Page 2 - IMPORTANT SAFETY INSTRUCTIONS; Instructions Importantes Concernant La Sécurité; SAVE THESE INSTRUCTIONS; Conserver Ces Instructions
ii Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 ------------------------------------------------------------------------ ------------------------------------------------------------------------ ---------------------------------- IMPORTANT SAFETY INSTRUCTIONS In...
Page 3 - Table of Contents; Introduction; Section I; Getting Started
iii Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Table of Contents Introduction xiii . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Configurations xiv . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 4 - Installing and Connecting Batteries; Section II; Understanding UPS Operation
iv Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 2.5 Initial Startup 2 --- 28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.6 Completing the Installation Checklist 2 --- 28 . . . . . . . . . . . . . . . . . . . . . . 2.6...
Page 7 - Remote Notification
vii Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 13 Remote Notification 13 --- 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13.1 Description 13 --- 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 8 - List of Figures
viii Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 List of Figures Figure 1 --- 1. Powerware 9330 (10 kVA --- 20 kVA) Cabinet as Shipped on Pallet 1 --- 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 1 --- 2. Powerware 9330 (25 kVA --- 40...
Page 10 - Input Meter
x Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Figure 12 --- 8. Events --- Active 12 --- 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 12 --- 9. Input Meter 12 --- 7 . . . . . . . . . . . . . . . . . . . . . . . ...
Page 11 - List of Tables
xi Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 List of Tables Table 4 --- 1. Remote EPO Wire Terminations 4 --- 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Table 4 --- 2. Remote EPO 4 --- 3 . . . . . . . . . . . . . . . . . . . . . . . ...
Page 12 - This Page Intentionally Left Blank.
xii Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 This Page Intentionally Left Blank.
Page 13 - System
xiii Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Introduction Powerware 9330 UPS true double conversion online power protection can be utilized to prevent loss of valuable electronic information, minimize equipment downtime, and/or minimize the adverse effect ...
Page 14 - System Configurations; These UPS system configurations are possible:
xiv Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 UPS CABINET BATTERY CABINET OPTIONS CABINET Typical Powerware 9330 (25 kVA --- 40 kVA) UPS System System Configurations These UPS system configurations are possible: · Single Module UPS with integral battery · Si...
Page 15 - Remote Monitor; Using This Manual
xv Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 · Parallel System with one to four UPS modules with remote battery and optional options cabinet · Parallel System with one to four UPS modules and integral battery · Parallel System with one to four UPS modules, i...
Page 16 - Conventions Used in This Manual; Bold type; Italic type
xvi Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 · Chapter 8 -- Using the Control Panel -- describes the controls and indicators found on the Control Panel and shows the various information screens displayed on the LCD screen. · Chapter 9 -- UPS Operating Instr...
Page 17 - Safety Considerations; If service or routine maintenance is required:
xvii Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Safety Considerations The UPS cabinet is designed for industrial or computer room applications, and contain safety shields behind the doors. However, the UPS system is a sophisticated power system and should be ...
Page 18 - For More Information; Powerware; Getting Help; manual does not answer, please call Powerware Corporation at:; United States
xviii Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 For More Information This manual describes how to install and operate the UPS modules. For more information about the installation and operation of a Parallel System, refer to the following: 164201363 Powerware...
Page 21 - Installing the UPS; The cabinet sections of the
Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 1--1 n Getting Started 1.1 Installing the UPS The cabinet sections of the UPS are shipped on separate pallets. Use a forklift or pallet jack, rated to handle the weight of the cabinets (refer to Drawing 164201300 ---...
Page 22 - following guidelines:; Preparing for Wiring the UPS System
1--2 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 The basic environmental requirements for operation of the UPS system are: Ambient Temperature Range: 0 --- 40 ˚ C (32 --- 104 ˚ F) Recommended Operating Range: 20 --- 25 ˚ C (68 --- 77 ˚ F) Maximum Relative Humi...
Page 23 - Inspecting and Unpacking Each Cabinet
Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 1--3 1.1.5 Inspecting and Unpacking Each Cabinet The first task in preparing for installation is inspecting and unpacking the UPS sections. The UPS and accessory cabinets are shipped bolted to wooden pallets, as show...
Page 24 - supports on the bottom of the unit.
1--4 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Figure 1 --- 2. Powerware 9330 (25 kVA --- 40 kVA) UPS Cabinet as Shipped on Pallet 1. Carefully inspect the outer packaging for evidence of damage during transit. CAUTION: Do not install a damaged cabinet. Repo...
Page 27 - Installing the UPS System; Preliminary Installation Information; Installation should be performed only by qualified personnel.; Refer to the following while installing the UPS system:
2--1 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Installing the UPS System 2.1 Preliminary Installation Information WARNING: Installation should be performed only by qualified personnel. Refer to the following while installing the UPS system: · Refer to Append...
