Powerware 100160 kVA - Manuals
Powerware 100160 kVA – Manual in PDF format online.
Manuals:
Manual Powerware 100160 kVA
Summary
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference. Consignes de s...
i EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Table of Contents 1 Introduction 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 Basic System Configurations 1-...
Table of Contents ii EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 4 Batteries 4-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1 Important Safety Instructi...
Table of Contents iii EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 8 Features, Options, and Accessories 8-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1 UPS Standard Features 8-1 . . . . . . . . . . . ...
Table of Contents iv EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9.3 System Controls Screen 9-45 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.4 Load Off Screen 9-47 . . . . . ....
Table of Contents v EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 13 Communication 13-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13.1 X-Slot Cards 13-1 . . . . . . . ...
Table of Contents vi EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com This page intentionally left blank.
1-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Chapter 1 Introduction The Powerware ® 9390 uninterruptible power supply (UPS) is a true online, continuous-duty, transformerless, double-conversion, solid-state, three-phase system, provid...
Introduction 1-2 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 1.1 Basic System Configurations The following basic UPS system configurations are possible: 쑺 Single module UPS and one to four battery cabinets 쑺 Single module UPS with UPS Si...
Introduction 1-3 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 1.2 Using This Manual This manual describes how to install and operate the Powerware 9390 UPS (100–160 kVA) cabinet. Read and understand the procedures described in this manual...
Introduction 1-4 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 쑺 Chapter 14, “Maintaining the UPS System” – contains maintenance instructions for the UPS system. 쑺 Chapter 15, “Product Specifications” – provides detailed specifications for...
Introduction 1-5 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 1.4 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenanc...
Introduction 1-6 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 1.5 For More Information Refer to the Powerware 9390 Integrated Battery Cabinet (Models IBC-S and IBC-L) Installation Manual (164201536) for the following additional informatio...
1-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Section I Installation
2-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Chapter 2 UPS Installation Plan and Unpacking Use the following basic sequence of steps to install the UPS: 1. Create an installation plan for the UPS system (Chapter 2). 2. Prepare your si...
UPS Installation Plan and Unpacking 2-2 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 2.2.1 Environmental Considerations The life of the UPS system is adversely affected if the installation does not meet the following guidelines: 쑺 The sys...
UPS Installation Plan and Unpacking 2-3 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 2.3 Inspecting and Unpacking the UPS Cabinet The cabinet is shipped bolted to a wooden pallet and protected with outer protective packaging material (see...
UPS Installation Plan and Unpacking 2-4 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 1. Carefully inspect the outer packaging for evidence of damage during transit. C A U T I O N Do not install a damaged cabinet. Report any damage to the ...
3-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Chapter 3 Installing the UPS System 3.1 Preliminary Installation Information W A R N I N G Installation should be performed only by qualified personnel. Refer to the following while install...
Installing the UPS System 3-2 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 3.2.1 Unloading the Powerware 9390 UPS Cabinet from the Pallet The UPS cabinet is bolted to a wooden pallet supported by wood skids. To remove the pallet, perform ...
Installing the UPS System 3-3 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Shipping Bracket Bolts Front View Pallet Vented Front Doors Front Shipping Bracket Shipping Bracket Bolts Removable Skid Skid Bolts Figure 3-1. Removing Front Ship...
Installing the UPS System 3-4 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Rear Shipping Bracket Pallet Rear View Shipping Bracket Bolts Shipping Bracket Bolts Figure 3-2. Removing Rear Shipping Bracket on the Powerware 9390 UPS
Installing the UPS System 3-6 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 3.2.3 Integrated Distribution Cabinet Installation To install and wire an IDC, refer to the Powerware 9390 Integrated Distribution Cabinet (160 kVA) Installation a...
Installing the UPS System 3-7 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com C A U T I O N DELTA SOURCES (TN-S) - The 9390 UPS system can be operated only from a delta supply source that is fully floating and if the neutral-forming transfor...
Installing the UPS System 3-8 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com C A U T I O N In the following step, DO NOT move the sensing and EMI wires from the rectifier contactor K1 input terminals. These wires must remain connected to th...
