing Accessories
INSTALLING THE UPS SYSTEM EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 3-6 3.5 Installing Input/Rectifier Customer Connections NOTE If you are installing connections to the Battery I/O terminal connections and terminal board CB2TB, in...
Page 31 - Completing the Installation Checklist
INSTALLING THE UPS SYSTEM EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 3-7 3.9 Completing the Installation Checklist The final step in installing the UPS system is completing the following installationchecklist. This checklist ensures...
Page 32 - Installation Checklist; All power cables are properly sized and terminated.
INSTALLING THE UPS SYSTEM EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 3-8 Installation Checklist - All packing materials and restraints have been removed from each cabinet. - Each cabinet in the UPS system is placed in its final inst...
Page 33 - Notes
INSTALLING THE UPS SYSTEM EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 3-9 Notes _________________________________________________________________________ _________________________________________________________________________ _____...
Page 35 - Chapter 4; Figure 4‐1. Remote Battery Disconnect Enclosure
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 4-1 Chapter 4 Installing a Remote Battery Disconnect The remote battery disconnect is crated separately for shipping. The enclosure isdesigned to be free‐standing. You can install a remote ...
Page 36 - Table 4‐1 details the power cable terminations.
INSTALLING A REMOTE BATTERY DISCONNECT EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 4-2 S Nominal voltages listed in this chapter are for a lead‐acid batteries rated per NEC at2.00 Vdc per cell. S Battery strings must be installed acc...
Page 37 - Chapter 5; Figure 5‐1. Eaton REPO Switch; REPO Installation; To install a REPO station:
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 5-1 Chapter 5 Installing a Remote Emergency Power-off Control A latching-type Remote Emergency Power-off (REPO) switch can be used in anemergency to shut down the UPS and remove power to th...
Page 38 - Figure 5‐2. REPO Wiring; REPO Operation; Figure 5‐3. REPO Operation
INSTALLING A REMOTE EMERGENCY POWER-OFF CONTROL EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 5-2 NOTE REPO switch rating is 6A/120 Vac or 3A/240 Vac. The REPO switch must be a latching-type switch with a dedicated circuit. REPO Switch...
Page 39 - Chapter 6; Table 6‐1. Optional Monitoring Accessories; Number and Type of Accessories Permitted
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 6-1 Chapter 6 Installing Optional Accessories This chapter contains installation information for the following options: S Monitoring accessories: Remote Monitor Panel (RMP), Relay Interface...
Page 40 - Installing an RMP
INSTALLING OPTIONAL ACCESSORIES EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 6-2 6.1 Installing an RMP As an option, you can install an RMP to monitor the UPS system operation fromvirtually any location within your facility, up to 152...
Page 41 - Securely mount the RMP.; Figure 6‐2. Terminal Block Bracket
INSTALLING OPTIONAL ACCESSORIES EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 6-3 To install an RMP: 1. Verify that the UPS system is turned off and all power sources are removed. SeeChapter 9, “UPS Operating Instructions,” for shutdow...
Page 42 - Table 6‐2. RMP Wire Terminations; From RMP A; Repeat Steps 1 through 8 if you are installing another RMP.
INSTALLING OPTIONAL ACCESSORIES EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 6-4 6. Connect the RMP wiring to the terminal block using terminations shown inTable 6‐2. Table 6‐2. RMP Wire Terminations From RMP A To UPS Remarks TB1‐4 TB...
Page 43 - Installing an RIM; Securely mount the RIM.
INSTALLING OPTIONAL ACCESSORIES EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 6-5 6.2 Installing an RIM The optional RIM uses relay contact closures to indicate the UPS system operatingstatus and alarm condition. The module uses an RS‐...
Page 44 - Figure 6‐4. Terminal Block Bracket; From RIM A; Repeat Steps 1 through 7 if you are installing another RIM.
INSTALLING OPTIONAL ACCESSORIES EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 6-6 Connect to Port 1 (DB‐9) on Customer Interface Panel Fuse TerminalBlock(TB3) Figure 6‐4. Terminal Block Bracket 6. Connect RIM wiring to the terminal blo...
