Liebert 50 & 60Hz - Manual

Liebert 50 & 60Hz

Liebert 50 & 60Hz – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
17 Page 17
18 Page 18
19 Page 19
20 Page 20
21 Page 21
22 Page 22
23 Page 23
24 Page 24
25 Page 25
26 Page 26
27 Page 27
28 Page 28
29 Page 29
30 Page 30
31 Page 31
32 Page 32
33 Page 33
34 Page 34
35 Page 35
36 Page 36
37 Page 37
38 Page 38
39 Page 39
40 Page 40
41 Page 41
42 Page 42
43 Page 43
44 Page 44
45 Page 45
46 Page 46
47 Page 47
48 Page 48
49 Page 49
50 Page 50
51 Page 51
52 Page 52
53 Page 53
54 Page 54
55 Page 55
56 Page 56
57 Page 57
58 Page 58
59 Page 59
60 Page 60
61 Page 61
62 Page 62
63 Page 63
64 Page 64
65 Page 65
66 Page 66
67 Page 67
68 Page 68
69 Page 69
70 Page 70
71 Page 71
72 Page 72
Page: / 72

Table of Contents:

  • Page 3 – TABLE OF CONTENTS
  • Page 4 – ii
  • Page 5 – iii
  • Page 6 – iv; FIGURES
  • Page 7 – Mini-Mate2 Indoor Condensing Unit; Table iii; Table iv; Chilled Water Unit
  • Page 9 – Product Features; RODUCT; Standard Product Features; Unit. A self-contained Chilled Water Fan Coil is also available.; Section 3; DX Evaporator Section; Temp head pressure control with receivers.
  • Page 10 – Optional Equipment; source of chilled-water may be piped to this coil.
  • Page 11 – Refrigerant Line Sweat Adapter Kits; using field supplied interconnecting refrigerant piping.; Return Air Filter Box with Duct Collar Kit; for ducting the evaporator air.
  • Page 12 – Site Preparation and Installation; ITE; Installation Considerations; Figure 1; for possible configurations. The condensing unit may be:; Outdoor Prop Fan Condensing Unit; Table 3; NOTE; conditioned room is the vapor barrier.
  • Page 13 – could interfere with maintenance or service.; CAUTION
  • Page 15 – Figure 3; System Weights; it to the shipper and to your Liebert supplier.; Table 4
  • Page 16 – Installing the Evaporator or Chilled-Water Units; See Figure 4; compressed more than the other side.; Figure 4; WARNING; accessories during installation and service. (See; The units must be level in order to drain condensate properly.
  • Page 17 – before connecting them together (See; ). If Single Point Power Kit is used, install the box into the; ments; . Remove “P” clamps from piping to aid fitting alignment.; Figure 5
  • Page 18 – Filter Box
  • Page 19 – Piping Connections and Coolant Requirements; Figure 6
  • Page 20 – Condensate Pump; Figure 7; Humidifier Water Supply Line
  • Page 21 – Chilled-Water Piping—Chilled-water Systems Only; Refer to; Figure 8
  • Page 22 – Figure 9
  • Page 23 – Refrigerant Charge Requirements:; Total refrigerant charge (R-22) will be required only if units; Piping Connections and Coolant Requirements; Total refrigerant = Units and Lines; bodies “bottom out” or until a definite resistance is felt.; for torque requirements.; Table 7; connecting quick connects.; Table 9
  • Page 24 – Figure 10 Evaporator or chilled-water unit dimensional data; FRONT
  • Page 25 – Power Connections; Do not connect additional electri-
  • Page 26 – Figure 11 Evaporator unit electrical connections; FRONT OF UNIT
  • Page 27 – Indoor Air-Cooled Centrifugal Fan Condensing Unit Installation; for hanging guidelines and to; General Considerations; directed toward the air inlet of an adjacent unit.; Considerations for Specific Applications; the discharge; If the condensing unit draws air from the outside of the building,; rain hoods must be
  • Page 28 – late the unit for maintenance.; Control Connections; Refer to serial tag for full load amp and wire size amp ratings
  • Page 30 – Low Voltage; Heat rejection connection
  • Page 31 – Outdoor Air-Cooled Condensing Unit Installation; cooled centrifugal fan condensing unit
  • Page 32 – Figure 15 Electrical field connections - outdoor condensing unit
  • Page 33 – Figure 16 Footprint dimensions - outdoor condensing unit; Model; FOOTPRINT DIMENSIONS
  • Page 34 – Model Numbers
  • Page 35 – Indoor Water- and Glycol-Cooled Condensing Unit Installation; Requirements; Water/Glycol Piping Considerations; Glycol-cooled units also; Automotive antifreeze must not be used.
