Page 2 - Installation and Servicing; ERP DATA
2 Installation and Servicing ERP DATA MODEL SYMBOL UNITS 24 30 35 Condensing Boiler n/a n/a yes yes yes Low Temperature Boiler n/a n/a no no no B1 Boiler n/a n/a no no no Cogeneration Space Heater n/a n/a no no no Equipped with a Supplementary Heater n/a n/a no no no Combination Heater n/a n/a y...
Page 3 - Seasonal Space heating efficiency class; Water heating energy efficiency class; Seasonal Space Heating Energy Efficiency of the Boiler; PRODUCT FICHE; Solar Contribution (from fiche of solar device); III
3 Installation and Servicing ATLANTIC COMBI COMBINATION BOILER Ideal Heating ERP DATA SYMBOL UNITS MODEL 24 30 35 Condensing boiler Yes Seasonal Space heating efficiency class A Rated heat output kW 24 Seasonal space heating energy efficiency ƞ s % 94* Annual energy consumption Q HE GJ 75 Sound powe...
Page 5 - DOCUMENT AMENDMENTS; Section 1.18 Water Treatment; Addititonal information added regarding use of water softeners; FOR ANY TECHNICAL QUERIES PLEASE RING THE
5 Installation and Servicing DOCUMENT AMENDMENTS Relevant Installation changes implemented in this book from Mod Level ...... A04 (Sep 21) to A05 (June 22) Section 1.18 Water Treatment Addititonal information added regarding use of water softeners Ideal Heating reserve the right to vary specificatio...
Page 7 - CONTENTS; Determining The Flue Length
7 Installation and Servicing CONTENTS 1 GENERAL .................................................................. 10 1.1 Introduction ................................................................ 10 1.2 Operation ................................................................... 10 1.3 Safe Han...
Page 8 - Gas consumption is calculated using a
8 Installation and Servicing SECTION 1 - GENERAL Note. Gas consumption is calculated using a calorific value of 38.7 MJ/m 3 (1038 Btu/ft 3 ) gross or 34.9 MJ/m 3 (935 Btu/ft 3 ) nett To obtain the gas consumption at a different calorific value: a. For l/s - divide the gross heat input (kW) by the gr...
Page 9 - Boiler size; Heating zone valves; Central heating flow temp.; For condensing boilers only; BENCHMARK COMMISSIONING CHECKLIST DETAILS
9 Installation and Servicing SECTION 1 - GENERAL Boiler size G.C. Appliance No. (Benchmark No.) 24 47-349-8130 47-349-8235 47-349-83 Natural Gas only Destination Country: GB, IE B oiler Page Make and model ......................................................... 9 Appliance serial no. on data badge...
Page 10 - GENERAL; Due to the high efficiency of the boiler a plume of water; OPTIONAL EXTRA KITS
10 Installation and Servicing SECTION 1 - GENERAL 1 GENERAL 1.1 INTRODUCTION The Atlantic combi range of boilers are wall mounted, full sequence, automatic spark ignition, low water content, fanned flue, high efficiency, condensing, combination gas boilers. Note. Due to the high efficiency of the bo...
Page 11 - Current Gas Safety (installation and use) regulations or rules; SAFE HANDLING OF SUBSTANCES; he boiler must not be fitted outside.; Timber Framed Buildings; Recessed
11 Installation and Servicing SECTION 1 - GENERAL 1.5 SAFETY Current Gas Safety (installation and use) regulations or rules in force: The appliance is suitable only for installation in GB and IE and should be installed in accordance with the rules in force.In GB, the installation must be carried out...
Page 12 - Gas Cock Pressure Drop; FLUE INSTALLATION; IMPORTANT; Flue Terminal Positions; Vertical Terminals; Table 4 - Balanced Flue Terminal Position
12 Installation and Servicing SECTION 1 - GENERAL 1.8 GAS SUPPLY The local gas supplier should be consulted, at the installation planning stage, in order to establish the availability of an adequate supply of gas. An existing service pipe must NOT be used without prior consultation with the local ga...
Page 13 - WATER CIRCULATION SYSTEM; no
13 Installation and Servicing SECTION 1 - GENERAL 1.10 AIR SUPPLY It is NOT necessary to have a purpose-provided air vent in the room or internal space in which the boiler is installed. Neither is it necessary to ventilate a cupboard or compartment in which the boiler is installed, due to the low su...