Page 45 - Installing an SCM; Securely mount the SCM.
INSTALLING OPTIONAL ACCESSORIES EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 6-7 6.3 Installing an SCM The optional SCM shown in Figure 6‐5 provides contacts for monitoring UPS systemstatus. See Figure A‐29 page A-41 for enclosure dim...
Page 46 - Figure 6‐6. Terminal Block Bracket; From SCM A; Repeat Steps 1 through 7 if you are installing another SCM.
INSTALLING OPTIONAL ACCESSORIES EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 6-8 Connect to Port 1 (DB‐9) on Customer Interface Panel Fuse TerminalBlock(TB3) Figure 6‐6. Terminal Block Bracket 6. Connect the SCM wiring to the terminal...
Page 48 - Installing X-Slot Cards; Install the X-Slot card into the communication bay.
INSTALLING OPTIONAL ACCESSORIES EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 6-10 6.4 Installing X-Slot Cards NOTE LAN and telephone drops for use with X-Slot cards must be provided by facility planners or the customer. NOTE For setup...
Page 49 - Section II
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 6-11 Section II Operation
Page 51 - Chapter 7; In this manual, the power required by your equipment is called the; Figure 7‐1. Main Elements of the UPS System
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 7-1 Chapter 7 Understanding UPS Operation The Powerware 9315 is a continuous duty, solid‐state UPS that supports thefollowing equipment: process control, data processing, telecommunications...
Page 52 - Operating Modes; Normal mode; command
UNDERSTANDING UPS OPERATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 7-2 If utility power is interrupted or falls outside the parameters specified in Chapter 14,“Product Specifications,” the UPS uses a backup battery supply to mai...
Page 53 - Normal Mode; System Normal
UNDERSTANDING UPS OPERATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 7-3 7.1.1 Normal Mode In Normal mode, utility AC power is supplied to the rectifier. The rectifier supplies DCpower to the inverter, which then supplies the crit...
Page 54 - Bypass Mode; The critical load is not protected while the UPS is in Bypass mode.; Figure 7‐3. Path of Current Through the UPS in Bypass Mode
UNDERSTANDING UPS OPERATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 7-4 7.1.2 Bypass Mode The UPS automatically switches to Bypass mode if it detects an overload, load fault,or internal failure. The bypass source supplies the com...
Page 55 - Battery Mode; Figure 7‐4. Path of Current Through the UPS in Battery Mode
UNDERSTANDING UPS OPERATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 7-5 7.1.3 Battery Mode The UPS transfers to Battery mode automatically if a utility power outage occurs, or ifthe utility power does not conform to specified par...
Page 57 - Chapter 8; Figure 8‐1. UPS Control Panel
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 8-1 Chapter 8 Using the Control Panel This chapter describes the UPS control panel, including controls and indicators, andhow to monitor UPS operation. The control panel is a black square a...
Page 58 - Using the LCD Screen; Figure 8‐2. LCD Screen
USING THE CONTROL PANEL EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 8-2 8.1 Using the LCD Screen The LCD screen at the top of the control panel provides an operator interface with theUPS system. Figure 8‐2 identifies the display fiel...
Page 59 - Using the Pushbuttons; Figure 8‐3. LCD Pushbuttons; Adjusting the Contrast
USING THE CONTROL PANEL EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 8-3 Use the LCD screen and the pushbuttons beneath it to: S Monitor UPS operation S Look at a log of UPS events (alarms, notices, and commands) 8.2 Using the Pushbut...
Page 60 - Reading the Status Indicators; Meters; – Displays performance meters for the system or critical load.; Events; – Displays the list of Active System Events and a historical log of; Statistics; through the internal UPS components.; Setup; time for the time stamp.
USING THE CONTROL PANEL EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 8-4 8.4 Reading the Status Indicators The six symbols on the left side of the control panel are status indicators. They arebacklit by colored LED lamps, and they wor...
