Page 2 - equipment and save this manual for future reference.; Consignes de sécurité; CONSIGNES DE SÉCURITÉ IMPORTANTES; Class A EMC Statements; NOTE; W A R N I N G
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference. Consignes de s...
Page 3 - Table of Contents; Introduction
i Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Table of Contents 1 Introduction 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 Basic System Configurations 1-2 . . . . . . . . . . ...
Page 4 - Installing a Remote Emergency Power-Off Control
Table of Contents ii Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 5 Installing a Remote Emergency Power-Off Control 5-1 . . . . . . . . . . . . . . . . . . . . . . . . . 6 Installing Options and Accessories 6-1 . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 5 - Using the Control Panel
Table of Contents iii Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 8.1.6 LanSafe Power Management Software 8-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1.7 Installation Features 8-2 . . . . . . . . . . . . . . . . . . . . . ....
Page 6 - 1 Using Features and Options
Table of Contents iv Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 10.2 Multiple Module Parallel Operation 10-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2.1 Starting the Parallel System in Normal Mode 10-8 . . . . ....
Page 7 - 5 Product Specifications; Single Module Specifications; Installation Information
Table of Contents v Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 15 Product Specifications 15-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15.1 Model Numbers 15-1 . . . . . . . . . . . . . . . . . . . ...
Page 8 - List of Figures
vi Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C List of Figures Figure 1-1. Powerware 9390 UPS (40–80 kVA) Cabinet 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 2-1. Powerware 9390 UPS (40–80 kVA) Cabinet as Shipped on Pa...
Page 9 - vii
vii Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Figure 9-24. Change Password Screen 9-19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 9-25. Change Password Save Screen 9-20 . . . . . . . . . . . ...
Page 10 - viii; This page intentionally left blank.
viii Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C This page intentionally left blank.
Page 11 - Chapter 1; Introduction; The Powerware
1-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Chapter 1 Introduction The Powerware ® 9390 uninterruptible power supply (UPS) is a true online, continuous-duty, transformerless, double-conversion, solid-state, three-phase system, providing conditioned and un...
Page 12 - Basic System Configurations
Introduction 1-2 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 1.1 Basic System Configurations The following basic UPS system configurations are possible: 쑺 Single module UPS and one to four battery cabinets 쑺 Single module UPS, one to four battery cabinets, an...
Page 13 - Using This Manual
Introduction 1-3 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 1.2 Using This Manual This manual describes how to install and operate the Powerware 9390 UPS (40–80 kVA) cabinet. Read and understand the procedures described in this manual to ensure trouble-free ...
Page 14 - Conventions Used in This Manual; Italic type
Introduction 1-4 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 쑺 Chapter 14, “Maintaining the UPS System” – contains maintenance instructions for the UPS system. 쑺 Chapter 15, “Product Specifications” – provides detailed specifications for the UPS system. 쑺 App...
Page 15 - IMPORTANT SAFETY INSTRUCTIONS; UPS system; D A N G E R
Introduction 1-5 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 1.4 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the UPS and batte...
Page 16 - For More Information; Installation Manual; Call your service representative
Introduction 1-6 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 1.5 For More Information Refer to the Powerware 9390 Integrated Battery Cabinet (Models IBC-S and IBC-L) Installation Manual (164201536) for the following additional information: 쑺 Integrated Batter...
Page 17 - Section I; Installation
1-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Section I Installation
Page 19 - Chapter 2; UPS Installation Plan and Unpacking; Use the following basic sequence of steps to install the UPS:; Creating an Installation Plan; create a logical plan for installing the system.; Preparing the Site; front of and above each cabinet for proper air circulation.
2-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Chapter 2 UPS Installation Plan and Unpacking Use the following basic sequence of steps to install the UPS: 1. Create an installation plan for the UPS system (Chapter 2). 2. Prepare your site for the UPS system ...
Page 20 - following guidelines:; Preparing for Wiring the UPS System; located inside the UPS.; Inspecting and Unpacking the UPS Cabinet
UPS Installation Plan and Unpacking 2-2 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 2.2.1 Environmental Considerations The life of the UPS system is adversely affected if the installation does not meet the following guidelines: 쑺 The system must be installed ...
Page 21 - C A U T I O N; between the pallet supports on the bottom of the unit.; C A U T I O N
UPS Installation Plan and Unpacking 2-3 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Figure 2-1. Powerware 9390 UPS (40–80 kVA) Cabinet as Shipped on Pallet C A U T I O N The UPS cabinet is heavy (see Table A on page A-3). If unpacking instructions are not clo...
Page 22 - on each side for removing the cabinet from the pallet.; Remove the protective covering from the cabinet.
UPS Installation Plan and Unpacking 2-4 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 3. Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft) on each side for removing the cabinet from the pallet. NOTE The UPS cabinet is shipped w...
Page 23 - Chapter 3; Installing the UPS System; Preliminary Installation Information; UPS Cabinet Installation
3-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Chapter 3 Installing the UPS System 3.1 Preliminary Installation Information W A R N I N G Installation should be performed only by qualified personnel. Refer to the following while installing the UPS system: 쑺 ...
Page 24 - Unloading the Powerware 9390 UPS Cabinet from the Pallet; bracket and securing hardware for later use.