Page 14 - The following minimum clearances must be maintained; Provided that the flue hole is cut accurately, e.g. with a core; Installation from inside ONLY
14 Installation and Servicing SECTION 1 - GENERAL 395 2.5 2.5 from case 700 Side flue dim. A 285 155 DA TA PLA TE CH FLOW DHW OUTLET COND. DRAIN GAS INLET DHW INLET CH RETURN PRV Underside View - Dimensions to Wall 43.5 65 28.5 28.5 60.5 75 39.5 54.5 99 99 34 103 103 103 WALL 1.15 BOILER DIMENSIONS,...
Page 15 - or; SYSTEM REQUIREMENTS - Central Heating
15 Installation and Servicing SECTION 1 - GENERAL General1. The installation must comply with all relevant national and local regulations. 2. The installation should be designed to work with flow temperatures of up to 84 o C. 3. All components of the system must be suitable for a working pressure of...
Page 16 - BALANCING; The application of any other treatment to this; DOMESTIC HOT WATER; Ideal Heating; Domestic Hot Water; Cold water, rising main and pipework in exposed areas; SYSTEM BALANCING
16 Installation and Servicing SECTION 1 - GENERAL The boiler does not normally need a bypass but at least some radiators on the heating circuit, of load of at least 10% of the minimum boiler output, must be provided with twin lockshield valves so that this minimum heating load is always available. S...
Page 17 - SECTION 2 - INSTALLATION; INSTALLATION; xploded; Note; that item numbers are linked to the spares list; INST
17 Installation and Servicing SECTION 2 - INSTALLATION 2 INSTALLATION 2.1 BOILER ASSEMBLY - E xploded V iew Note that item numbers are linked to the spares list 104 CH RETURN VALVE 105 CH FLOW VALVE 106 DHW INLET & OUTLET 108 PUMP HEAD 110 AIR VENT PUMP 111 DIVERTOR VALVE MOTOR 112 DIVERTOR VALV...
Page 18 - HARDWARE PACK CONTENTS; Pack B is suppled as a separate order.; Unpack and check the contents.; (located on internal protective packaging); Remove outer sleeve
18 Installation and Servicing SECTION 2 - INSTALLATION HARDWARE PACK CONTENTS Gas Valve Pack 1. Gas Cock 2. Valve - DHW 3. Valve - Return 4. Valve - Flow 5. Pipe - DHW Outlet 6. Nut - G 1/2" 7. Washer - Gas 8. Washer - DHW 9. Washer - CH 10. Screw 11. Wall Plug 12. Turret Clamp Screw (spare) Fix...
Page 19 - Lift the lower front panel access flap.; Pack B Contents Telescopic; FRONT PANEL REMOVAL
19 Installation and Servicing SECTION 2 - INSTALLATION D C A B C D A E B 2.3 UNPACKING CONT’D 1. Lift the lower front panel access flap. 2. Unscrew the single fixing screw, close the access flap to retain the screws and hinge the lower front panel down into the service position. 3. Remove the two up...
Page 20 - Care MUST be taken to ensure the correct holes are drilled.; WALL MOUNTING TEMPLATE; NOTE
20 Installation and Servicing SECTION 2 - INSTALLATION “A” - See Diagram in Frame 1 Extended centre line 155 (200) 3G9495 X Section through wall Note. Check all of the hole positions before drilling. Side flue only 5" diameter hole Rear flue only 5" diameter hole The wall mounting template i...
Page 21 - INSTALLATION; FLUE OUTLET; DETERMINING THE FLUE LENGTH AND FLUE PACKS REQUIRED; telescopic flue incorporating a terminal, rubber wall seals and; Total Maximum Permissible Vertical Flue Length
21 INSTALLATION Installation and Servicing FLUE OUTLET 2.9 DETERMINING THE FLUE LENGTH AND FLUE PACKS REQUIRED IMPORTANT . The boiler must be installed in a vertical position in accordance to the installation instructions. FLUE KITS Telescopic Flue‘B’ Pack - contains: Flue turret, telescopic flue in...
Page 22 - ALL; DETERMINING THE FLUE LENGTH AND FLUE PACKS REQUIRED, CONT’D; Horizontal Flue Terminal; FIGURE 1; Note. Maximum permissible
22 INSTALLATION Installation and Servicing FLUE OUTLET 100mm Edge of turret to outside face of wall plus 44mm = flue length Centre of turret to edge of turret = 100mm Turret has a flue insertion of 30mm The compressed outer wall seal has protruding wall to seal mounting lip - 14mm From centreline of...