Installing the UPS System 3-10 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 14. Route and connect the output cable between the UPS cabinet and the IDC or IAC. Refer to the applicable IDC or IAC installation and operation manual, reference...
Installing the UPS System 3-14 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 6. When all wiring is complete, reinstall the safety shield panels removed in previous steps. Secure with the retained hardware. 7. Close the control panel door a...
Installing the UPS System 3-15 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Installation Checklist - All packing materials and restraints have been removed from each cabinet. - Each cabinet in the UPS system is placed in its installed loc...
Installing the UPS System 3-16 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Parallel System Installation Checklist - Each cabinet in the parallel system is placed in its installed location. - All conduits and cables are properly routed to...
Installing the UPS System 3-17 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Notes _________________________________________________________________________ _________________________________________________________________________ ________...
4-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Chapter 4 Batteries 4.1 Important Safety Instructions This chapter describes installing the UPS batteries. C A U T I O N Only qualified service personnel (such as a licensed electrician) sh...
Batteries 4-2 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com A V E R T I S S E M E N T ! 쑺 Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par des courts-circuits de haute intensité. Prendre les précautions né...
5-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Chapter 5 Installing a Remote Emergency Power-off Switch A latching-type REPO switch can be used in an emergency to shut down the UPS and remove power to the critical load from a location a...
Installing a Remote Emergency Power-off Switch 5-3 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 13. If you are installing multiple REPO stations, wire additional stations in parallel with the first REPO. 14. If required, install wiring fr...
6-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Chapter 6 Installing Options and Accessories 6.1 Installing a Powerware Hot Sync CAN Bridge Card As an option, a Powerware Hot Sync Computer Area Network Bridge Card shown in Figure 6-1, ca...
Installing Options and Accessories 6-2 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 4. Install wiring from the Powerware Hot Sync CAN Bridge Card in accordance with the instructions listed below: 쑺 Parallel system wiring (see paragraph 6....
Installing Options and Accessories 6-3 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 11. Install parallel system backup control (pull chain) wiring between UPMs. See Drawing 164201604-8 starting on page A-33 for terminal locations and wiri...
Installing Options and Accessories 6-4 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 7. Install wiring between the UPS and RMP II. See Drawing 164201604-8 starting on page A-33 for Powerware Hot Sync CAN Bridge Card and RMP II location, te...
Installing Options and Accessories 6-6 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 6.5 Installing a Supervisory Contact Module II To install SCM II wiring, perform the following procedure: 1. Verify the UPS system is turned off and all p...
Installing Options and Accessories 6-7 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9. Install wiring between the SCM II terminal block TB2 and the monitoring equipment. See Figure 6-2 for terminal assignments and Drawing 164201604-8 on p...
6-9 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Section II Operation
7-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Chapter 7 Understanding UPS Operation 7.1 Looking Inside the UPS System The Powerware 9390 UPS is a continuous-duty, solid-state, transformerless (at 208 and 480 Vac), three-phase, true onl...
Understanding UPS Operation 7-2 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com If utility power is interrupted or falls outside the parameters specified in Chapter 15, “Product Specifications,” the UPS uses a backup battery supply to mainta...
Understanding UPS Operation 7-3 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com The UPS continually monitors itself and the incoming utility power, and automatically switches between these modes as required, without operator intervention. Th...
Understanding UPS Operation 7-4 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 7.2.2 Normal Mode – RT Figure 7-2 shows the path of electrical power through the UPS system when the UPS is operating in Normal mode. Static Switch K5 Rectifier ...
Understanding UPS Operation 7-5 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com The neutral from the system input is connected to the neutral regulator in the DC capacitors. The output neutral of the system is connected with the required neu...
Understanding UPS Operation 7-6 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 7.2.3 Bypass Mode – RT The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure. The bypass source supplies the c...
Understanding UPS Operation 7-7 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com During an outage, the UPS prohibits transfers to bypass and provides upstream protection. The backfeed protection contactor is opened, preventing system output v...
Understanding UPS Operation 7-8 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 7.2.4 Battery Mode – RT The UPS automatically transfers to Battery mode if a utility power outage occurs, or if the utility power does not conform to specified p...
Understanding UPS Operation 7-9 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com If the input power fails to return or is not within the acceptance windows required for normal operation, the battery continues discharging until a DC voltage le...