Page 61 - System Meters Screen; Figure 8‐4. System Meters Screen
USING THE CONTROL PANEL EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 8-5 8.5.1 System Meters Screen Figure 8‐4 shows the LCD screen as it appears when you first start the UPS. TheMeters menu is displayed in the menu box, with the Syst...
Page 62 - Load Amps Meters Screen; Select; Load Amps; from the Meters menu to view a real‐time bar graph of the output; Figure 8‐5. Load Amps Meters Screen
USING THE CONTROL PANEL EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 8-6 8.5.2 Load Amps Meters Screen Select Load Amps from the Meters menu to view a real‐time bar graph of the output current of the UPS. The graph shows the current f...
Page 63 - Software Versions Screen; Versions; from the Meters menu to view the software versions installed on; Figure 8‐6. Software Versions Screen
USING THE CONTROL PANEL EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 8-7 8.5.3 Software Versions Screen Select Versions from the Meters menu to view the software versions installed on the UPS. Figure 8‐6 shows the Software Versions sc...
Page 64 - Event History Log Screen; from the Events menu to display the Event History Log. The Event; Figure 8‐7. Event History Log Screen
USING THE CONTROL PANEL EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 8-8 8.5.4 Event History Log Screen Select History from the Events menu to display the Event History Log. The Event History Log lists up to 400 system events in chron...
Page 65 - Active System Events Screen; Active; Figure 8‐8 shows the Active System Events screen.; Figure 8‐8. Active System Events Screen
USING THE CONTROL PANEL EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 8-9 8.5.5 Active System Events Screen Select Active from the Events menu to display a listing of all system events that are currently active. The most recent system ...
Page 66 - Unit Statistics Screen; Unit; Figure 8‐9 shows the Unit Statistics screen.; Figure 8‐9. Unit Statistics Screen
USING THE CONTROL PANEL EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 8-10 8.5.6 Unit Statistics Screen Select Unit from the Statistics menu to display a listing of statistics about UPS operation. Figure 8‐9 shows the Unit Statistics s...
Page 67 - Mimic Screen; Mimic; of the flow of current through the UPS.; Figure 8‐10. Mimic Screen
USING THE CONTROL PANEL EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 8-11 8.5.7 Mimic Screen Select Mimic from the Graphics menu to display a real‐time graphical representation of the flow of current through the UPS. Figure 8‐10 shows...
Page 68 - Time Setup Screen; Time; from the Setup menu to display the Time Setup screen. The Time Setup; Figure 8‐11. Time Setup Screen
USING THE CONTROL PANEL EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 8-12 8.5.8 Time Setup Screen Select Time from the Setup menu to display the Time Setup screen. The Time Setup screen allows you to set the internal time stamp of the...
Page 69 - Port Setup Screen; Figure 8‐12. Port Setup Screen
USING THE CONTROL PANEL EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 8-13 8.5.9 Port Setup Screen Select Port 1 or Port 2 from the Setup menu to display one of the Port Setup screens. The Port Setup screens allow you to specify settin...
Page 71 - Chapter 9; UPS Controls and Indicators; Figure 9‐1. UPS Controls and Indicators
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 9-1 Chapter 9 UPS Operating Instructions This chapter describes the UPS controls and instructions for operating the UPSsystem. NOTE Before starting the UPS, ensure all installation tasks ar...
Page 72 - Control Panel; Off; UPS Circuit Breakers; The UPS can contain as many as four circuit breakers:; Emergency UPM Off; An Emergency UPM
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 9-2 9.1.1 Control Panel The UPS control panel contains an LCD screen to display the current UPS systemstatus. You can view a statistical history and log of system...
Page 73 - Starting the UPS
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 9-3 9.2 Starting the UPS To start the UPS system: NOTE This procedure assumes Automode is enabled. 1. Verify that the UPS circuit breakers are set as follows: UPS...