Page 28 - UPS Cabinet Installation; remove the pallet, perform the following procedure:; brackets and securing hardware for later use.
2--2 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 2.2 UPS Cabinet Installation To install an UPS cabinet, perform the procedures in the following paragraphs. 2.2.1 Unloading the Powerware 9330 (10 kVA --- 20 kVA) UPSCabinet from the Pallet The UPS cabinet is bo...
Page 29 - FRONT VIEW
2--3 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 VENTED FRONT PANEL SOLID FRONT PANEL FRONT SHIPPING BRACKET (3) PALLET SHIPPING BOLTS (2) SHIPPING BOLTS (1) FRONT VIEW Figure 2 --- 1. Removing Front Shipping Bracket (Powerware 9330 (10 kVA --- 20 kVA))
Page 30 - REAR VIEW
2--4 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 REAR SHIPPING BRACKET (3) PALLET SKID BOLTS (4) (3 PLACES) REMOVABLE SKID (5) REAR VIEW SHIPPING BOLTS (1) SHIPPING BOLTS (2) Figure 2 --- 2. Removing Rear Shipping Bracket (Powerware 9330 (10 kVA --- 20 kVA))
Page 35 - Installing; Optional Remote Battery Power Wiring to the; plate to punch conduit holes.
2--9 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 2.2.3 Installing Optional Remote Battery Power Wiring to the Powerware 9330 (10 kVA --- 20 kVA) UPS If installing a remote battery system, perform the following procedure: CAUTION: When sizing battery system, do...
Page 37 - Installing UPS External Power Wiring; gain access to input and output terminals.
2--11 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 2.2.5 Installing UPS External Power Wiring 1. Remove left front solid panel and right front vented panel from the Powerware 9330 (10 kVA --- 20 kVA) UPS cabinet or left front solid panel and front vented panels...
Page 38 - Installing Customer Connections; To prepare the UPS for wiring to Customer Connections:; Prepare for Installing Accessories; If installing accessories, such as the Remote Emergency Power Off; To prepare the UPS for wiring to Accessories:
2--12 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 2.2.6 Installing Customer Connections NOTE: If installing connections (building alarms, relay outputs, or external CAN for a Parallel System) to the Communications Server Board (CSB), you must install conduit b...
Page 39 - Battery Cabinet Installation; Unloading the Battery Cabinet from the Pallet
2--13 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 2.3 Battery Cabinet Installation To install optional battery cabinets, perform the procedures in the following paragraphs. 2.3.1 Unloading the Battery Cabinet from the Pallet To remove the Battery cabinet from ...
Page 44 - Joining Additional Battery Cabinets
2--18 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 14. Install side panel removed from the UPS cabinet to the right side of the Battery cabinet. Secure with screws removed from Battery cabinet. 15. When all wiring is complete, proceed to Chapter 3 and connect b...
Page 46 - Options Cabinet Installation; Unloading the Options Cabinet from the Pallet
2--20 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 2.4 Options Cabinet Installation 2.4.1 Unloading the Options Cabinet from the Pallet To remove the Options cabinet from the pallet, refer to paragraph 2.2.1. 2.4.2 Joining the Options Cabinet to the UPS Cabinet...
Page 51 - Secure cabinets to floor with contractor supplied hardware.
2--25 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 13. Remove the top side panel mounting screw (tie/grounding bracket location in Figures 2 --- 9 or 2 --- 11) from both the Option and UPS cabinets. 14. Secure the back of Options cabinet to the back of the UPS ...
Page 52 - Installing Options Cabinet Internal Power Wiring
2--26 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 2.4.3 Installing Options Cabinet Internal Power Wiring 1. Remove left front solid panel, and right front vented panel from the Powerware 9330 (10 kVA --- 20 kVA) UPS cabinet or left front solid panel and front ...
Page 53 - Installing Options Cabinet External Power Wiring
2--27 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 2.4.4 Installing Options Cabinet External Power Wiring NOTE: Remove Options cabinet input and output conduit landing plate to punch conduit holes. 1. Route input and output cables to input/output terminal block...
Page 54 - system for the first time.
2--28 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 NOTE: Remove Options cabinet PDM conduit landing plate to punch conduit holes. 15. Install Square-D Type QO or QOB breakers into PDM panelboard. Refer to Appendix A of this manual for access information. 16. Wi...
Page 55 - Installation Checklist
2--29 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 2.6.1 Installation Checklist - All packing materials and restraints have been removed from each cabinet. - Each cabinet in the UPS system is placed in its installed location. - A cabinet grounding/mounting kit ...
Page 56 - Notes
2--30 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Notes ________________________________________________________________________________ ________________________________________________________________________________ __________________________________________...
Page 57 - Important Safety Instructions; Use tools with insulated handles.
3--1 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Installing and Connecting Batteries 3.1 Important Safety Instructions This chapter describes installing the UPS batteries.The installation of batteries should be performed or supervised by personnel knowledgeabl...