Page 23 - only the outer flue; Measure from the outer terminal lip to end of outer flue. Mark the
23 INSTALLATION Installation and Servicing FLUE OUTLET 2.11 CUTTING & SETTING THE FLUE LENGTH CUT 75MM OFF HORIZONTAL FLUE TERMINAL 1000MM LONG B PACK (TELESCOPIC) 1. Measure cut flue length (A+44mm). (If required telescopic length is not between 658 and 708 then proceed to “Setting Telescopic F...
Page 24 - INSTALLING THE FLUE; FITTING FLUE THROUGH THE WALL; small location mark at the dimension acquired at point 1.; FITTING THE TURRET -; Secure clamp to appliance using securing screw.
24 INSTALLATION Installation and Servicing FLUE OUTLET Flue Outlet C A A - Duct Assembly B - Flue Turret C - Turret Clamp D - Seal Flue Outlet D B 2.12 INSTALLING THE FLUE FITTING FLUE THROUGH THE WALL 1. Measure wall thickness and add 14mm. 2. Measure from the outer terminal lip towards the end of ...
Page 25 - with the installation of this kit.; FITTING THE OPTIONAL ROOF FLUE KIT
25 INSTALLATION Installation and Servicing FLUE OUTLET Note. A flat or pitched roof flashing plate (not supplied) is required before proceeding with the installation of this kit. This kit is suitable for both flat and pitched roof terminations, using a concentric flue to run vertically from the top ...
Page 26 - Fixed; FLUE TERMINAL POSITION; min; Flat roof - with structure; The terminal should be positioned so that products of; Pluming may occur at the termination so, where possible,; Minimum dimensions are shown below; Pitched roof - with velux window
26 INSTALLATION Installation and Servicing FLUE OUTLET rf8394- 1 690mm Fixed 300mm min 2.15 FLUE TERMINAL POSITION rf8393- 1 300mm min 300mm min 625mm Fixed Flat roof - with structure The terminal should be positioned so that products of combustion can safely disperse at all times. Pluming may occur...
Page 27 - Extension; ASSEMBLING THE ROOF FLUE KIT; Flue Terminal; ASSEMBLY A
27 INSTALLATION Installation and Servicing FLUE OUTLET Extension Duct Vertical connector 5 4 2 2.16 ASSEMBLING THE ROOF FLUE KIT Determine the correct height that the flue should terminate above the roof. If after calculating or measuring the overall flue height from the top of the boiler, it is nec...
Page 28 - Condensate
28 Installation and Servicing SECTION 2 - INSTALLATION 2.17 CONDENSATE DRAIN 137 47 156 Condensate Drain T his appliance is fitted with a siphonic 75mm condensate trap system that requires filling before operating the appliance for the 1st time or after maintenance.All condensate pipework should con...
Page 30 - WATER CONNECTIONS CH; WATER CONNECTIONS DHW; The DHW flow rate is automatically regulated to a max:
30 Installation and Servicing SECTION 2 - INSTALLATION Safety Drain Valve Black Handle Yellow Handle Black Handle Blue Handle DHW Outlet Gas Supply CH Return DHW Inlet Gas Pressure Test Point 2.18 CONNECTIONS & FILLING NOTES. Ensure all boss blanking plugs are removed before connecting hardware....
Page 31 - Wiring External to the Boiler; thermostat, preferably on the return pipework.; EXTERNAL ELECTRICAL CONNECTIONS; WARNING; L N; Use of General Live for Room Stat; FROST THERMOSTAT - WIRING
31 Installation and Servicing SECTION 2 - INSTALLATION 2.19 ELECTRICAL CONNECTIONS Wiring External to the Boiler The fuse rating should be 3A.Wiring external to the boiler MUST be in accordance with the current I.E.E. (BS.7671) Wiring Regulations and any local regulations. Frost Protection If parts ...
Page 33 - GENERAL; Please Note; DO NOT; - The integrity of the flue system and the flue seals,; INLET PRESSURE; opening hot tap to maximum flow.; open all windows and doors, extinguish naked lights and; IT IS A CONDITION OF THE MANUFACTURERS WARRANTY THAT THE
33 Installation and Servicing SECTION 2 - INSTALLATION 2.23 COMMISSIONING AND TESTING GENERAL Please Note : The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type defined on the appliance data plate. DO NOT adjust the air/gas ratio valve....
