Table of Contents:

  • Page 2 – INTRODUCTION & SYSTEM DESCRIPTION
  • Page 3 – MAJOR COMPONENTS; TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS; MINI-TOWER INSTALLATION
  • Page 4 – RACKMOUNT INSTALLATION
  • Page 5 – CONTROLS AND INDICATORS; Alarm Silence/Battery Test Button
  • Page 7 – OPERATION; NORMAL MODE OPERATION
  • Page 8 – COMMUNICATIONS INTERFACE PORT; PIN; UPS MONITORING; Collector to Emitter*
  • Page 9 – MINI-TOWER BATTERY REPLACEMENT
  • Page 10 – RACKMOUNT BATTERY REPLACEMENT
  • Page 12 – AUDIBLE ALARM CONDITIONS; CONDITION; FUSE REPLACEMENT PROCEDURES; MODELS
  • Page 14 – Technical Support; PowerSureTM Interactive
Loading the manual

P

OWER

P

ROTECTION

IMPORTANT SAFETY INSTRUCTIONS

WARNING: Do not attempt to service this product yourself except to
replace the battery. Opening or removing the cover may expose you to

dangerous voltages, even when the AC cord is disconnected from the
electrical outlet. Refer all servicing to qualified service personnel.


1.

SAVE THESE INSTRUCTIONS. THIS MANUAL CONTAINS
IMPORTANT SAFETY INSTRUCTIONS.

Read all safety and operating

instructions before operating the Uninterruptible Power System (UPS).
Adhere to all warnings on the unit and in this manual. Follow all
operating and user instructions.

2. This product is designed for Commercial/Industrial use only. It is not

intended for use with life support and other designated “critical” devices.
Maximum load must not exceed that shown on the UPS rating label. If
uncertain, consult your dealer. See Limited Warranty.

3. When replacing the batteries, use the appropriate Liebert-Approved

Replacement Battery Kit. Proper disposal of batteries is required. Refer
to your local laws and regulations for disposal requirements.

4. Always turn off the UPS and unplug it before starting the battery

replacement procedure. To replace batteries, refer to the battery
replacement procedure. If you feel unqualified to replace the batteries,
do not open the battery door. Refer all servicing to qualified service
personnel.

5.

CAUTION:

Do not open or mutilate the batteries. Released electrolyte is

harmful to skin and eyes and may be toxic.

6. The mains supply socket or means of isolation must be within 2 metres

of the equipment and accessible to the operator. The UPS is designed
for data processing equipment.

7. The UPS comes with two output power leads with moulded connectors.

Do not modify the output power leads. Consult dealer if connector does
not match the load socket. UPS must be earthed at all times while in
use. Turn UPS off before unplugging it, or the safety earth will be
removed.

8. The PowerSure Interactive models 700 VA, 1000 VA, and 1400 VA are

not supplied with an input power lead for connection to the mains supply
socket. Use the input mains supply power lead from your data
processing equipment to connect the UPS to the mains supply. For the
2200 VA model, use the supplied 16 ampere rated input mains supply
leads. For UK supply systems, consult a qualified electrician to connect
the lead supplied for the 2200 VA model to the mains supply. Note
caution on following page.

U

SER

M

ANUAL

English

700-2200 VA

230 V

PowerSure™ Interactive

R

2

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - INTRODUCTION & SYSTEM DESCRIPTION

CAUTION: The UPS and connected load total earth leakage current must not exceed 3.5 milliamperes. If the connected load earth leakage current is likely to exceed 2.5 milliamperes or you are unsure, then convert the input lead attachment to either a fixed wiring installation or an industrial plug/soc...

Page 3 - MAJOR COMPONENTS; TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS; MINI-TOWER INSTALLATION

MAJOR COMPONENTS TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS These UPS components provide surge protection and filter electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the mains line and keep the sensitiv...

Page 4 - RACKMOUNT INSTALLATION

The wires in the mains lead are colored with the following code: Green and Yellow = Earth Blue = Neutral Brown = Live As the color of the wires in the mains lead may not correspond with the colored marking identifying the terminals in the plug, proceed as follows: The green and yellow wire must be c...