Installing the UPS System 3-2 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 3.2.1 Unloading the Powerware 9390 UPS Cabinet from the Pallet The UPS cabinet is bolted to a wooden pallet supported by wood skids. To remove the pallet, perform the following procedur...
Page 25 - Front View
Installing the UPS System 3-3 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C NOTE Do not discard the front anti-tip/shipping bracket. This bracket is required for installation. Shipping Bracket Bolts Front View Pallet Vented Front Door Front Anti-tip/Shipping Br...
Page 26 - Rear View
Installing the UPS System 3-4 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Rear Shipping Bracket Pallet Skid Bolts (3 Places) Removable Skid Rear View Shipping Bracket Bolts Shipping Bracket Bolts Figure 3-2. Removing Rear Shipping Bracket on the Powerware 939...
Page 27 - Roll the cabinet to the final installation location.; not resting on the casters and the cabinet is level.
Installing the UPS System 3-5 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C NOTE In the following step the pallet tilts and acts as a ramp once the cabinet is rolled beyond the the center of the pallet. Be sure to restrain the cabinet as it continues to roll do...
Page 28 - Integrated Distribution Cabinet Installation; To install an IDC, refer to the; Installing UPS External and Battery Power Wiring; Slide the air filter up and remove from the cabinet.
Installing the UPS System 3-6 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 3.2.3 Integrated Distribution Cabinet Installation To install an IDC, refer to the Powerware 9390 Integrated Distribution Cabinet (80 kVA) Installation and Operation Manual . After the ...
Page 29 - Powerware 9390 Integrated Distribution; Powerware 9390 Integrated Battery Cabinet
Installing the UPS System 3-7 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 12. Connect phase A, B, C, and Neutral (if required) bypass input power wiring from the utility source to the bypass input terminals and neutral terminals in the UPS cabinet. See Append...
Page 33 - Installing Accessories and Parallel System Control Wiring
Installing the UPS System 3-11 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 3.2.5.3 X-Slot Connections NOTE LAN and telephone drops for use with X-Slot connectivity cards must be provided by facility planners or customer. NOTE When installing external wiring t...
Page 34 - Completing the Installation Checklist; Installation Checklist.
Installing the UPS System 3-12 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 3.4 Completing the Installation Checklist The final step in installing the UPS system is completing the following Installation Checklist. This checklist ensures that you have completel...
Page 35 - Installation Checklist
Installing the UPS System 3-13 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Installation Checklist - All packing materials and restraints have been removed from each cabinet. - Each cabinet in the UPS system is placed in its installed location. - Front shippin...
Page 36 - Parallel System Installation Checklist; All power cables are properly sized and terminated.
Installing the UPS System 3-14 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Parallel System Installation Checklist - Each cabinet in the parallel system is placed in its installed location. - All conduits and cables are properly routed to the UPMs and to the p...
Page 37 - Notes
Installing the UPS System 3-15 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Notes _________________________________________________________________________ _________________________________________________________________________ ______________________________...
Page 39 - Chapter 4; Batteries; Important Safety Instructions; This chapter describes installing the UPS batteries.
4-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Chapter 4 Batteries 4.1 Important Safety Instructions This chapter describes installing the UPS batteries. C A U T I O N Only qualified service personnel (such as a licensed electrician) should perform the batte...
Page 40 - A V E R T I S S E M E N T !; Installing Batteries; Recycling the Used Battery
Batteries 4-2 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C A V E R T I S S E M E N T ! 쑺 Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par des courts-circuits de haute intensité. Prendre les précautions nécessaires. 쑺 Pour le r...
Page 41 - Chapter 5; Installing a Remote Emergency Power-Off Control; enclosure dimensions and wiring knockouts.
5-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Chapter 5 Installing a Remote Emergency Power-Off Control A REPO switch can be used in an emergency to shut down the UPS and remove power to the critical load from a location away from where the UPS is installed...
Page 43 - with UL Class II requirements.
Installing a Remote Emergency Power-Off Control 5-3 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 13. If you are installing multiple REPO stations, wire additional stations in parallel with the first REPO. 14. If required, install wiring from the REPO station t...
Page 45 - Chapter 6; Installing Options and Accessories; Installing a Hot Sync Computer Area Network Bridge Card; Supervisory Contact Module to the UPS.
6-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Chapter 6 Installing Options and Accessories 6.1 Installing a Hot Sync Computer Area Network Bridge Card As an option, a Hot Sync CAN Bridge Card, as shown in Figure 6-1, can be installed to provide connectivity...
Page 46 - Preliminary Wiring Procedure; Perform the following procedure before installing wiring:
Installing Options and Accessories 6-2 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 6.2 Preliminary Wiring Procedure Perform the following procedure before installing wiring: 1. If not already removed, remove the door. Remove the retaining screw located inside...
Page 47 - Installing Parallel System Control Wiring; Reinstall the conduit landing plate and install the conduit.; steps. Secure with the retained hardware.
Installing Options and Accessories 6-3 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 6.3 Installing Parallel System Control Wiring NOTE When installing external wiring to the X-Slot CAN card, conduit must be installed to the UPS cabinet. When installing interna...
Page 48 - Installing a Remote Monitor Panel
Installing Options and Accessories 6-4 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 6.4 Installing a Remote Monitor Panel NOTE Only one system monitoring device can be connected to the Hot Sync CAN Bridge Card at one time (see Table 6-1). Table 6-1. Optional M...