Understanding UPS Operation 7-10 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Up to four units can be paralleled for redundancy or capacity without any additional cabinets. The system is paralleled for redundancy (1+1) in a system where t...
Understanding UPS Operation 7-11 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 7.3.2 Normal Mode – Parallel In Normal mode, utility AC power is supplied to the UPMs. Each UPM then conditions the incoming AC power and provides clean, regula...
Understanding UPS Operation 7-12 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 7.3.3 Bypass Mode – Parallel In Bypass mode, the output of the system is provided with three-phase AC power directly from the bypass input. While in this mode, ...
Understanding UPS Operation 7-13 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com The parallel system can be transferred from Normal mode to Bypass mode manually. However, the parallel system automatically switches to Bypass mode whenever the...
Understanding UPS Operation 7-15 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com If the input power fails to return or is not within the acceptance windows required for normal operation, the battery continues discharging until a DC voltage l...
Understanding UPS Operation 7-16 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com An ABM charging cycle starts with the charger driving the battery voltage, at maximum current limit, to a battery charge level of 2.34 volts/cell. The time it t...
8-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Chapter 8 Features, Options, and Accessories 8.1 UPS Standard Features The UPS has many standard features that provide cost-effective and consistently reliable power protection. 8.1.1 Contr...
Features, Options, and Accessories 8-2 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 8.1.5 Advanced Battery Management A three-stage charging system increases battery service life by optimizing recharge time, and protects batteries from da...
Features, Options, and Accessories 8-3 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 8.2.3 Integrated Accessory Cabinet (IAC-B, IAC-T, and IAC-D) The following IACs are designed for use with the Powerware 9390 three-phase Uninterruptible P...
Features, Options, and Accessories 8-4 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 8.2.8 Remote Monitor Panel II An optional RMP II contains backlit status indicators and a local horn, allowing you to monitor the operational status and a...
9-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Chapter 9 Using the Control Panel This chapter describes the UPS control panel, including controls and indicators, and how to monitor UPS operation. The control panel (see Figure 9-1) is lo...
Using the Control Panel 9-2 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9.1 Using the LCD and Pushbuttons The LCD on the control panel provides an operator interface with the UPS system. Figure 9-2 identifies the display areas discussed ...
Using the Control Panel 9-3 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9.2 Using the Main Menu The UPS main menu bar allows you to display data in the information area to help you monitor and control UPS operation. The following menus a...
Using the Control Panel 9-4 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9.2.2 Event Screens Press the EVENTS pushbutton on the main menu bar or History Menu bar to display a listing of all system events that are currently active. The mos...
Using the Control Panel 9-5 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Press the HISTORY pushbutton on the Active Events Menu bar to display the History Log. The History Log lists up to the 500 system events in chronological order, with...
Using the Control Panel 9-6 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9.2.3 Unit Meter Screens The Unit Meter screens show the UPS meter readings for the unit (or units, if a parallel system is installed). The default voltage displayed...
Using the Control Panel 9-7 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com The Input screen shows input voltage (phase-to-neutral), input current (each phase), and frequency of the incoming utility source, as well as the kVA, kW, and power ...
Using the Control Panel 9-8 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com The Battery screen displays the battery voltage (Vdc), the battery current (Idc), the minutes of battery time remaining, and battery temperature. Battery temperature...
Using the Control Panel 9-9 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9.2.4 Battery Discharge Log Press the METERS pushbutton on the main menu bar to display the Unit Meter screens. Scroll through the meter screens using the or pushbut...
Using the Control Panel 9-10 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Press the LOG pushbutton on the Battery Discharge Log Summary Menu bar to display the Battery Discharge Log screen.The Battery Discharge Log screen displays the ind...
Using the Control Panel 9-11 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9.2.5 KW Demand Log Press the METERS pushbutton on the main menu bar to display the Unit Meter screens. Scroll through the meter screens using the or pushbuttons on...
Using the Control Panel 9-12 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Press the LOG pushbutton on the KW Demand Log Summary Menu bar to display the KW Demand Log screen.The KW Demand Log screen displays the individual log entries, inc...