Page 58 - Battery Installation; Installing Internal Batteries in the UPS Cabinet
3--2 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 3.2 Battery Type The following battery types are supplied in the UPS Cabinets and external Battery Cabinets. When purchasing UPS Cabinets or external Battery Cabinets without batteries, only the following types ...
Page 59 - and Battery Cabinet
3--3 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Figure 3 --- 1. Battery Schematic --- Powerware 9330 (10 kVA --- 20 kVA) UPS and Battery Cabinet
Page 61 - Installing Internal Batteries in the Battery Cabinet; Connecting Batteries; Electrically Connecting Integral Battery Strings
3--5 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 3.3.2 Installing Internal Batteries in the Battery Cabinet If the battery cabinet was ordered without batteries, install the batteries in accordance with the following procedure. WARNING: LETHAL VOLTAGE WILL BE ...
Page 62 - Electrically Connecting Battery Cabinet Battery; forward to disengage magnetic latches.
3--6 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 3. Remove screws securing internal safety shield panels and remove panels to gain access to batteries. 4. Connect the string of battery trays together by mating the loose red connector from each tray to the fixe...
Page 64 - Install and connect remote Battery System as follows:
3--8 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 3.5 Installing and Connecting Remote Battery System Install and connect remote Battery System as follows: CAUTION: When sizing battery system, do not exceed internal battery charger capabilities. Refer to Chapte...
Page 65 - Installing a Remote Emergency; Installation Procedures; Before installing a Remote EPO, be sure you have prepared the UPS; To install a Remote EPO control:; stud within the wall. Do not use hollow wall anchors.
4--1 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Installing a Remote Emergency Power Off (EPO) Control 4.1 Installation Procedures Figure 4 --- 1. Remote EPO Control 4.2 To install a Remote EPO: NOTE: Before installing a Remote EPO, be sure you have prepared t...
Page 66 - Mount cover to Remote EPO switch enclosure bottom, as shown in
4--2 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 TB2 TB1 COVER BOTTOM ENCLOSURE Figure 4 --- 2. Remote EPO Control (inside view of cover and bottom of enclosure) 3. Mount cover to Remote EPO switch enclosure bottom, as shown in Figure 4 --- 2, for easier wirin...
Page 69 - shows the enclosure dimensions and cable exit openings.
5--1 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Installing a Remote Monitor Panel 5.1 Installation Procedures As an option, you can install a Remote Monitor Panel (RMP) to monitor the operation of the UPS system from virtually any location within your facilit...
Page 75 - Looking Inside the UPS System; critical load
6--1 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Understanding UPS Operation 6.1 Looking Inside the UPS System The Powerware 9330 is a continuous duty, solid-state, transformerless (at 208 VAC), three phase, true online system that provide conditioned and unin...
Page 76 - “Product Specifications,” the UPS uses a
6--2 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 DIGITAL AC INPUT TO AC INPUT TO AC OUTPUT INPUT RECTIFIER INVERTER FILTER METERING RECTIFIER/ BYPASS TO CRITICAL STATIC SWITCH CHARGER LOAD OUTPUT FILTER INPUT BATTERY BREAKER CB2 BREAKER CB1 POWER PROCESSING UN...
Page 77 - UPS Modes; load. There are four standard operation modes:
6--3 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 6.2 UPS Modes The UPS system functions automatically to supply AC electrical power to the critical load. There are four standard operation modes: · In Normal mode, the critical load is supplied by the inverter, ...
Page 78 - Normal Mode; UPS is operating in Normal mode.; NORMAL MODE; level on the battery during normal operation.
6--4 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 6.2.1 Normal Mode Figure 6 --- 2 shows the path of electrical power through the UPS system when the UPS is operating in Normal mode. CB1 CB2 K1 K5 K3 K2 Open Closed Breakers Contactors Main Power Flow Energized ...
Page 80 - Bypass Mode; operating in Bypass mode.; The critical load is not protected while the UPS is in Bypass mode.; BYPASS MODE
6--6 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 6.2.2 Bypass Mode The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure. The bypass source supplies the commercial AC power to the load directly.Figure 6 --- 3 ...
Page 81 - Bypass mode, an alarm condition is recorded.
6--7 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 the inverter rectifier. The static switch being an electronically controlled device can be turned on immediately to pickup the load from the inverter while the inverter output contactor K3 opens to isolates the ...
Page 82 - High Efficiency Mode; operating in High Efficiency mode.; HIGH EFFICIENCY MODE; While the UPS is in High Efficiency mode, the; NORMAL; light on the front display
6--8 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 6.2.3 High Efficiency Mode When the UPS is operating in High Efficiency mode, the bypass source supplies the commercial AC power to the load directly.Figure 6 --- 4 shows the path of electrical power through the...