Page 49 - Installing a Relay Interface Module
Installing Options and Accessories 6-5 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C NOTE Setup of the Hot Sync CAN Bridge Card must be performed by an authorized Powerware Customer Service Engineer. Contact service to schedule a date. 9. To check the operation...
Page 51 - Installing a Supervisory Contact Module; To install SCM wiring, perform the following procedure:; mounting hole locations.; Reinstall the conduit landing plate.
Installing Options and Accessories 6-7 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 6.6 Installing a Supervisory Contact Module NOTE Only one system monitoring device can be connected to the Hot Sync CAN Bridge Card at one time (see Table 6-1). To install SCM ...
Page 52 - Figure 6-2. Supervisory Contact Module TB2
Installing Options and Accessories 6-8 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 9. Install wiring between the SCM terminal block TB2 and the monitoring equipment. See Figure 6-2 for terminal assignments and Drawing 164201535-8 for terminal block location. ...
Page 53 - Section II; Operation
6-9 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Section II Operation
Page 55 - Chapter 7; Understanding UPS Operation; Looking Inside the UPS System; In this manual, the power required by your equipment is called the; Figure 7-1. Main Elements of the UPS System
7-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Chapter 7 Understanding UPS Operation 7.1 Looking Inside the UPS System The Powerware 9390 UPS is a continuous-duty, solid-state, transformerless (at 208 and 480 Vac), three-phase, true online system that provid...
Page 56 - backup battery supply
Understanding UPS Operation 7-2 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C If utility power is interrupted or falls outside the parameters specified in Chapter 15, “Product Specifications,” the UPS uses a backup battery supply to maintain power to the critic...
Page 57 - response to these system events:
Understanding UPS Operation 7-3 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C The UPS continually monitors itself and the incoming utility power, and automatically switches between these modes as required, without operator intervention. The sophisticated detect...
Page 58 - operating in Normal mode.; Figure 7-2. Path of Current Through the UPS in Normal Mode – RT; size of the battery string attached to the unit.
Understanding UPS Operation 7-4 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 7.2.2 Normal Mode – RT Figure 7-2 shows the path of electrical power through the UPS system when the UPS is operating in Normal mode. Static Switch K5 Rectifier Inverter K1 K3 Battery...
Page 59 - power returns, the UPS returns to Normal mode.
Understanding UPS Operation 7-5 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C The neutral from the system input is connected to the neutral regulator in the DC capacitors. The output neutral of the system is connected with the required neutral supplied at the u...
Page 60 - Figure 7-3. Path of Current Through the UPS in Bypass Mode – RT; unless the bypass input source becomes unavailable.
Understanding UPS Operation 7-6 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 7.2.3 Bypass Mode – RT The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure. The bypass source supplies the commercial AC power to ...
Page 61 - is placed into a maintenance position where repairs can be made.
Understanding UPS Operation 7-7 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C During an outage, the UPS prohibits transfers to bypass and provides upstream protection. The backfeed protection contactor is opened, preventing system output voltage from bleeding a...
Page 62 - Figure 7-4. Path of Current Through the UPS in Battery Mode – RT
Understanding UPS Operation 7-8 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 7.2.4 Battery Mode – RT The UPS automatically transfers to Battery mode if a utility power outage occurs, or if the utility power does not conform to specified parameters. In Battery ...
Page 63 - Multiple Module Parallel System
Understanding UPS Operation 7-9 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C If the input power fails to return or is not within the acceptance windows required for normal operation, the battery continues discharging until a DC voltage level is reached where t...
Page 64 - Multiple Module Parallel System Modes; command
Understanding UPS Operation 7-10 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Up to four units can be paralleled for redundancy or capacity without any additional cabinets. The system is paralleled for redundancy (1 + 1) in a system where two UPMs are parallel...
Page 65 - shared among the available UPMs in the system.; Figure 7-5. Path of Current through the UPMs in Normal Mode – Parallel; power returns, the UPMs returns to Normal mode.
Understanding UPS Operation 7-11 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 7.3.2 Normal Mode – Parallel In Normal mode, utility AC power is supplied to the UPMs. Each UPM then conditions the incoming AC power and provides clean, regulated AC power to either...
Page 66 - Figure 7-6. Path of Current through the UPMs in Bypass Mode – Parallel
Understanding UPS Operation 7-12 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 7.3.3 Bypass Mode – Parallel In Bypass mode, the output of the system is provided with three-phase AC power directly from the bypass input. While in this mode, the output of the syst...
Page 67 - source and requires operator intervention to transfer.
Understanding UPS Operation 7-13 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C The parallel system can be transferred from Normal mode to Bypass mode manually. However, the parallel system automatically switches to Bypass mode whenever the UPMs can no longer su...
Page 69 - time due to the current required to recharge the batteries.; Functional Description; energizing the rectifier.; Battery Charger and Advanced Battery Management
Understanding UPS Operation 7-15 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C If the input power fails to return or is not within the acceptance windows required for normal operation, the battery continues discharging until a DC voltage level is reached where ...
Page 71 - Chapter 8; UPS Standard Features; See Chapter 9, “Using the Control Panel,” for additional information.
8-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Chapter 8 Features, Options, and Accessories 8.1 UPS Standard Features The UPS has many standard features that provide cost-effective and consistently reliable power protection. 8.1.1 Control Panel The control p...