Page 74 - On the UPS, turn the Mode key switch to NORMAL for one second.; Starting the UPS in Bypass Mode; Verify that the UPS circuit breakers are set as follows:
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 9-4 13. If system is equipped with motor operated breaker CB2, proceed to Step 14;otherwise, proceed to Step 16. 14. Confirm UPS Battery Breaker CB2 has closed by...
Page 75 - Transferring to Bypass Mode; On Bypass; Transferring to Normal Mode; Normal
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 9-5 9.4 Transferring to Bypass Mode NOTE In the following step, holding the Mode key switch in the BYPASS position for three seconds transfers the load to Bypass ...
Page 76 - Transferring to Bypass and Shutting Down the UPS; Shutting Down the UPS and Critical Load
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 9-6 9.6 Transferring to Bypass and Shutting Down the UPS To transfer the critical load to Bypass mode and shut down the UPS: 1. On the UPS, turn the Mode key swit...
Page 77 - Using the UPS Emergency UPM Off Pushbutton; Press the Emergency UPM Off pushbutton.; Resetting the UPS System after an Emergency UPM Off; To reset the UPS system:
UPS OPERATING INSTRUCTIONS EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 9-7 To restart the UPS after pressing the Emergency UPM Off pushbutton, follow theprocedure in paragraph 9.8.2, “Resetting the UPS System after an Emergency UPMOf...
Page 79 - Using Features and Options
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 10-1 Chapter 10 Using Features and Options The many standard features of your UPS system provide consistent, economical, anddependable power protection. In addition, you can add available o...
Page 80 - Optional Remote Monitor Panel
USING FEATURES AND OPTIONS EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 10-2 10.3 Optional Remote Monitor Panel The optional Remote Monitor Panel (RMP) monitors the UPS system operating statusand alarm condition from virtually any loc...
Page 82 - Optional Relay Interface Module; The RIM can provide the following signals:
USING FEATURES AND OPTIONS EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 10-4 10.4 Optional Relay Interface Module The optional Relay Interface Module (RIM) uses relay contact closures to indicate theoperating status and alarm conditio...
Page 83 - Optional Supervisory Contact Module; The SCM provides signals for the following indications:
USING FEATURES AND OPTIONS EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 10-5 10.5 Optional Supervisory Contact Module An optional Supervisory Contact Module (SCM) establishes an interface between theParallel Capacity/Redundant system ...
Page 85 - Responding to System Events; from the Events menu on the LCD screen to display the Active System; System Event Horns; When a notice occurs, the horn beeps at two‐second intervals.; System Event Indicators
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 11-1 Chapter 11 Responding to System Events When the UPS system is operating in Normal mode, it continually monitors itself andthe incoming utility power. In Battery or Bypass modes, the UP...
Page 87 - Communication; Locating the Customer Interface Panel; The customer interface panel inside the UPS contains:; Connecting Equipment to a Serial Port; Pin Number
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 12-1 Chapter 12 Communication This chapter describes the communication features of the Powerware 9315 UPS andprovides information about connecting hardware, configuring the ports, changings...
Page 89 - Configuring the Serial Ports; Figure 12‐3. Setup Serial Port 1 Screen
COMMUNICATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 12-3 12.3 Configuring the Serial Ports Configure the communication port using the LCD screen and pushbuttons on the UPScontrol panel. Select Port 1 or Port 2 from the Setup me...
Page 90 - Table 12‐3. Options Available for Each Communication Port; Options; Modes; Terminal Mode; Rate
COMMUNICATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 12-4 Table 12‐3. Options Available for Each Communication Port Port 1 Port 2 Options X X Terminal Mode X X System Configuration Mode X Calibration Mode X Computer Mode X Remot...
Page 91 - Handshaking; – If handshaking is enabled, the UPS uses special characters (XON and; Save
COMMUNICATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 12-5 12.3.3 Data/Stop The data size and stop bits of the equipment connected to this port determine thenumber of bits transmitted per ASCII character. The data size and stop b...
Page 92 - Symbol; Printing Selected Information
COMMUNICATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 12-6 12.4 Terminal Mode In this mode, system events are continually logged through the serial port to thedevice connected to the port. Port 2 operates by default in Terminal m...