Page 83 - Battery Mode; operating in Battery mode.; BATTERY MODE
6--9 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 6.2.4 Battery Mode The UPS transfers to Battery mode automatically if a utility power outage occurs, or if the utility power does not conform to specified parameters. In Battery mode, the battery provides emerge...
Page 85 - Test and Maintenance Bypass Modes; the UPS system when operating in Maintenance Bypass mode.; The critical load is not protected while the UPS is in Test or; TEST MODE
6--11 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 6.2.5 Test and Maintenance Bypass Modes An internal maintenance switch is used to safely supply utility power to the system output during periods of maintenance or repairs. Before this switch is used, the UPS s...
Page 86 - MAINTENANCE BYPASS MODE; Functional Description
6--12 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 CB1 CB2 K1 K5 K3 K2 Open Closed Breakers Contactors Main Power Flow Energized De-- Energized Trickle Current RECTIFIER STATIC SWITCH BOOST CONVERTER INVERTER MAINTENANCE BYPASS MODE CHARGER BATTERY MAINTENANCE ...
Page 87 - Boost Converter and Neutral Regulator; out the high frequency switching components (line to neutral).
6--13 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 6.3.2 Boost Converter and Neutral Regulator A Boost Converter converts the raw DC IN to a regulated DC Link of approximately 400 volts DC. It is operated in current mode and controlled using a variable frequenc...
Page 89 - General; Control Panel; LOAD OFF
7--1 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Operational Controls and Features 7.1 General The UPS system should function automatically and require very little attention during normal operation. The controls and indicators identified in this section are us...
Page 92 - UPS Cabinet; Optional Battery Cabinet; Optional Options Cabinet; UPS Standard Features; Computer Interface; Building Alarm Monitoring
7--4 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 7.2.2 UPS Circuit Breakers The UPS can contain as many as 10 circuit breakers, depending on the system options. The UPS circuit breakers are described in detail in Chapter 9, “UPS Operating Instructions.” UPS Ca...
Page 93 - Summary Alarm Contacts; cards are hot pluggable.; Options and Accessories; pushbutton is a required option to; REMOTE EMERGENCY POWER OFF; pushbutton is
7--5 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Summary Alarm Contacts Alarm contacts are provided for connection to equipment at your facility, such as a light, an audible alarm, or a computer terminal. The equipment you connect to these contacts alerts you ...
Page 94 - Bypass Input Isolation Transformer (Dual Input); Output Isolation Transformer; Power Distribution Module; UPM and as backup for each other.
7--6 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 7.4.2 Remote Monitor Panel An optional Remote Monitor Panel (RMP) contains backlit status indicators and a local horn, allowing you to monitor the operational status and alarm condition of the UPS from virtually...
Page 95 - Modem; SNMP adapter
7--7 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 7.4.6 Communications Modem An optional modem is available for use with the Remote Notification feature described in Chapter 13, “Remote Notification”. Refer to the manual supplied with the modem for modem operat...
Page 96 - handled with appropriate care, following these guidelines:
7--8 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 7.5 Safety Considerations The UPS enclosure is designed for industrial or computer room applications, and contain safety shields. However, the system is sophisticated and should be handled with appropriate care,...
Page 99 - Using the Control Panel; Description; The Control Panel contains the red; system control pushbutton switch (
8--1 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Using the Control Panel 8.1 Description This chapter describes the UPS Control Panel, including controls and indicators, and how to monitor UPS operation. The Control Panel is located on the front of the UPS (se...
Page 100 - Using the LCD Screen and Pushbuttons; Alarm
8--2 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 8.2 Using the LCD Screen and Pushbuttons The LCD screen on the Control Panel provides an operator interface with the UPS system. Figure 8 --- 2 identifies the display areas discussed in the following sections. A...
Page 101 - Using the Main Menu; main menu; EVENTS
8--3 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 8.3 Using the Main Menu The UPS main menu allows you to display data in the information area to help you monitor and control UPS operation. The following menus and options are available: · EVENTS Displays the li...
Page 102 - NORMAL MODE COMMAND
8--4 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 8.3.2 System Event Screens Select EVENTS from the Main menu to display the Event History Log. The Event History Log lists up to 500 system events in chronological order, with the most recent event listed last. T...
Page 103 - Select; METERS; from the Main menu to display the System Meter screens.; IA
8--5 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 8.3.3 System Meter Screens Select METERS from the Main menu to display the System Meter screens. Figures 8 --- 6 through 8 --- 10 show the System Meter screens.To scroll through the meter screens, select the or ...
Page 105 - the UPS. The graph shows the current for each phase.; Output
8--7 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 The Output Current Screen displays a real-time bar graph of the output current of the UPS. The graph shows the current for each phase. Output I A B C 125% 100% 75% 50% 25% 0% Figure 8 --- 10. Output Current (Loa...