Page 72 - battery cabinets are wired through the side panels of the units.; Options and Accessories; installation, but may be installed separate from the UPS cabinet.
Features, Options, and Accessories 8-2 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 8.1.5 Advanced Battery Management A three-stage charging system increases battery service life by optimizing recharge time, and protects batteries from damage due to high curre...
Page 73 - Modbus
Features, Options, and Accessories 8-3 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 8.2.3 HotSync Parallel System A parallel UPS system with two to four uninterruptible power modules can be installed to provide a parallel capacity and/or redundant system. This...
Page 75 - Chapter 9; Using the Control Panel; The control panel consists of the following:
9-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Chapter 9 Using the Control Panel This chapter describes the UPS control panel, including controls and indicators, and how to monitor UPS operation. The control panel (see Figure 9-1) is located on the front doo...
Page 76 - Using the LCD and Pushbuttons; METERS; UPS status; You can use the LCD and the pushbuttons to:
Using the Control Panel 9-2 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 9.1 Using the LCD and Pushbuttons The LCD on the control panel provides an operator interface with the UPS system. Figure 9-2 identifies the display areas discussed in the following secti...
Page 77 - Using the Main Menu; Menu; CONTROLS
Using the Control Panel 9-3 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 9.2 Using the Main Menu The UPS main menu bar allows you to display data in the information area to help you monitor and control UPS operation. The following menus and options are availab...
Page 78 - Press the; EVENTS; pushbutton on the main menu bar or History Menu bar to display a; HISTORY
Using the Control Panel 9-4 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 9.2.2 Event Screens Press the EVENTS pushbutton on the main menu bar or History Menu bar to display a listing of all system events that are currently active. The most recent event is list...
Page 79 - CONTROL POWER ON
Using the Control Panel 9-5 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Press the HISTORY pushbutton on the Active Events Menu bar to display the History Log. The History Log lists up to the 500 system events in chronological order, with the most recent event...
Page 80 - pushbutton on the main menu bar to display the Unit Meter screens.; KVA
Using the Control Panel 9-6 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 9.2.3 Unit Meter Screens The Unit Meter screens show the UPS meter readings for the unit (or units, if a parallel system is installed). Press the METERS pushbutton on the main menu bar to...
Page 81 - UNIT
Using the Control Panel 9-7 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C The Input screen shows input voltage (phase-to-phase), output current (each phase), and frequency of the incoming utility source, as well as the kVA, kW, and power factor measurements. IN...
Page 82 - Battery is displayed.; VDC; The graph shows the current for each phase.
Using the Control Panel 9-8 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C The Battery screen displays the battery voltage (Vdc), the battery current (Idc), and the minutes of battery time remaining. When battery life decreases to less than 20%, Check Battery is...
Page 83 - WORD
Using the Control Panel 9-9 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 9.2.4 System Meters Screens The System Meters screens show the total system and individual UPS unit meter readings from any unit, when a parallel system is installed. Press the METERS pus...
Page 84 - Figure 9-12. Total System Output Meter Screen
Using the Control Panel 9-10 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C The Output Total System screen shows output voltage (phase-to-neutral), output current (each phase), and frequency being supplied by the UPS, as well as the kVA, kW, and power factor mea...
Page 86 - measurements for the selected unit.; factor measurements for the selected unit.
Using the Control Panel 9-12 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C The Input screen shows input voltage (phase-to-phase), output current (each phase), and frequency of the incoming utility source, as well as the kVA, kW, and power factor measurements fo...
Page 87 - for the selected unit. The graph shows the current for each phase.; OUTPUT CURRENT UNIT X
Using the Control Panel 9-13 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C The Battery screen displays the battery voltage (Vdc), the battery current (Idc), and the minutes of battery time remaining for the selected unit. When battery life decreases to less tha...
Page 88 - SETUP; ENTER PASSWORD
Using the Control Panel 9-14 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 9.2.5 System Setup Level 0 Screens Press the SETUP pushbutton on the main menu bar to display the System Setup Level 0 Screen. This screen can be used to: 쑺 Enter a password to access Le...
Page 89 - CONTRAST; CONTRAST ADJUST
Using the Control Panel 9-15 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Select CONTRAST from the System Setup Level 0 menu to display the Contrast Adjust screen. Figure 9-19 shows the Contrast Adjust screen. Use the or pushbuttons to adjust the contrast for ...
Page 90 - VERSIONS
Using the Control Panel 9-16 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Select VERSIONS from the System Setup Level 0 menu to display the Versions screen. The Versions screen provides the firmware version numbers installed on the UPS. Figure 9-20 shows the V...
Page 91 - from the System Setup Level 0 menu to display the Enter Password; DONE
Using the Control Panel 9-17 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 9.2.6 System Setup Level 1 Screens A password is required to access the Level 1 functions. To enter the password, select ENTER PASSWORD from the System Setup Level 0 menu to display the ...
Page 92 - SELECT
Using the Control Panel 9-18 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C The System Setup Level 1 screen can be used to set the UPS date and time, the serial ports, change the Level 1 password, and log out of Level 1. In addition, the Level 0 functions are av...
Page 93 - CHANGE PASSWORD
Using the Control Panel 9-19 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Select CHANGE PASSWORD from the System Setup Level 1 menu to display the Change Password screen. The Change Password screen allows the System Setup Level 1 password to be changed. Figure...