Page 93 - Figure 12‐4. Event History Log
COMMUNICATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 12-7 12.4.2 Entire Log [Ctrl]+[P] The [Ctrl]+[P] key sequence prints the entire UPS Event History Log at the time thedata is requested. The printout begins with the oldest ala...
Page 94 - Figure 12‐5. System Meters Screen
COMMUNICATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 12-8 12.4.3 Meters Printout [Ctrl]+[M] The [Ctrl]+[M] key sequence prints the current readings of the UPS system meters.The Input area shows the phase‐to‐phase voltage, freque...
Page 95 - System Configuration Mode; System Configuration Mode Main Menu; following menu is displayed:
COMMUNICATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 12-9 12.5 System Configuration Mode The System Configuration mode allows you to modify special functions in your UPS.These functions include programming of building alarms, cu...
Page 96 - Function; Customize Alarm Messages
COMMUNICATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 12-10 If you select 1 , 2 , or 3 from this menu, the following menu is displayed: Enable/Disable ( Function ) Enabled Building Alarm Number(s) 1 4 Enter E# to Enable Building ...
Page 97 - Enter E to Enable Custom Message; Program Unit Name; Change Password
COMMUNICATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 12-11 At this level you can enter a custom message, 30 characters maximum, to displaywhen Building Alarm 1 is activated. If a custom message is entered to activate thebuilding...
Page 98 - Battery Test Setup
COMMUNICATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 12-12 12.5.7 Battery Test Setup If Battery Test Setup (option 5 ) is selected from the Main menu (see page 12-9), the following menu is displayed: NOTE If a message stating “B...
Page 99 - Modify Low Battery Time; If Modify Low Battery Time (option; To change the Low Battery Time warning level, enter a new time.; Calibration Mode; Computer Mode
COMMUNICATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 12-13 12.5.8 Modify Low Battery Time If Modify Low Battery Time (option 6 ) is selected from the Main menu (see page 12-9), the following menu is displayed: Modify Low Battery...
Page 100 - eNotify Service; eNotify Service Features
COMMUNICATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 12-14 12.9 eNotify Service The Powerware 9315 UPS supports Eaton's eNotify Remote Monitoring andDiagnostic Service. The eNotify Service is included at no charge during the fir...
Page 101 - Four separate, programmable notification groups (phone numbers); Call Answer; – The Call Answer function allows the user to call into the UPS from a; Call Out; – The Housekeeping function maintains the link between the UPS
COMMUNICATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 12-15 12.10 Remote Notification For connection and setup of a modem, or to enable Remote Notify and Call Homefeatures within the UPS, please contact Eaton (see page 1-7). Remo...
Page 102 - Power Xpert Gateway Card
COMMUNICATION EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 12-16 12.11 X-Slot Cards The Powerware 9315 UPS has one factory‐installed X-Slot communication bay. SeeFigure A‐13 on page A-23 for the bay location. The UPS is compatible wit...
Page 103 - Maintaining the UPS System; Important Safety Instructions; Remember that your UPS system is designed to supply power; EVEN WHEN; . The UPS cabinet interiors are unsafe until; DO NOT ATTEMPT
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 13-1 Chapter 13 Maintaining the UPS System The components inside the UPS cabinet are secured to a sturdy metal frame that issupported by the UPS magnetics. This design allows authorized ser...
Page 104 - Performing Preventive Maintenance; Daily Maintenance
MAINTAINING THE UPS SYSTEM EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 13-2 13.2 Performing Preventive Maintenance The UPS system requires very little preventive maintenance. However, inspect theUPS system periodically to verify that...
Page 105 - Battery Maintenance; Recycling the Used Battery or UPS
MAINTAINING THE UPS SYSTEM EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 13-3 13.2.4 Battery Maintenance NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode. Contact your Eaton service representative for battery maint...
Page 107 - Product Specifications; Model Numbers
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 14-1 Chapter 14 Product Specifications The following sections detail the input, output, environmental, and batteryspecifications for the UPS. 14.1 Model Numbers The UPS systems are housed i...