Page 34 - THE DISPLAY; CH; Note. The boiler incorporates a fan overrun cycle; MECHANICAL TIMER
34 Installation and Servicing SECTION 2 - INSTALLATION 2.24 INITIAL LIGHTING THE DISPLAY The user control has two LEDs and two 7 segment displays to inform the user about the status. The display will show the status of the boiler. The LED will show the status of the flame. If no flame is detected th...
Page 35 - WATER TEMPERATURES; Fully open all DHW taps in turn and ensure that water flows; Make the following checks for correct operation in:; the flushing process.
35 Installation and Servicing SECTION 2 - INSTALLATION WATER TEMPERATURES Temperatures can be selected using the CH and DHW thermostats. Knob Setting CH Flow Temp DHW Outlet Temp o C o C Max 80 65 Min 30 40 2.25 GENERAL CHECKS DOMESTIC HOT WATER (DHW) MODE 1. Fully open all DHW taps in turn and ensu...
Page 36 - receive the full benefit of the warranty.; “Additionally, the temperature can be controlled by the
36 Installation and Servicing SECTION 2 - INSTALLATION 2.26 RESTART PROCEDURE 2.27 HANDING OVER 8. Loss of system water pressure Explain that the dial underneath the boiler indicates the central heating system pressure and that if the normal COLD pressure of the system is seen to decrease over a per...
Page 37 - SECTION 3 - SERVICING; SERVICING; Always turn; SER
37 Installation and Servicing SECTION 3 - SERVICING 3 SERVICING 3.1 SERVICING F or the very latest copy of literature for specification & maintenance practices, visit our website idealheating.com, where you will be able to download the relevant information. WARNING. Always turn OFF the gas suppl...
Page 38 - REMOVAL; Remove the two upper front panel fixing screws, lift the; REPLACEMENT; Retain the upper panel with the two fixing screws previously; FAN AND VENTURI ASSEMBLY REMOVAL AND CLEANING
38 Installation and Servicing SECTION 3 - SERVICING 3.2 BOILER UPPER & LOWER FRONT PANEL REMOVAL / REPLACEMENT REMOVAL 1. Lift the lower front panel access flap.2. Unscrew the fixing screw, close the access flap to retain the screw and hinge the lower front panel down into the service position. ...
Page 39 - Remove the 2 burner front fixing screws and loosen the 2 rear; Ensure condensate trap is fully drained before removal.; When reassembling ensure the trap is full of water; CLEANING THE CONDENSATE TRAP/SIPHON
39 Installation and Servicing SECTION 3 - SERVICING 3.4 BURNER REMOVAL AND CLEANING 1. Ensure the sump is fully drained 2. Undo the two screws and remove the sump cover retaining the lower flue manifold. 3. Lift the manifold to clear the bottom sealing gasket and remove manifold. 4. Remove the 2 bur...
Page 40 - Ensure the condensate trap/siphon
40 Installation and Servicing SECTION 3 - SERVICING 3.6 CLEANING THE HEAT EXCHANGER Note: Ensure the condensate trap/siphon is fully drained before cleaning. Refer to Section 3.19.1. Remove the ignition/flame detection electrode. Refer to Section 3.12. 2. It is advisable to replace the sump cover pr...
Page 41 - Remove the lower front panel fixing screws, swing the panel; THE BOILER MUST NOT BE OPERATED WITHOUT THE FRONT PANEL FITTED; noting
41 Installation and Servicing SECTION 3 - SERVICING 3.8 REPLACEMENT OF COMPONENTS GENERAL When replacing ANY component 1. Isolate the electricity supply. 2. Turn off the gas supply. 3. Remove the lower front panel fixing screws, swing the panel into the servicing position and remove the upper front ...
Page 42 - Remove the 2 front fixing screws and loosen the 2 rear
42 Installation and Servicing SECTION 3 - SERVICING 4 3.10 BURNER INJECTOR REPLACEMENT 1. Refer to Section 3.8. 2. Disconnect the electrical leads from the fan. 3. Remove the clip from the gas valve to venturi pipe and ease the pipe upwards, rotate and ease down to remove. 4. Loosen the screw retain...
Page 43 - Straight edge; Spark Gap
43 Installation and Servicing SECTION 3 - SERVICING 3.12 IGNITION ELECTRODE / IONISATION DETECTION PROBE REPLACEMENT 1. Refer to Section 3.8. 2. Remove the burner. Refer to Section 3.11. 3. Unplug the ignition lead from the electrode. 4. Remove the earth lead from the ignition electrode/ionisation d...