Page 94 - Press; SAVE
Using the Control Panel 9-20 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C The Change Password Save screen lets you save the new password, retry another password, or abort the password change. Figure 9-25 shows the Change Password Save screen. Press SAVE , RETR...
Page 95 - DATE AND TIME; TIME FORMAT SETUP
Using the Control Panel 9-21 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Select DATE AND TIME from the System Setup Level 1 menu to display the Time Format Setup screen. The Time Format Setup screen allows the selection of either month/day/year or day/month/y...
Page 96 - DATE
Using the Control Panel 9-22 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C The Set Date and Time MM/DD/YYYY screen allows the internal date and time of the UPS to be set in the month/day/year format. The date and time information is used for display on the scre...
Page 97 - DATE MONTH YEAR HOUR M
Using the Control Panel 9-23 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C The Set Date and Time DD/MM/YYYY screen allows the internal date and time of the UPS to be set in the day/month/year format. The date and time information is used for display on the scre...
Page 98 - COM PORT SETUP
Using the Control Panel 9-24 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Select COM PORT SETUP from the System Setup Level 1 menu to display the COM Port Setup screen. This screen allows selection of the serial COM port to set up. Figure 9-29 shows the COM Po...
Page 99 - ABORT
Using the Control Panel 9-25 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C The COM Setup screen is used to change and save the settings for the serial communication ports. The COM port number selected from the COM Port Setup screen displays. If the changes are ...
Page 100 - System Controls Screen; pushbutton on the main menu bar to display the System Controls; LOAD OFF
Using the Control Panel 9-26 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 9.3 System Controls Screen Press the CONTROLS pushbutton on the main menu bar to display the System Controls screen. LOAD OFF, normal operation, transfer to bypass, charger control, and ...
Page 101 - switch toggles the power module function On and Off.
Using the Control Panel 9-27 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C SYSTEM CONTROLS LOAD OFF PM OFF CHGR ON MAINTENANCE BYPASS BYPASS POWER MODULE (PM) OFF : OFF : ONLINE : CHARGER OFF : Figure 9-32. System Controls Screen 2 The CHGR pushbutton switch to...
Page 102 - Load Off Screen; Chapter 10, “UPS Operating Instructions.”; HOLD LOAD OFF BUTTON FOR 3 SECONDS
Using the Control Panel 9-28 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 9.4 Load Off Screen The Load Off screen appears when the LOAD OFF pushbutton is selected from the main menu bar or System Controls Menu bar. This screen allows the LOAD OFF process to be...
Page 103 - Reading the Status Indicators; status indicators
Using the Control Panel 9-29 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 9.5 Reading the Status Indicators The four symbols on the right side of the control panel are status indicators . They are colored light emitting diode (LED) lamps, and they work in conj...
Page 105 - UPS Operating Instructions; Single Module Operation
10-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Chapter 10 UPS Operating Instructions The following procedures provide instructions for operating the UPS or parallel system. For a description of the UPS control panel functions, see Chapter 9, “Using the Cont...
Page 106 - DC STARTING; NORMAL
UPS Operating Instructions 10-2 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 7. Observe the following messages appear sequentially on the power module (PM) status line: DC STARTING INVERTER STARTING INVERTER SYNCING READY ONLINE The rectifier and inverter turn...
Page 107 - Transfer from Normal to Bypass Mode
UPS Operating Instructions 10-3 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 10.1.3 Starting the Power Module To start the power module without transferring the critical load to normal, perform the following procedure: 1. Close the UPS input feeder circuit bre...
Page 108 - Transfer from Bypass to Normal Mode; The; Transfer from Normal to Bypass Mode and Shut Down UPS
UPS Operating Instructions 10-4 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 3. The UPS is now operating in Bypass mode and the BYPASS status indicator is illuminated. The power module (PM) status indicates READY. The system is now on bypass and the UPS power ...
Page 111 - A UPS emergency power-off is initiated by the; REPO; To use the REPO switch:; Press the REPO pushbutton switch.
UPS Operating Instructions 10-7 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 10.1.10 Using the Remote Emergency Power-Off Switch A UPS emergency power-off is initiated by the REPO pushbutton switch. In an emergency, you can use this switch to control the UPS o...
Page 112 - Multiple Module Parallel Operation; Starting the Parallel System in Normal Mode
UPS Operating Instructions 10-8 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 10.2 Multiple Module Parallel Operation 10.2.1 Starting the Parallel System in Normal Mode To start the parallel system, perform the following procedure: 1. Close all uninterruptible ...
Page 113 - Starting the Parallel System in Bypass Mode
UPS Operating Instructions 10-9 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 10.2.2 Starting the Parallel System in Bypass Mode If the inverter output of the UPMs is not available and the critical load needs to be energized, perform the following procedure: C ...
Page 114 - Transfer Parallel System from Normal to Bypass Mode; Transfer Parallel System from Bypass to Normal Mode
UPS Operating Instructions 10-10 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 10.2.3 Transfer Parallel System from Normal to Bypass Mode To transfer the critical load to Bypass mode, perform the following procedure: C A U T I O N In Bypass mode, the critical l...