Page 106 - SYSTEM SETUP; CONTRAST; CONTRAST ADJUST
8--8 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 8.3.4 Setup Menu Screens Select SETUP from the Main menu to display the System Setup Screen. This screen can be used to set the screen contrast, the UPS date and time, the serial ports, and show the firmware ver...
Page 108 - SERIAL PORTS; “Serial; COM
8--10 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Select SERIAL PORTS from the System Setup menu to display the Serial Port screen. The Serial Port screen allow you to specify settings for the serial communication ports on the UPS. Figure 8 --- 14 shows the Se...
Page 109 - from the System Setup menu to display the Versions screen.; VERSIONS
8--11 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Select VERSIONS from the System Setup menu to display the Versions screen. The Versions screen provides the firmware version numbers installed on the UPS. Figure 8 --- 15 shows the Versions screen. To return to...
Page 110 - System Controls Screen; CONTROLS; from the Main menu screen or use the SYSTEM CONTROL
8--12 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 8.4 System Controls Screen Select CONTROLS from the Main menu screen or use the SYSTEM CONTROL pushbutton on the right side of the control panel to display the System Controls screen. Normal operation, transfer...
Page 112 - CHARGER; from the System Controls screen to display the Charger; CHARGER CONTROLS
8--14 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 8.4.1 Charger Controls Screen Select CHARGER from the System Controls screen to display the Charger Controls screen. Use the controls on this screen to turn the battery charger on and off. Figure 8 --- 18 shows...
Page 113 - Unit Shutdown Screen; “UPS Operating Instructions”.; UNIT SHUTDOWN
8--15 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 8.5 Unit Shutdown Screen The Unit Shutdown screen appears when the LOAD OFF pushbutton is pressed. This screen allows the LOAD OFF process to be aborted if the LOAD OFF pushbutton was pressed accidentally. Figu...
Page 114 - Reading the Status Indicators; The five symbols on the left side of the control panel are; section of Chapter 11.
8--16 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 8.6 Reading the Status Indicators The five symbols on the left side of the control panel are status indicators . They are backlit by colored light emitting diode (LED) lamps, and they work in conjunction with t...
Page 115 - UPS Operating Instructions; Operation; installation was successful and the UPS operates properly.; Starting the UPS in Normal Mode; OPEN
9--1 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 UPS Operating Instructions 9.1 Operation The following procedures provide instructions for operating the UPS system. Refer to Chapters 7 and 8 of this manual for a description of the UPS controls and control pan...
Page 116 - Starting the UPS in Bypass Mode
9--2 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 12. Observe the following messages appear sequentially on the PPU status line: WAITING FOR INPUT DC STARTING INVERTER STARTING SYNCING ONLINE The rectifier and inverter turn on. When the inverter reaches full vo...
Page 117 - Starting the Power Processing Unit
9--3 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 9.4 Starting the Power Processing Unit To start the Power Processing Unit (PPU) without transferring the critical load to normal, perform the following procedure: 1. Ensure the UPS circuit breakers and switches ...
Page 118 - Cold Starting the UPS; set circuit breakers as instructed in steps 2 through 5.
9--4 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 9.5 Cold Starting the UPS To start the UPS system when commercial power is not available, perform the following procedure: NOTE: Output to the load will be limited to the available energy in the battery supply w...
Page 119 - BATTERY; Transfer from Normal to Bypass Mode; BYPASS
9--5 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 13. Observe the following messages appear sequentially on the PPU status line: WAITING FOR INPUT DC STARTING INVERTER STARTING SYNCING ONLINE The inverter turns on. When the inverter reaches full voltage, UPS ou...
Page 120 - Transfer from Bypass to Normal Mode; Transfer from Normal to High Efficiency Mode; Transfer from High Efficiency to Normal Mode; Customer Service Engineer.
9--6 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 9.7 Transfer from Bypass to Normal Mode To transfer the critical load to normal mode, perform the following procedure: 1. Press the System Control pushbutton. The System Control screen appears. 2. Select NORMAL ...
Page 121 - UPS and Critical Load Shutdown; UPS Maintenance Bypass Transfer
9--7 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 9.10 Transfer from Normal to Bypass Mode with UPS Shutdown 1. Transfer critical load to bypass by performing procedure in paragraph 9.6. 2. Press the System Control pushbutton. The System Control screen appears....
Page 122 - Options Cabinet Maintenance Bypass Transfer; Using the Power Distribution Module
9--8 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 9.13 Options Cabinet Maintenance Bypass Transfer To transfer the critical load to Maintenance Bypass, perform the following procedure: 1. Transfer critical load to bypass by performing procedure in paragraph 9.6...
Page 123 - An UPS Emergency Power Off is initiated by; Remote Emergency Power OFF; Press the REPO pushbutton switch.
9--9 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 9.16 Using the REMOTE EMERGENCY POWER OFF Switch An UPS Emergency Power Off is initiated by Remote Emergency Power OFF (REPO) pushbutton switch . In an emergency, you can use this switch to control the UPS outpu...