  • Page 36 – Figure 18 Indoor water/glycol condensing unit dimensional data
  • Page 38 – Two circuits provided. Single circuit shown.
  • Page 39 – Optional Equipment Piping
  • Page 41 – Checklist for Completed Installation
  • Page 42 – Microprocessor Control; ICROPROCESSOR; - System Performance Microprocessor Controls; Feature Overview; ENTER
  • Page 43 – Press the; MENU; Use the
  • Page 44 – Setpoints; Default setpoints and allowable ranges; Setpoint
  • Page 45 – Time; Night and weekend setback plan; Event
  • Page 46 – to select this function, then use the; key to select the desired humidity control method.
  • Page 47 – any contaminates which may have collected in the system.; Change Passwords; Each alarm can be disabled or enabled. Use the; Setup functions, default values and allowable ranges; Function; The high-water alarm will automatically shut the unit off.
  • Page 48 – Alarm Time Delay; YES; For software alarms such as “loss of power” and “short cycle,” the time; Alarm default time delays; Alarm
  • Page 49 – LCD Display Contrast
  • Page 50 – Test Outputs; onds on to prevent damage.; Test Inputs; Fan turned on with all loads.
  • Page 51 – Test Micro; firmware revision number.; Figure 24 Control menu
  • Page 52 – Figure 25 Control board (inside evaporator); P16 Remote Sensor Connection
  • Page 53 – System Performance Microprocessor Controls; YSTEM; Control Type Response Proportional Control; the “Setup Operation” menu.; Reheat
  • Page 54 – Dehumidification / Humidification Percent Required; relative and absolute. Relative humidity control is the default.; System Activation; tion, and is deactivated when the requirement falls below 50%.; Load Control Features
  • Page 55 – Alarms; LARMS; depending upon the model.; Alarms: Definitions and Troubleshooting; to
  • Page 56 – from outdoor humidity? Are doors or windows open to outside air?
  • Page 57 – Optional/Custom Alarms
  • Page 58 – System Operation, Testing, and Maintenance; Maintenance Inspection Checklist; to record preventive maintenance inspections.; System Testing; of the main functions.
  • Page 59 – Maintenance and Component Operation; Air Distribution; disconnecting all power and control wiring entering the panel.; Protect refrigerant and water piping from damage.
  • Page 60 – meet specific application requirements.; Suction Pressure; sure switch will shut the compressor down at its cut-out setting.; Thermostatic Expansion Valve; fouled and should be replaced.; Typical discharge pressures; System Design; Maximum
  • Page 61 – Glycol Solution Maintenance; ucts from different manufacturers.; Operation; ized and superheat is not adjustable.; Adjustment; is within the range desired.
  • Page 62 – Replacement Procedures; Compressor Replacement:; for discharge; long rubber gloves in handling contaminated parts.
  • Page 63 – and goes to normal operation. No drain is permitted until then.
  • Page 64 – Replacing the Humidifier Canister; Record the original setpoint.; Humidifier control board DIP switch settings; Voltage
  • Page 65 – AINTENANCE
  • Page 66 – ROUBLESHOOTING; Troubleshooting
  • Page 68 – NOTES
  • Page 72 – Precision Cooling
Loading the manual

Precision Cooling
For

Business-Critical Continuity™

Liebert Mini-Mate2

User Manual - 8 Tons, 50 & 60Hz

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 3 - TABLE OF CONTENTS

i TABLE OF CONTENTS M ODEL N UMBER N OMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V 1.0 P RODUCT F EATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 Standard Product...

Page 4 - ii

ii 2.7 Indoor Water- and Glycol-Cooled Condensing Unit Installation . . . . . . . . . . . . . . . . . . . . . . 27 2.7.1 Location Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 2.7.2 Piping Connections . . . . . . . . ....

Page 5 - iii

iii 4.3 Reheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 4.3.1 Electric Reheat - Staged . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 4....

Other Liebert Models

All Liebert Other