Page 116 - Parallel System and Critical Load Shutdown
UPS Operating Instructions 10-12 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 7. Press the NORMAL pushbutton on the System Controls menu bar of the UPM. 8. Observe the following messages appear sequentially on the power module (PM) status line of the UPM: DC S...
Page 118 - Using the Parallel System Remote Emergency Power-Off Switch
UPS Operating Instructions 10-14 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 10.2.9 Using the Parallel System Remote Emergency Power-Off Switch A parallel system emergency power-off is initiated by the REPO pushbutton switch. In an emergency, you can use this...
Page 119 - Using Features and Options; and terminals and for terminal wiring information, see:; Building Alarm Monitoring; connections are located inside the UPS.; General Purpose Relay Contact; area where the UPS horn may not be heard immediately.
11-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Chapter 11 Using Features and Options The many standard features of your UPS system provide consistent, economical, and dependable power protection. In addition, you can add available options to enhance the per...
Page 120 - Optional Remote Monitor Panel; Table 11-1. Optional Monitoring Accessories; Number and Type of Accessories Permitted
Using Features and Options 11-2 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 11.3 Optional Remote Monitor Panel As an option, a Remote Monitor Panel (RMP) can be installed to monitor the operation of the UPS system from virtually any location within the facili...
Page 122 - Relay Interface Module; Table 11-3. Customer Interface Connectors
Using Features and Options 11-4 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 11.4 Relay Interface Module An optional RIM uses relay contact closures to indicate the operating status and alarm condition of the UPS system. The RIM can be flush-mounted or surface...
Page 123 - Supervisory Contact Module; Table 11-4. SCM Status Indicators and Connections; ON GENERATOR
Using Features and Options 11-5 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 11.5 Supervisory Contact Module An optional SCM establishes an interface between the UPS system and the customer’s monitor. This interface allows the customer to monitor operational s...
Page 125 - Responding to System Events; Select; Events; System Event Horns; place. Horn 1 cycles at a one second rate.; System Event Indicators
12-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Chapter 12 Responding to System Events 12.1 General When the UPS system is running in Normal mode, it continually monitors itself and the incoming utility power. In Battery or Bypass modes, the UPS may issue al...
Page 126 - ALARMS
Responding to System Events 12-2 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C ALARMS Message Horn Phone Relay Log* Indication Battery Totally Discharged 1 No 1 HA Shutdown Imminent Battery Totally Discharged OK Off No 1 HA Condition Cleared Building Alarm 1 1 ...
Page 129 - NOTICES
Responding to System Events 12-5 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C NOTICES Message Horn Phone Relay Log* Indication Automatic Shutdown Pending 1 No No A Information Only Automatic Shutdown Pending OK OFF No No A Condition Cleared Automatic Startup P...
Page 132 - STATUS
Responding to System Events 12-8 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C STATUS Message Horn Phone Relay Log* Indication Battery Switchgear Closed No No No H User Status Battery Switchgear Open No No No H User Status Bypass Switchgear Closed No No No H Us...
Page 133 - COMMAND
Responding to System Events 12-9 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C COMMAND Message Horn Phone Relay Log* Indication Load Off Command Received Yes No No H Information Only To Normal Mode Command No No No H Information Only To Bypass Command No No No ...
Page 135 - Communication
13-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Chapter 13 Communication This chapter describes the communication features of the Powerware 9390 40–80 kVA UPS and provides information about connecting hardware and using Terminal mode. 13.1 X-Slot Cards The P...
Page 136 - LanSafe Power Management Software; can select the most useful view for their specific needs.; Remote Notification; Remote and local ability to clear Call Out alarms and events.
Communication 13-2 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Relay Interface Card Modem Card Modbus Card ConnectUPS-X Web/SNMP Card Hot Sync CAN Bridge Card Industrial Relay Card Figure 13-1. Optional X-Slot Cards 13.2 LanSafe Power Management Software Each...
Page 137 - and enter Terminal mode.; In Terminal mode, the user can request the following:
Communication 13-3 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Remote Notification differs from the basic Terminal mode with the addition the following functions: 쑺 Call AnswerThe Call Answer function allows the user to call into the UPS from a remote locatio...
Page 138 - connected to the port.
Communication 13-4 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 13.4.2 Event History Log This key sequence prints the entire Event History Log of the UPS at the time the data is requested. The printout begins with the oldest alarm entry in the queue and ends w...
Page 141 - Maintaining the UPS System; Important Safety Instructions; EVEN WHEN; DO NOT ATTEMPT TO ACCESS
14-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Chapter 14 Maintaining the UPS System The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, with very little disassembly. T...
Page 142 - Performing Preventive Maintenance; are in good condition.
Maintaining the UPS System 14-2 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 쑺 Determine if the battery is inadvertently grounded. If it is, remove the source of the ground. Contact with any part of a grounded battery can result in electrical shock. The likeli...
Page 143 - Maintenance Training
Maintaining the UPS System 14-3 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 3. Ensure the operating environment is within the parameters specified in Chapter 15, “Product Specifications,” and Drawing 164201535-2 on page A-3. 4. Ensure the UPS is in Normal mod...
Page 145 - Product Specifications
15-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Chapter 15 Product Specifications 15.1 Model Numbers The UPS systems are housed in free-standing cabinets with safety shields behind the doors. The UPS systems are available in 50/60 Hz with various output powe...