Page 125 - Using Features; You should use twisted pair wires for each alarm input and common.; General Purpose Relay Contacts; alarm horn may not be heard immediately.
10--1 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Using Features 10.1 General The many standard features of your UPS system provide consistent, economical, and dependable power protection. In addition, you can add available options to enhance the performance o...
Page 126 - Optional Remote Monitor Panel
10--2 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 10.4 Optional Remote Monitor Panel As an option, you can install a Remote Monitor Panel (RMP) to monitor the operation of the UPS system from virtually any location within your facility, up to 500 feet from the...
Page 129 - Responding to System Events; Events; System Event Horns
11--1 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Responding to System Events 11.1 General When the UPS system is running in Normal mode, it continually monitors itself and the incoming utility power. In Battery or Bypass modes, the UPS may issue alarms to let...
Page 130 - System Event Messages
11--2 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 11.4 System Event Messages When a system event occurs, a message appears on the LCD screen in the UPS Status area. This message is also is written to the Active Events log and may be added to the Events History...
Page 139 - Communications; information about connecting hardware, and using terminal mode.; Communications and Expansion Ports; customer communications options (refer to Chapter 7; Refer to Appendix A for location of; Connecting Equipment to a Serial Port
12--1 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Communications 12.1 Description This chapter describes the serial communications feature of the Powerware 9330 10 kVA --- 20 kVA and 25 kVA --- 40 kVA UPS. One serial communications port on the UPS allows you...
Page 140 - Configuring the Serial Ports
12--2 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 3 2 1 5 4 7 6 9 8 TXD RXD DSR RETURN DTR CTS RTS NOT USED SERIAL PORT (DB-- 9) NOT USED Figure 12 --- 1. Serial Port Pin Assignments Table 12 --- 1. Pin Assignments for Serial Port (DB --- 9) Pin # Symbol Descr...
Page 141 - In Terminal Mode, the user can request the following:
12--3 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 12.5 Terminal Mode In Terminal Mode, the user can request the following: NOTE: The brackets ([ ]) in the following bullets indicate standard keyboard characters. To use a key combination, hold down the Escape k...
Page 150 - Terminal mode uses this format for printing alarm entries:; use key combinations at any time to print selected information:
12--12 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 12.5.2 Event History Log This key sequence prints the entire Event History Log of the UPS at the time the data is requested. The printout begins with the oldest alarm entry in the queue and ends with the most ...
Page 154 - Remote Notification Features; option are as follows:
13--2 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 13.2 Remote Notification Features Remote Notification provides the UPS with the capability to utilize a standard off-the-shelf PC modem as a telephone interface. The features provided by this option are as foll...
Page 155 - Description of Operation; from a remote computer or terminal.
13--3 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 13.3 Description of Operation The Remote Notification option performs three basic functions: Call Answer into Terminal mode, Call Out to a remote terminal, and Housekeeping. Remote Notification also allows acce...
Page 157 - Hardware Requirements; Notification function.
13--5 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 13.4 Hardware Requirements The following hardware components are required to connect the Remote Notification function. · Modem: Basic external PC modem supporting the following AT commands.T --- Tone dialing. &...
Page 158 - Configuring the Modem; sections of this chapter.; Configuring the Modem to Call a Remote Computer; In steps 4 through 7, the “xxxxxxx” is the phone number of a remote
13--6 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 13.5 Configuring the Modem The modem must be programmed with the Call Out telephone numbers in order to operate the Remote Notification option.To configure the modem, connect the serial port of a standard PC co...
Page 159 - Modem to Call a Numeric Pager” section of this chapter.; Configuring the Modem to Call a Numeric Pager; prevents the pager service from picking up on the modem hang-up
13--7 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 7. To program a group four number, key in [A], [T], [&], [Z], [3], [=], [xxxxxxx], then press [ENTER]. 8. Confirm that the modem responds with “OK” or “0” (zero). 9. Connect a telephone line to the modem an...
Page 160 - To set up group one through four numbers to call a computer, refer to; UPS Setup Configuration; The modem should be connected to the UPS as described in the modem
13--8 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 7. To program a group four number, key in [A], [T], [&], [Z], [3], [=], [xxxxxxx], [,], [,], [,], [yyyyyyy], [#], then press [ENTER]. 8. Confirm that the modem responds with “OK” or “0” (zero). 9. Connect a...
Page 163 - Maintaining the UPS System; Remember that your UPS system is designed to supply power; DO NOT; If
14--1 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Maintaining the UPS System 14.1 General The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, with very little disassembly....
Page 165 - Performing Preventive Maintenance; Perform the following checks DAILY:
14--3 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 14.3 Performing Preventive Maintenance The UPS system requires very little preventive maintenance. However, the system should be inspected periodically to verify that the units are operating normally and that t...