Using the Control Panel 9-13 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Press the SETUP pushbutton on the KW Demand Log Summary Menu bar to display the Current KW Demand Log Setup screen 1.The Current KW Demand Log Setup screen 1 displa...
Using the Control Panel 9-14 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Press the CHANGE pushbutton on the Current KW Demand Log Setup Menu bar to display the Current KW Demand Log Setup screen 2.The Current KW Demand Log Setup screen c...
Using the Control Panel 9-15 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Select TIME INTERVAL MONITORED from the Current KW Demand Log Setup screen 2 menu to display the Time Interval Monitored Setup screen. The Time Interval Monitored S...
Using the Control Panel 9-16 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com The Time Interval Monitored Setup Save screen lets you save the new time interval, retry another time interval, or abort the change. Figure 9-18 shows the Time Inte...
Using the Control Panel 9-19 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9.2.6 Maximum Current Log Press the METERS pushbutton on the main menu bar to display the Unit Meter screens. Scroll through the meter screens using the or pushbutt...
Using the Control Panel 9-21 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com MAXIMUM CURRENT LOG SUMMARY INTERVAL : 07/30/2005 TIME OVER LIMIT 15 : 26 : 10 – 15 : 30 : 10 *** . ** % 2 MINUTES 3 RESET MAXIMUM CURRENT EVENT NUM TIMES OVER THIS...
Using the Control Panel 9-22 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Press the CHANGE pushbutton on the Maximum Current Log Setup Menu bar to display the Maximum Current Log Setup screen 2.The Maximum Current Log Setup screen can be ...
Using the Control Panel 9-23 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Select TIME INTERVAL MONITORED from the Maximum Current Log Setup screen 2 menu to display the Time Interval Monitored Setup screen. The Time Interval Monitored Set...
Using the Control Panel 9-24 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com The Time Interval Monitored Setup Save screen lets you save the new time interval, retry another time interval, or abort the change. Figure 9-18 shows the Time Inte...
Using the Control Panel 9-25 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Select MAXIMUM % of FULL LOAD from the Maximum Current Log Setup screen (screen 2) menu to display the Maximum % of Full Load Setup screen. The Maximum % of Full Lo...
Using the Control Panel 9-26 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com The Maximum % of Full Load Setup Save screen lets you save the new load limit, retry another load limit, or abort the change. Figure 9-29 shows the Maximum % of Ful...
Using the Control Panel 9-27 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Select CALCULATION METHOD from the Maximum Current Log Setup screen 2 menu to display the Calculation Method Setup screen. The Calculation Method Setup screen allow...
Using the Control Panel 9-28 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9.2.7 System Meters Screens The System Meters screens show the total system and individual UPS unit meter readings from any unit, when a parallel system is installe...
Using the Control Panel 9-29 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com The Output Total System screen shows output voltage (phase-to-neutral), output current (each phase), and frequency being supplied by the UPS, as well as the kVA, kW...
Using the Control Panel 9-31 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com The Input screen shows input voltage (phase-to-neutral), output current (each phase), and frequency of the incoming utility source, as well as the kVA, kW, and powe...
Using the Control Panel 9-32 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com The Battery screen displays the battery voltage (Vdc), the battery current (Idc), the minutes of battery time remaining, and battery temperature. Battery temperatur...
Using the Control Panel 9-33 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9.2.8 System Setup Level 0 Screens Press the SETUP pushbutton on the main menu bar to display the System Setup Level 0 Screen. This screen can be used to: 쑺 Enter a...
Using the Control Panel 9-34 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Select CONTRAST from the System Setup Level 0 menu to display the Contrast Adjust screen. Figure 9-39 shows the Contrast Adjust screen. Use the or pushbuttons to ad...
Using the Control Panel 9-35 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Select VERSIONS from the System Setup Level 0 menu to display the Versions screen. The Versions screen provides the firmware version numbers installed on the UPS. F...
Using the Control Panel 9-36 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9.2.9 System Setup Level 1 Screens A password is required to access the Level 1 functions. To enter the password, select ENTER PASSWORD from the System Setup Level ...
Using the Control Panel 9-37 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com The System Setup Level 1 screen can be used to set the UPS date and time, set the serial ports, change the Level 1 password, and log out of Level 1. In addition, th...
