Table of Contents:

  • Page 4 – Wiring for Low-Current Applications
  • Page 6 – Digital Output Circuit; Caution; not; Protection for Inductive Loads
  • Page 7 – Status Indicators; and; Isolation and Safety Guidelines; Read the following information before
  • Page 8 – double insulation; Never
  • Page 9 – Safety Guidelines for Hazardous Locations
  • Page 10 – Special Conditions for Hazardous Locations Use in Europe; Specifications; Output Characteristics; POWER
  • Page 11 – Power Requirements; Environmental
  • Page 12 – Safety; Electromagnetic Compatibility; Note; Environmental Management; NI and the
  • Page 13 – Waste Electrical and Electronic Equipment (WEEE); EU Customers; At the end of their life cycle, all products; Mechanical Dimensions; ⬉ᄤֵᙃѻક∵ᵻ᥻ࠊᄣ⧚ࡲ⊩ ˄Ё೑; RoHS; National Instruments; about China RoHS compliance, go to
  • Page 14 – Where to Go for Support
Loading the manual

FIELDPOINT

OPERATING INSTRUCTIONS

AND SPECIFICATIONS

FP-DO-403 and cFP-DO-403

16-Channel, 5 to 30 V Sinking Digital Output Module

These operating instructions describe how to install and use the
National Instruments FP-DO-403 and cFP-DO-403 digital output
modules, referred to inclusively as the [c]FP-DO-403. For
information about configuring and accessing the [c]FP-DO-403
over a network, refer to the user manual for the FieldPoint network
module you are using.

Features

The [c]FP-DO-403 is a FieldPoint digital output module with the
following features:

16 sinking digital output channels

Outputs that sink 2 A per channel, 16 A

2

per module

Compatible with voltages from 5 to 30 VDC

250 V

rms

CAT II continuous channel-to-ground isolation,

verified by 2,300 V

rms

, 5 s dielectric withstand test

– 40 to 70 °C operation

ON/OFF LED indicators

Hot swappable

Installing the FP-DO-403

The FP-DO-403 mounts on a FieldPoint terminal base (FP-TB-

x

),

which provides operating power to the module. Installing the
FP-DO-403 onto a powered terminal base does not disrupt the
operation of the bank.

To install the FP-DO-403, refer to Figure 1 and complete the
following steps:

1. Slide the terminal base key to either position X, used for any

module, or position 6, used for the FP-DO-403 module.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 4 - Wiring for Low-Current Applications

[c]FP-DO-403 4 ni.com loads on the output channels, up to 2 A per channel. 1 Connect the external power supply to multiple V and V SUP terminals and to multiple C and COM terminals as needed to ensure that the maximum current through any terminal is 2 A or less. Install a 2 A maximum, fast-acting fu...

Page 6 - Digital Output Circuit; Caution; not; Protection for Inductive Loads

[c]FP-DO-403 6 ni.com Digital Output Circuit The [c]FP-DO-403 digital output channels are optically isolated from the rest of the FieldPoint bank. In the ON state, a transistor is turned on between the V OUT terminal and the external supply (the C and COM terminals). In the OFF state, this transisto...

Page 7 - Status Indicators; and; Isolation and Safety Guidelines; Read the following information before

© National Instruments Corp. 7 [c]FP-DO-403 mount the flyback diode within 18 in. of the load. Figure 5 shows a flyback diode connected to an inductive load. Figure 5. Connection to Inductive Load with Flyback Diode Although the [c]FP-DO-403 contains flyback diodes to prevent excessively high voltag...