Page 166 - Maintenance Training; Carolina, or call Powerware corporation field service at
14--4 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 14.4 Maintenance Training A basic training course, available from Powerware Inc., gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective mainte...
Page 167 - Product Specifications; Model Numbers; UPS System Input
15--1 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Product Specifications 15.1 Model Numbers The UPS systems are housed in freestanding, cabinets with safety shields behind the front panels. The UPS systems are available in 50/60 Hz with various output power ra...
Page 168 - UPS System Output
15--2 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 15.3 UPS System Output DC Filtering Ripple voltage less than 0.5% peak to peak UPS Output Capacity 100% rated current at 0.7 power factor Output Voltage Regulation 1% (10% to 100% load) Output Voltage Adjustmen...
Page 169 - Environmental Specifications
15--3 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 15.4 Environmental Specifications Operating Temperature 0 to 40 ˚ C without derating. The recommended operating temperature is 25 ˚ C. Operating Altitude Maximum 1500m (5000 ft) at 40 _ C without derating Stora...
Page 180 - Terminals are UL and CSA rated at 90
DESCRIPTION: DATE: DRAWING NO: 9 of 17 SHEET: REVISION: F 111501 NOTE: Customer ground, size 1/0, can be run in any conduit listed in Table R. POWER WIRING INSTALLATION NOTES 164201300 --- 1 A --- 10 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 9. Terminals are...
Page 184 - Table S. Power Cable Conduit Requirements Powerware 9330 (20 kVA)
DESCRIPTION: DATE: DRAWING NO: 13 of 17 SHEET: REVISION: F 111501 POWER WIRING INSTALLATION NOTES 164201300 --- 1 A --- 14 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Table S. Power Cable Conduit Requirements Powerware 9330 (20 kVA) Powerware System Voltage Te...
Page 187 - required, it is to be supplied by designated personnel.; Table V. Maximum Input Circuit Breaker Ratings; DC
DESCRIPTION: DATE: DRAWING NO: 16 of 17 SHEET: REVISION: F 111501 164201300 --- 1 POWER WIRING INSTALLATION NOTES A --- 17 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 13. External overcurrent protection is not provided by this product, but is required by codes...
Page 188 - Table W. Maximum Output Circuit Breaker Ratings; Rated battery current is computed at the computed voltage.
DESCRIPTION: DATE: DRAWING NO: 17 of 17 SHEET: REVISION: D 053001 164201300 --- 1 POWER WIRING INSTALLATION NOTES A --- 18 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 16. Output overcurrent protection and output disconnect switch are to be provided by the user...
Page 189 - Table X. Customer Interface Inputs and Outputs
DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: G 1 of 5 051502 CUSTOMER INTERFACE WIRING INSTALLATION NOTES 164201300 --- 2 A --- 19 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 1. Use Class 1 wiring methods (as defined by the NEC) for control wiring. Install ...
Page 190 - CSB CUSTOMER INTERFACE
DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: G 2 of 5 061502 CUSTOMER INTERFACE WIRING INSTALLATION NOTES CSB CUSTOMER INTERFACE RELAY #2 NC RELAY #2 RETURNRELAY #2 NO RELAY #1 NC RELAY #1 RETURNRELAY #1 NO BUILDING ALARM #1 RETURN BUILDING ALARM #1 BUILDING ALARM #2 RETURN BUILDING ALARM #2 BUIL...
Page 192 - Table Y. Summary Alarm Relay Contacts; RELAY 1
DESCRIPTION: DATE: DRAWING NO: 4 of 5 SHEET: REVISION: G 051502 CUSTOMER INTERFACE WIRING INSTALLATION NOTES 164201300 --- 2 A --- 22 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 Table Y. Summary Alarm Relay Contacts 2 1 3 2 1 3 RELAY 1 RELAY 2 CONTACT RATING: ...
Page 193 - upstream protective devices to the UPS.; Table Z Remote EPO; Remote EPO switch rating is 24 VDC, 1 Amp minimum.
DESCRIPTION: DATE: DRAWING NO: 5 of 5 SHEET: REVISION: G 051502 CUSTOMER INTERFACE WIRING INSTALLATION NOTES 164201300 --- 2 A --- 23 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 3. The Remote EPO feature opens all breakers and contactors in the UPS cabinet and...
Page 194 - shown in Table AA, according to your UPS system configuration.
DESCRIPTION: DATE: DRAWING NO: 1 of 2 SHEET: REVISION: G 061502 PHYSICAL FEATURES AND REQUIREMENTS 164201300 --- 3 A --- 24 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 1. The UPS equipment operating environment must meet the size and weight requirements shown ...
Page 195 - Ambient Temperature Range:; The UPS ventilation requirements are shown in Table AC.; Table AC. Air Conditioning or Ventilation Requirements
DESCRIPTION: DATE: DRAWING NO: 2 of 2 SHEET: REVISION: G 061502 PHYSICAL FEATURES AND REQUIREMENTS 164201300 --- 3 A --- 25 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 6. The basic environmental requirements for operation of the UPS system are: Ambient Tempera...