Using the Control Panel 9-38 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Select CHANGE PASSWORD from the System Setup Level 1 menu to display the Change Password screen. The Change Password screen allows the System Setup Level 1 password...
Using the Control Panel 9-40 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Select DATE AND TIME from the System Setup Level 1 menu to display the Time Format Setup screen. The Time Format Setup screen allows the selection of either month/d...
Using the Control Panel 9-41 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com The Set Date and Time MM/DD/YYYY screen allows the internal date and time of the UPS to be set in the month/day/year format. The date and time information is used f...
Using the Control Panel 9-42 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com The Set Date and Time DD/MM/YYYY screen allows the internal date and time of the UPS to be set in the day/month/year format. The date and time information is used f...
Using the Control Panel 9-43 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Select COM PORT SETUP from the System Setup Level 1 menu to display the COM Port Setup screen. This screen allows selection of the serial COM port to set up. Figure...
Using the Control Panel 9-45 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9.3 System Controls Screen Press the CONTROLS pushbutton on the main menu bar to display the System Controls screen. LOAD OFF, normal operation, transfer to bypass,...
Using the Control Panel 9-46 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com SYSTEM CONTROLS LOAD OFF PM OFF CHGR ON MAINTENANCE BYPASS BYPASS POWER MODULE (PM) OFF : OFF : ONLINE : CHARGER OFF : Figure 9-52. System Controls Screen 2 The CHG...
Using the Control Panel 9-47 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9.4 Load Off Screen The Load Off screen appears when the LOAD OFF pushbutton is selected from the main menu bar or System Controls menu bar. This screen allows the ...
Using the Control Panel 9-48 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9.5 Reading the Status Indicators The four symbols on the right side of the control panel are status indicators . They are colored light emitting diode (LED) lamps,...
10-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Chapter 10 UPS Operating Instructions The following procedures provide instructions for operating the UPS or parallel system. For a description of the UPS control panel functions, see Chap...
UPS Operating Instructions 10-2 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 7. Observe the following messages appear sequentially on the power module (PM) status line: DC STARTINGINVERTER STARTINGINVERTER SYNCINGREADYONLINE The rectifier...
UPS Operating Instructions 10-3 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 10.1.3 Starting the Power Module To start the power module without transferring the critical load to normal, perform the following procedure: 1. Close the UPS in...
UPS Operating Instructions 10-4 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 3. The UPS is now operating in Bypass mode and the BYPASS status indicator is illuminated. The power module (PM) status indicates READY. The system is now on byp...
UPS Operating Instructions 10-7 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 10.1.10 Using the Remote Emergency Power-off Switch A UPS emergency power-off is initiated by the REPO pushbutton switch. In an emergency, you can use this switc...
UPS Operating Instructions 10-8 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 10.2 Multiple Module Parallel Operation 10.2.1 Starting the Parallel System in Normal Mode To start the parallel system, perform the following procedure: 1. Clos...
UPS Operating Instructions 10-9 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 10.2.2 Starting the Parallel System in Bypass Mode If the inverter output of the UPMs is not available and the critical load needs to be energized, perform the f...
UPS Operating Instructions 10-10 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 10.2.3 Transfer Parallel System from Normal to Bypass Mode To transfer the critical load to Bypass mode, perform the following procedure: C A U T I O N In Bypas...
UPS Operating Instructions 10-12 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 7. Press the NORMAL pushbutton on the System Controls menu bar of the UPM. 8. Observe the following messages appear sequentially on the power module (PM) status...
UPS Operating Instructions 10-14 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com C A U T I O N Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and cleared. 3. To restart the UPS after p...
11-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Chapter 11 Using Features and Options The many standard features of your UPS system provide consistent, economical, and dependable power protection. In addition, you can add available opti...
Using Features and Options 11-2 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 11.3 Optional Remote Monitor Panel II As an option, a Remote Monitor Panel II (RMP II) can be installed to monitor the operation of the UPS system from virtually...
Using Features and Options 11-4 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 11.4 Relay Interface Module II An optional RIM II uses relay contact closures to indicate the operating status and alarm condition of the UPS system. The RIM II ...