Page 147 - Multiple Module Parallel Specifications
Product Specifications 15-3 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 15.3 Multiple Module Parallel Specifications 15.3.1 UPM Input Same as single module. 15.3.2 UPM Output Same as single module. 15.3.3 Environmental Same as single module. 15.3.4 Battery Sa...
Page 149 - Appendix A; the UPS system. This appendix contains the following drawings:
A-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Appendix A 16- Installation Information The information in this appendix is helpful during the planning and installation of the UPS system. This appendix contains the following drawings: 쑺 164201535-1 Typical Po...
Page 151 - The UPS cabinet is palleted separately for shipping.
DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 164201535 --- 2 1 of 2 PHYSICAL FEATURES AND REQUIREMENTS 111504 B Installation Information A-3 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 1. The UPS equipment operating environment must meet weight requirement...
Page 152 - Ambient Temperature Range:; The UPS ventilation requirements are shown in Table C.
2 of 2 PHYSICAL FEATURES AND REQUIREMENTS 111504 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: B 164201535 --- 2 Installation Information A-4 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 7. The basic environmental requirements for operation of the UPS system...
Page 154 - Remove jumper for dual feed.; SINGLE OR DUAL FEED
BATTERY BREAKER 1 of 5 UPS SYSTEM ONELINE DRAWING 111504 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: B 164201535 --- 4 UPS CABINET INVERTER RECTIFIER STATIC SWITCH REMOTE EPO BUILDING ALARMS AC OUTPUT TO CRITICAL LOAD AC INPUT TO UPS RECTIFIER 3 WIRE A --- B --- C AC INPUT TO BYPASS 4 WIRE A ---...
Page 156 - TYPICAL PARALLEL SYSTEM
UPS SYSTEM ONELINE DRAWING 093004 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: B OUTPUT TO CRITICAL LOAD BATTERY CABINET BATTERY BREAKER E4. E5 E9 E10 E11 E12 FUSE K5 STATIC SWITCH FUSE K3 FUSE BATTERY CONVERTER RECTIFIER INVERTER K1 UPM 1 E1 E2 E3 E6E 7E8 E12 A B SEE NOTE 2 MODULE TIE CABINET (O...
Page 159 - Callout letters
1 of 16 POWER WIRING INSTALLATION NOTES 111504 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: B 164201535 --- 5 Installation Information A-11 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Table E. INPUT/OUTPUT Ratings & External Wiring Requirements for Pow...
Page 163 - Customer ground can be run in any conduit listed in Table K.; Terminals are UL and CSA rated at 90
POWER WIRING INSTALLATION NOTES 111504 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: B 164201535 --- 5 NOTE: Customer ground can be run in any conduit listed in Table K. 5 of 16 Installation Information A-15 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 8. Te...
Page 167 - is required, it is to be supplied by the user.; 0 kVA load, regardless of the rating of the UPS.
POWER WIRING INSTALLATION NOTES 111504 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: B 164201535 --- 5 9 of 16 Installation Information A-19 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 12. External overcurrent protection is not provided by this product, but...
Page 169 - termination requirements.
POWER WIRING INSTALLATION NOTES 093004 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: B 164201535 --- 5 11 of 16 Installation Information A-21 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 23. Parallel system UPM and system bypass input feeds must come from th...
Page 174 - This rule has a tolerance of approximately
POWER WIRING INSTALLATION NOTES 093004 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: B 164201535 --- 5 UPM 2 Battery Bypass inputs to UPMs UPM 1 Battery UPM 3 Battery UPM 4 Battery Outputs from UPMs 1A 2A 3A 4A 1B 2B 3B 4B 16 of 16 Installation Information A-26 Powerware ® 9390 UPS (40–80 kVA) Ins...
Page 175 - TOP VIEW
1 of 2 CONDUIT AND WIRE ENTRY LOCATIONS 111504 B 164201535 --- 6 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: REMOVE DEBRIS SHIELD COVERING EXHAUST GRILL BEFORE OPERATING SYSTEM. TOP ENTRY CONDUIT LANDING FOR AC INPUT AND OUTPUT, DC INPUT, DC CONTROL, AND INTERFACE CONNECTIONS. (REMOVE PANEL TO D...
Page 176 - LEFT SIDE VIEW
2 of 2 CONDUIT AND WIRE ENTRY LOCATIONS 111504 B DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: LEFT SIDE VIEW RIGHT SIDE VIEW INTER-CABINET WIRING ACCESS KNOCKOUTS. REMOVE KNOCKOUTS, AS REQUIRED, TO ROUTE WIRES BETWEEN CABINETS. INSIDE PANELS INTER-CABINET WIRING ACCESS KNOCKOUTS. REMOVE KNOCKOUTS...
Page 177 - Metal shields covering wiring
1 of 4 UPS POWER TERMINAL LOCATIONS 111504 B 164201535 --- 7 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 208V INPUT AND 208V OUTPUT NOTE: Metal shields covering wiring terminals must be removed or opened to gain access to terminals. GROUND TERMINALS AC INPUT TO UPS RECTIFIER AND BYPASS (A, B, C,...