Page 108 - UPS System Output; Environmental Specifications
PRODUCT SPECIFICATIONS EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 14-2 14.3 UPS System Output DC Filtering Ripple voltage less than 0.5% peak to peak UPS Output Capacity 100% rated current at 0.8 power factor or 100% rated current a...
Page 109 - Warranty; Limited Factory Warranty; Three‐Phase Powerware UPS Products
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com 15-1 Chapter 15 Warranty Limited Factory Warranty Three‐Phase Powerware UPS Products WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delawar...
Page 111 - Appendix A; Figur; Installation Reference; Physical Features and Requirements; Table A. Equipment Weight; Weight; Table B. UPS Cabinet Clearances; From the Top of the Cabinet; From the Front of the Cabinet
EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-1 Appendix A Figur Installation Reference The information in this appendix will help you plan for and install the Powerware9315. This appendix contains the following information: S Physic...
Page 112 - Ambient Temperature Range:; Rating
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-2 6. The basic environmental requirements for UPS system operation are: S Ambient Temperature Range: 0–40°C (32–104°F) S Recommended Operating Range: 20–25°C (68–77...
Page 113 - Figure A‐2. Inverter/Rectifier Cabinet – PCM 1 Dimensions
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-3 DIMENSIONS ARE IN MILLIMETERS [INCHES] ÓÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓÓ ÓÓÓ...
Page 115 - Figure A‐4. Output/Inverter Cabinet – PCM 2 Dimensions
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-5 DIMENSIONS ARE IN MILLIMETERS [INCHES] ÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓÓÓ ÓÓÓÓÓÓ...
Page 117 - Figure A‐6. MBC – PCM 3 Dimensions
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-7 DIMENSIONS ARE IN MILLIMETERS [INCHES] FRONT VIEW 2080.0 [ 38.2] 558.8[22.0] Figure A‐6. MBC – PCM 3 Dimensions
Page 119 - UPS System Oneline Configurations; Table D. Powerware 9315 UPS System Oneline Configurations; Oneline Drawing
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-9 A.2 UPS System Oneline Configurations NOTE A bypass neutral feeder must be supplied when the output neutral is used. If no bypass neutral feeder is supplied, the ...
Page 122 - Power Wiring Installation Notes; For external wiring, use 90
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-12 A.3 Power Wiring Installation Notes Read and understand the following notes while planning your installation: 1. Refer to national and local electrical codes for...
Page 127 - Table I. Power Cable Conduit Requirements
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-17 10. Per NEC, Article 300‐20(a), all three-phase conductors must be run in the sameconduit. If a neutral and/or ground is used, it must be run in the same conduit...
Page 128 - Figure A‐10. Securing Cables
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-18 Table J. Recommended Installation Parts and Tool (Not Supplied by Eaton) Part Size Quantity Manufacturer Part Number Notes Long Barrel 2 Hole Lug 500 MCM As requ...
Page 129 - Table K. Maximum Input Circuit Breaker Ratings; UPS Model
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-19 14. External overcurrent protection is not provided by this product, but is requiredby codes. See Table E through Table G starting on page A-13 for wiringrequire...
Page 130 - Table L. Maximum Output Circuit Breaker Ratings; There is no DC disconnect device within the UPS.
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-20 Table L. Maximum Output Circuit Breaker Ratings UPS Model Output Voltage Rating 400V 480V 600V PW9315-625/400PW9315-625/450 800A N/A N/A PW9315-625/500PW9315-625...
Page 131 - ST; Figure A‐11. CB2TB to DC Source Disconnect Device
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-21 28. A battery disconnect switch is recommended, and may be required by NEC orlocal codes when batteries are remotely located. The battery disconnectswitch may be...
Page 132 - Location of UPS Terminals; Figure A‐12. Inverter/Rectifier Cabinet – PCM 1 Terminals
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-22 A.4 Location of UPS Terminals NOTE Metal shield covering power wiring terminals and battery compartment must be removed to gain access to wiring terminals. DC IN...