Using Features and Options 11-5 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 11.5 Supervisory Contact Module II An optional SCM II establishes an interface between the UPS system and the customer’s monitor. This interface allows the custo...
12-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Chapter 12 Responding to System Events 12.1 General When the UPS system is running in Normal mode, it continually monitors itself and the incoming utility power. In Battery or Bypass modes...
Responding to System Events 12-2 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com ALARMS Message Horn Phone Relay Log* Indication Battery Totally Discharged 1 No 1 HA Shutdown Imminent Battery Totally Discharged OK Off No 1 HA Condition Clear...
Responding to System Events 12-5 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com NOTICES Message Horn Phone Relay Log* Indication Automatic Shutdown Pending 1 No No A Information Only Automatic Shutdown Pending OK OFF No No A Condition Clear...
Responding to System Events 12-8 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com STATUS Message Horn Phone Relay Log* Indication Battery Switchgear Closed No No No H User Status Battery Switchgear Open No No No H User Status Bypass Switchgea...
Responding to System Events 12-9 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com COMMAND Message Horn Phone Relay Log* Indication Load Off Command Received Yes No No H Information Only To Normal Mode Command No No No H Information Only To By...
13-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Chapter 13 Communication This chapter describes the communication features of the Powerware 9390 100–160 kVA UPS and provides information about connecting hardware and using Terminal mode....
Communication 13-2 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com LAN and telephone drops for use with X-Slot connectivity cards must be provided by facility planners or the customer. For installation and setup of an X-Slot card, please con...
Communication 13-3 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Remote Notification is an extension of the Terminal mode with the additional support algorithms necessary to control an external modem. Connection to the UPS is made when a u...
Communication 13-4 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 13.4.2 Event History Log This key sequence prints the entire Event History Log of the UPS at the time the data is requested. The printout begins with the oldest alarm entry i...
14-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Chapter 14 Maintaining the UPS System The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, with very...
Maintaining the UPS System 14-2 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 쑺 Determine if the battery is inadvertently grounded. If it is, remove the source of the ground. Contact with any part of a grounded battery can result in electr...
Maintaining the UPS System 14-3 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 3. Ensure the operating environment is within the parameters specified in Chapter 15, “Product Specifications,” and Drawing 164201604-2 on page A-3. 4. Ensure th...
15-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Chapter 15 Product Specifications 15.1 Model Numbers The UPS systems are housed in free-standing cabinets with safety shields behind the doors. The UPS systems are available in 50/60 Hz wi...
Product Specifications 15-3 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 15.3 Multiple Module Parallel Specifications 15.3.1 UPM Input Same as single module. 15.3.2 UPM Output Same as single module. 15.3.3 Environmental Same as single mod...
A-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Appendix A 16- Installation Information The information in this appendix is helpful during the planning and installation of the UPS system. This appendix contains the following drawings: 쑺 ...
164201604 --- 2 1 of 2 PHYSICAL FEATURES AND REQUIREMENTS 091505 A DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: Installation Information A-3 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 1. The UPS equipment operating environment must m...
2 of 2 PHYSICAL FEATURES AND REQUIREMENTS 091505 A 164201604 --- 2 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: Installation Information A-4 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 7. The basic environmental requirements for opera...
BATTERY BREAKER 1 of 6 UPS SYSTEM ONELINE DRAWING 032406 B 164201604 --- 4 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: UPS CABINET INVERTER RECTIFIER STATIC SWITCH REMOTE EPO BUILDING ALARMS AC OUTPUT TO CRITICAL LOAD AC INPUT TO UPS RECTIFIER 3 WIRE A --- B --- C AC INPUT TO BYPASS 3 or 4 WIRE ...
UPS SYSTEM ONELINE DRAWING 091505 A DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: OUTPUT TO CRITICAL LOAD BATTERY CABINET BATTERY BREAKER E4. E5 E9 E10 E11 E12 FUSE K5 STATIC SWITCH FUSE K3 FUSE BATTERY CONVERTER RECTIFIER INVERTER K1 UPM 1 E1 E2 E3 E6E 7E8 E12 A B SEE NOTE 2 MODULE TIE CABINET (O...