Page 178 - TERMINAL DETAIL
2 of 4 UPS POWER TERMINAL LOCATIONS 111504 B 164201535 --- 7 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 208V INPUT AND 208V OUTPUT RECTIFIER INPUT TERMINALS BYPASS INPUT TERMINALS NEUTRAL TERMINALS (E12) OUTPUT TERMINALS DC INPUT FROM BATTERY + (E4) --- (E5) AC INPUT TO UPS RECTIFIER (DUAL INPU...
Page 181 - facility planners or the customer.
1 of 12 INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS 111504 B DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 164201535 --- 8 Installation Information A-33 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 1. Use Class 1 wiring methods (as defined by ...
Page 182 - INTERFACE TERMINAL LOCATIONS
X --- SLOTS STANDARD X --- SLOT COMMUNICATION BAY 1 2 3 4 OPTIONALX --- SLOT COMMUNICATION BAY WIREWAY FOR BOTTOM ENTRY INTERFACE WIRING 111504 B 164201535 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS NOTE: Metal shields covering wi...
Page 183 - INTERFACE TERMINALS
NOTE: 1. All building alarm inputs or remote features require an isolated normally- open contact or switch (rated at 24 Vdc, 20 mA minimum) connected between the alarm input and common terminal as shown. All control wiring and relay and switch contacts are customer provided. 2. Regardless of assignm...
Page 184 - the DC source disconnect device.
111504 B 164201535 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS 4 of 12 Installation Information A-36 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 9. The UPS DC UVR trip and Battery Aux signal...
Page 185 - EPO contact is not used.
111504 B 164201535 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS 5 of 12 Installation Information A-37 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C 11. The Remote EPO feature opens all contacto...
Page 187 - Hot Sync CAN Bridge Card; interface wiring in separate conduit from the power wiring.
111504 B 164201535 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS Hot Sync CAN Bridge Card CONNECTIONS FOR PARALLEL SYSTEM CONTROL CONNECTIONS FOR RMP, RIM, OR SCM (ONLY ONE DEVICE CAN BE CONNECTED AT A TIME) BUILDING ALARM 2 REPLACEM...
Page 188 - PARALLEL SYSTEM CAN AND BACK UP CONTROL (PULL CHAIN); PARALLEL SYSTEM CAN WIRING
093004 B 164201535 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS NOTE: This drawing is for parallel wiring purposes and is not a floor layout plan. UPMs can be placed in any physical order. PARALLEL SYSTEM CAN AND BACK UP CONTROL (PU...
Page 189 - PARALLEL SYSTEM BACK UP
Installation Information A-41 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Building Alarm Pull Chain Wiring Terminations From UPM 1 To UPM 2 To UPM 3 (If Installed) To UPM 4 (If Installed) TB1–2 (BA 2) TB1–2 (BA 2) TB1–2 (BA 2) TB1–2 (BA 2) TB1–3 (Rtn) TB1–3 (...
Page 190 - ALTERNATE PARALLEL SYSTEM
Installation Information A-42 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Alternate Building Alarm Pull Chain Wiring Terminations From UPM 1 To UPM 2 To UPM 3 (If Installed) To UPM 4 (If Installed) CAN Card J3–1 (Alarm) CAN Card J3–1 (Alarm) CAN Card J3–1 (Al...
Page 191 - REMOTE MONITOR PANEL AND RELAY
111504 B 164201535 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS TERMINAL TB–1 SIGNAL CONNECTIONS FROM THE UPS GROUND TERMINAL REMOTE MONITOR PANEL AND RELAY INTERFACE MODULE TERMINAL LOCATIONS TERMINAL TB–3 120 VAC POWER SUPERVISORY...
Page 192 - The wire should be rated for 1A minimum.
111504 B 164201535 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS UPS CAN CARD J3 120 VAC FROM CRITICAL BUS LINE NEUTRAL TWISTED PAIR GROUND TERMINAL RMP, RIM, OR SCM 12 of 12 Installation Information A-44 Powerware ® 9390 UPS (40–80 ...
Page 195 - BOTTOM VIEW with OPTIONAL FLOOR MOUNTING BRACKETS
UPS CABINET DIMENSIONS 111504 B 164201535 --- 9 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: Dimensions are in millimeters [inches] 3 of 4 BOTTOM VIEW with OPTIONAL FLOOR MOUNTING BRACKETS Installation Information A-47 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535...
Page 196 - BOTTOM VIEW with OPTIONAL SEISMIC MOUNTING BRACKETS
UPS CABINET DIMENSIONS 111504 B 164201535 --- 9 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: Dimensions are in millimeters [inches] 4 of 4 BOTTOM VIEW with OPTIONAL SEISMIC MOUNTING BRACKETS Installation Information A-48 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 1642015...
Page 197 - Conduit and wiring between the
1 of 1 OPTIONAL REMOTE EMERGENCY POWER-OFF 111504 B 164201535 --- 10 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 114.3 (4.50) 115.8 (4.56) 11.9 (0.47) 95.3 (3.75) SQUARE 88.9 (3.50) 1/2 in. Knockout Pattern typ. 5 sides TO UPS TO OTHER EQUIPMENT NOTE: 1. Conduit and wiring between the Remote Eme...
Page 203 - Warranty
W-1 Powerware ® 9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C Warranty LIMITED FACTORY WARRANTY FOR POWERWARE ® 9390 PRODUCTS WARRANTOR: The warrantor for the limited warranties set forth herein is Powerware Corporation, a Delaware Corporation (“Powerware”). LIMITED WARRAN...