Page 134 - Figure A‐14. Output/Inverter Cabinet – PCM 2 Terminals
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-24 15 PIN INTERCABINETCONNECTION ONPIGTAIL HARNESSTO INPUT/ RECTIFIERCABINET NEGATIVE DC INPUTFROM RECTIFIER DC LINK(SEE FIGURE A‐15) AC OUTPUTTO MBC OR SBM(E9, E10...
Page 136 - Figure A‐16. MBC – PCM 3 Terminals
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-26 AC INPUTTO BYPASS(E6, E7, E8)(A, B, C) GROUND OUTPUTNEUTRALCONNECTION(E12) STATIC SWITCH BACKFEEDPROTECTION BREAKER (FBP) AC INPUTFROM INVERTER(TOP TWO TERMINALH...
Page 138 - Customer Interface Wiring Notes; Table O. Input/Rectifier Cabinet Customer Interface Connections
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-28 A.5 Customer Interface Wiring Notes 1. Use Class 1 wiring methods (as defined by the NEC) for control wiring. Installthe control wiring in separate conduit from ...
Page 142 - Table P. Output/Inverter Cabinet Customer Interface Connections
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-32 Table P. Output/Inverter Cabinet Customer Interface Connections CUSTJ4 Terminal Name Description 1 Building Alarm 2 Programmable UPS alarm. Activated by a remote...
Page 144 - Table Q. MBC Customer Interface Connections
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-34 Table Q. MBC Customer Interface Connections CUSTJ4 Terminal Name Description 1 Building Alarm 2 Programmable UPS alarm. Activated by a remote dry contact closure...
Page 146 - Figure A‐23. Summary Alarm Relay Contacts; Typical REPO; Twisted; Figure A‐24. REPO Wiring
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-36 NOTE The Summary Alarm Relay contact rating is 32 Vac/42 Vdc maximum switched voltage and 1A maximum current. NOTE Relays are shown in de‐energized state. Relays...
Page 147 - Figure A‐25. Eaton REPO Switch
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-37 DIMENSIONS ARE IN MILLIMETERS [INCHES] NOTE Interface wiring and conduit between the REPO switch and the UPS are to be supplied by the customer. 115.8[4.56] 114....
Page 148 - RMP Dimensions and Mounting Details; Figure A‐26. RMP Dimensions and Mounting Details
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-38 A.7 RMP Dimensions and Mounting Details DIMENSIONS ARE IN MILLIMETERS [INCHES] 100.1[3.94] 74.7 [2.94] 171.5[6.75] 25.4 [1.00] KNOCKOUTS PROVIDED ON5 SURFACES 28...
Page 149 - RIM Dimensions and Mounting Details; Figure A‐27. RIM Dimensions and Mounting Details
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-39 A.8 RIM Dimensions and Mounting Details DIMENSIONS ARE IN MILLIMETERS [INCHES] 28.6 [1.12] FLUSH MOUNT 215.9[8.50] 196.8[7.75] 41.1 [1.62] 88.9 [3.50] 190.5[7.50...
Page 151 - SCM Dimensions and Mounting Details; Figure A‐29. SCM Dimensions and Mounting Details
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-41 A.9 SCM Dimensions and Mounting Details 41.1 DIMENSIONS ARE IN MILLIMETERS [INCHES] 100.1[3.94] 74.7 [2.94] 171.5[6.75] 25.4 [1.00] KNOCKOUTS PROVIDED ON5 SURFAC...
Page 152 - A.10 Battery Disconnect Switch Dimensions; Figure A‐30. Battery Disconnect Switch Dimensions
INSTALLATION REFERENCE EATON Powerware ® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com A-42 A.10 Battery Disconnect Switch Dimensions DIMENSIONS ARE IN MILLIMETERS [INCHES] 806.5 [31.75] 870.0 [34.25] 88.9 [3.50] 438.15[17.25] REMOVABLE FEET (IF WALL MO...