1 of 15 POWER WIRING INSTALLATION NOTES 032406 B 164201604 --- 5 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: Installation Information A-12 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Table E. INPUT/OUTPUT Ratings & External Wirin...
POWER WIRING INSTALLATION NOTES 032406 B 164201604 --- 5 3 of 15 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: Installation Information A-14 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Table G. INPUT/OUTPUT Ratings & External Wirin...
POWER WIRING INSTALLATION NOTES 032406 B 164201604 --- 5 NOTE: Customer ground can be run in any conduit listed in Table J. 4 of 15 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: Installation Information A-15 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev...
POWER WIRING INSTALLATION NOTES 091505 A 164201604 --- 5 8 of 15 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: Installation Information A-19 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 14. External overcurrent protection is not provide...
POWER WIRING INSTALLATION NOTES 091505 A 164201604 --- 5 9 of 15 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: Installation Information A-20 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 19. There is no DC disconnect device within the UP...
POWER WIRING INSTALLATION NOTES 032406 B 164201604 --- 5 10 of 15 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: Installation Information A-21 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 25. Parallel system UPM and system bypass input f...
POWER WIRING INSTALLATION NOTES 091505 A 164201604 --- 5 11 of 15 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: Installation Information A-22 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 28. See Drawing 164201604 --- 7 for UPM terminal ...
POWER WIRING INSTALLATION NOTES 091505 A 164201604 --- 5 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: UPM 2 Battery Bypass inputs to UPMs UPM 1 Battery UPM 3 Battery UPM 4 Battery Outputs from UPMs 1A (30) 2A (35) 3A (40) 4A (45) 1B (25) 2B (20) 3B (15) 4B (10) 15 of 15 NOTE: Wire lengths in the ...
1 of 2 CONDUIT AND WIRE ENTRY LOCATIONS 091505 A 164201604 --- 6 REMOVE DEBRIS SHIELD COVERING EXHAUST GRILL BEFORE OPERATING SYSTEM. TOP ENTRY CONDUIT LANDING FOR AC INPUT AND OUTPUT, DC INPUT, DC CONTROL, AND INTERFACE CONNECTIONS. (REMOVE PANEL TO DRILL OR PUNCH CONDUIT HOLES.) DESCRIPTION: DATE:...
2 of 2 CONDUIT AND WIRE ENTRY LOCATIONS 091505 A LEFT SIDE VIEW DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: RIGHT SIDE VIEW INTER-CABINET WIRING ACCESS KNOCKOUTS. REMOVE KNOCKOUTS, AS REQUIRED, TO ROUTE WIRES BETWEEN CABINETS. (INSTALL NYLON GROMMET AFTER REMOVAL OF KNOCKOUTS.) INSIDE PANELS INT...
1 of 4 UPS POWER TERMINAL LOCATIONS 032406 B 164201604 --- 7 NOTE: Metal shields covering wiring terminals must be removed or opened to gain access to terminals. GROUND TERMINALS AC INPUT TO UPS RECTIFIER AND BYPASS (A, B, C, N) DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: DC INPUT FROM BATTERY T...
2 of 4 UPS POWER TERMINAL LOCATIONS 091505 A 164201604 --- 7 TERMINAL DETAIL PHASE A (E9) PHASE B (E10) PHASE C (E11) DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: AC OUTPUT TO CRITICAL LOAD DC INPUT FROM BATTERY + (E4) --- (E5) PHASE A (E1) PHASE B (E2) PHASE C (E3) PHASE A (E6) PHASE B (E7) PHAS...
1 of 13 INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS 032406 B DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 164201604 --- 8 Installation Information A-33 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 1. Use Class 1 wiring m...
032406 B 164201604 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS TB1 TB2 X-SLOTS STANDARD X-SLOT COMMUNICATION BAY WIREWAY FOR BOTTOM ENTRYINTERFACE WIRING NOTE: Metal shields covering wiring terminals must be removed or opened to ga...
NOTE: 1. All building alarm inputs require an isolated normally-open or normally-closed contact or switch (rated at 24 Vdc, 20 mA minimum) connected between the alarm input and common terminal as shown. Building alarm inputs can be programmed for use with either normally-open or normally-closed cont...