Page 198 - Table AD. UPS System Configurations Oneline
DESCRIPTION: DATE: DRAWING NO: 1 of 2 UPS SYSTEM CONFIGURATIONS SHEET: REVISION: F 164201300 --- 5 111501 NOTE 2: Output Voltage must match Bypass Input Voltage. NOTE 1: A bypass neutral feeder must be supplied. A --- 28 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 06...
Page 200 - UPS SYSTEM WITH 208V INPUT AND OUTPUT, SINGLE OR DUAL FEED
A --- 30 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: G ONELINE DRAWINGS OF UPS SYSTEM 1 of 1 031502 UPS CABINET INVERTER RECTIFIER CB1 STATIC SWITCH BACKFEED CONTACTOR (K5) RS --- 232 REMOTE EPO BUILDING ALARMS C...
Page 201 - UPS SYSTEM OPTIONS CABINET CONFIGURATIONS
A --- 31 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: F OPTIONS CABINET SCHEMATICS 1 of 10 111501 UPS SYSTEM OPTIONS CABINET CONFIGURATIONS POWERWARE 9330 (10 kVA --- 20 kVA) B A C A B DISTRIBUTION GND GND GND 42 ...
Page 211 - UPS CABINET POWER TERMINALS
A --- 41 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: F 1 of 5 111501 164201300 --- 8 UPS CABINET POWER TERMINALS LOCATION OF UPS CABINET TERMINALS FRONT VIEW NOTE : METAL SHIELD COVERING POWER WIRING TERMINALS AN...
Page 212 - FRONT VIEW DETAIL
A --- 42 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: F 2 of 5 111501 UPS CABINET POWER TERMINALS LOCATION OF UPS CABINET TERMINALS FRONT VIEW DETAIL INPUT BREAKER CB1 AC INPUT TO UPS RECTIFIER (CB1) (DUAL INPUT) ...
Page 213 - LEFT VIEW
A --- 43 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: F 3 of 5 111501 UPS CABINET POWER TERMINALS LOCATION OF UPS CABINET TERMINALS LEFT VIEW INPUT BREAKER CB1 AC INPUT TO UPS RECTIFIER AND BYPASS (TB2) (SINGLE IN...
Page 214 - UPS CABINET CUSTOMER INTERFACE TERMINALS
A --- 44 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: F 4 of 5 111501 LOCATION OF UPS CABINET TERMINALS 164201300 --- 8 UPS CABINET CUSTOMER INTERFACE TERMINALS X --- SLOT DEVICE INTERFACE PANELS BOTTOM ENTRY COND...
Page 215 - TOP VIEW
A --- 45 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: F 5 of 5 111501 LOCATION OF UPS CABINET TERMINALS 164201300 --- 8 UPS CABINET CUSTOMER INTERFACE TERMINALS X --- SLOT DEVICES X4 X3 X2 X1 COMMUNICATIONS SERVER...
Page 222 - OPTIONS CABINET POWER TERMINALS
A --- 52 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: D LOCATION OF OPTIONS CABINET TERMINALS 1 of 4 053001 OPTIONS CABINET POWER TERMINALS GROUND TERMINALS OPTIONAL 42 CIRCUIT DISTRIBUTION PANEL MAINTENANCE BYPAS...
Page 230 - BATTERY CABINET TERMINALS
A --- 60 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: F LOCATION OF BATTERY CABINET TERMINALS 1 of 1 111501 BATTERY CABINET TERMINALS BATTERY BREAKER EXTERNAL BATTERY CABINET POWER CONNECTOR FOR ADDITIONAL BATTERY...
Page 237 - OPTIONS CABINET
A --- 67 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: D 1 of 2 053001 OPTIONS CABINET DIMENSIONS OPTIONS CABINET Dimensions are in millimeters and [inches] POWERWARE 9330 (10 kVA -- 20 kVA) 164201300 --- 15
Page 241 - BATTERY CABINET
A --- 71 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: D 1 of 1 053001 BATTERY CABINET DIMENSIONS BATTERY CABINET Dimensions are in millimeters and [inches] POWERWARE 9330 (10 kVA -- 20 kVA) 164201300 --- 17 POWERW...
Page 245 - LIMITED FACTORY WARRANTY FOR THREE-PHASE POWERWARE PRODUCTS; to the conditions herein, Powerware Corporation (Powerware
W--1 Powerware 9330 (10 kVA-- 40 kVA) Installation and Operation 164201300 REV. G 061502 LIMITED FACTORY WARRANTY FOR THREE-PHASE POWERWARE PRODUCTS This Warranty applies only to units installed in the Fifty (50) United States of America. Subject to the conditions herein, Powerware Corporation (Powe...