091505 A 164201604 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS NOTE: 1. All building alarm inputs require an isolated normally-open or normally-closed contact or switch (rated at 24 Vdc, 20 mA minimum) connected between the alarm i...
032406 B 164201604 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS 5 of 13 Installation Information A-37 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 9. The UPS DC UVR trip ...
032406 B 164201604 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS 6 of 13 Installation Information A-38 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com 11. The Remote EPO feat...
091505 A 164201604 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS POWERWARE HOT SYNC CAN BRIDGE CARD CONNECTIONS FOR PARALLEL SYSTEM CONTROL CONNECTIONS FOR RMP II, RIM II, OR SCM II BUILDING ALARM 2 REPLACEMENT J3 NOTE: All interface...
091505 A 164201604 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS NOTE: This drawing is for parallel wiring purposes and is not a floor layout plan. UPMs can be placed in any physical order. PARALLEL SYSTEM CAN AND BACKUP CONTROL (PUL...
Installation Information A-43 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Building Alarm Pull Chain Wiring Terminations From UPM 1 To UPM 2 To UPM 3 (If Installed) To UPM 4 (If Installed) TB2–1 (BA 2) TB2–1 (BA 2) TB2–1 (BA 2) TB2–1 (BA ...
091505 A 164201604 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS TERMINAL TB–1 SIGNAL CONNECTIONS FROM THE UPS GROUND TERMINAL REMOTE MONITOR PANEL AND RELAY INTERFACE MODULE TERMINAL LOCATIONS TERMINAL TB–3 120 VAC POWER SUPERVISORY...
091505 A 164201604 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS UPS CAN CARD J3 120 VAC FROM CRITICAL BUS LINE NEUTRAL TWISTED PAIR GROUND TERMINAL RMP II, RIM II, OR SCM II 13 of 13 Installation Information A-45 EATON Powerware ® 9...
1 of 4 UPS CABINET DIMENSIONS 091505 A 164201604 --- 9 FRONT VIEW RIGHT SIDE VIEW DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: Dimensions are in millimeters [inches] Installation Information A-46 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerwar...
UPS CABINET DIMENSIONS 091505 A 164201604 --- 9 BOTTOM VIEW WITH OPTIONAL FLOOR MOUNTING BRACKETS Dimensions are in millimeters [inches] 3 of 4 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: LEFT SIDE RIGHT SIDE FRONT Installation Information A-48 EATON Powerware ® 9390 UPS (100–160 kVA) Installati...
UPS CABINET DIMENSIONS 091505 A 164201604 --- 9 BOTTOM VIEW WITH OPTIONAL SEISMIC MOUNTING BRACKETS Dimensions are in millimeters [inches] 4 of 4 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: SEISMIC KIT INSTALLATION LEFT SIDE RIGHT SIDE FRONT Installation Information A-49 EATON Powerware ® 9390 U...
1 of 1 OPTIONAL POWERWARE REMOTE EMERGENCY POWER-OFF 091505 A 164201604 --- 10 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 114.3 (4.50) 115.8 (4.56) 11.9 (0.47) 95.3 (3.75) SQUARE 88.9 (3.50) 1/2 in. Knockout Pattern typ. 5 sides TO UPS TO OTHER EQUIPMENT Dimensions are in millimeters [inches] N...
W-1 EATON Powerware ® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com Warranty LIMITED FACTORY WARRANTY FOR THREE-PHASE POWERWARE ® PRODUCTS WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delaware Corporation ...
Powerware Manuals
-
Powerware 5110
Manual
-
Powerware 9315 UPS
Manual
-
Powerware 9125
Manual
-
Powerware 700 VA
Manual
-
Powerware 10001500 VA
Manual
-
Powerware 1085
Manual
-
Powerware 9315
Manual
-
Powerware 10001100 kVA
Manual
-
Powerware 2500
Manual
-
Powerware 15 KVA
Manual
-
Powerware IPK-0318
Manual
-
Powerware 5125
Manual
-
Powerware 5115A USB
Manual
-
Powerware 5140
Manual
-
Powerware IPK-0320
Manual
-
Powerware 3115
Manual
-
Powerware 5105
Manual
-
Powerware 6000 VA
Manual
-
Powerware Powerware 9390
Manual
-
Powerware 3110
Manual