Page 44 - Undo the single screw fixing the gas; Ensure sealing washer is fully
44 Installation and Servicing SECTION 3 - SERVICING 3.13 SPARK GENERATOR REPLACEMENT 3.14 GAS CONTROL VALVE REPLACEMENT 1. Refer to Section 3.8. 2. Unplug the electrical lead connection from the gas control valve and disconnect the earth wire. 3. Remove the outlet gas valve clip and slide the pipe u...
Page 45 - Ensure condensate trap is fully drained
45 Installation and Servicing SECTION 3 - SERVICING 3.15 DIVERTER VALVE ACTUATOR REPLACEMENT 1. Refer to Section 3.8. Note: Ensure condensate trap is fully drained before removal. 2. Pull off the rubber pipe at the SIPHON. 3. Disconnect the condensate drain pipe. 4. Turn the siphon clockwise to dise...
Page 46 - boiler range and output, but when ordering PCB as a spare; show “n” for Natural Gas, then press restart button.
46 Installation and Servicing SECTION 3 - SERVICING 3.17 MAIN PCB REPLACEMENT * Note. that production boiler PCB’s are factory pre-set to operate for boiler range and output, but when ordering PCB as a spare Note. Fit the earth strap provided with the PCB to your wrist and secure to a suitable earth...
Page 47 - Remove the 4 fixing screws.; REPLACING THE MECHANICAL TIMER; DOMESTIC HOT WATER CIRCUIT
47 Installation and Servicing SECTION 3 - SERVICING 1. Refer to Section 3.8. 2. Swing the boiler lower front panel into the service position. Refer to Section 3.2. 3. Remove the 4 fixing screws. 4. Disconnect the 4 push on connectors. 5. Remove programmer, earth cable and cover. 6. Re-fit 4 push on ...
Page 48 - unclip the C clip from the flow manifold port; PRESSURE GAUGE REPLACEMENT
48 Installation and Servicing SECTION 3 - SERVICING 3.20 DHW FLOW TURBINE SENSOR REPLACEMENT 1. Refer to Section 3.8. 2. Drain the DHW system. Refer to Section 3.19. 3. Pull off the electrical connection. 4. Using a suitable tool, lift and remove the retaining clip. 5. Use the clip to ease the turbi...
Page 49 - fitting positioned outside the boiler; PUMP AUTOMATIC AIR VENT REPLACEMENT; Refill the boiler. Check operation of the
49 Installation and Servicing SECTION 3 - SERVICING 3.22 SAFETY RELIEF VALVE REPLACEMENT 1. Refer to Section 3.8.2. Drain the boiler. Refer to Section 3.19.3. Pull out and remove the clip (positioned safety valve. 4. Undo the safety valve pipe compression fitting positioned outside the boiler casing...
Page 50 - Ensure dimples and “bottom” are lower most.; DHW PLATE HEAT EXCHANGER REPLACEMENT; o remove the valve body assembly:
50 Installation and Servicing SECTION 3 - SERVICING 3.24 DIVERTER VALVE BODY ASSEMBLY REPLACEMENT 1. Refer to Section 3.8.2. Drain the boiler. Refer to Section 3.19.3. Remove the condensate siphon. Refer to Section 3.16. 4. Remove the two plate heat exchanger fixing screws. 5. Slide the plate heat e...
Page 51 - Clean or replace filter as necessary.
51 Installation and Servicing SECTION 3 - SERVICING 3.27 CH WATER PRESSURE SWITCH REPLACEMENT 3.28 DHW FILTER & DHW FLOW REGULATOR CLEANING/REPLACEMENT 1. Refer to Section 3.8.2. Drain the boiler. Refer to Section 3.19. 3. Pull off the two electrical connections. 4. Using a suitable tool, pull o...
Page 52 - is securely fitted to the pipe on the thermistor locator tab; FLOW THERMISTOR
52 Installation and Servicing SECTION 3 - SERVICING 1. Refer to Section 3.8. 2. Unclip the return thermistor from the return pipe and withdraw it from the boiler. 3. Disconnect the electrical lead from the thermistor. 4. Reconnect the electrical lead to the new thermistor and reassemble in reverse o...
Page 53 - Refer also to Section 2.1 - ‘Boiler Exploded View’; Pull out the flow pipe spring clip, pull the pipe down to
53 Installation and Servicing SECTION 3 - SERVICING 3.31 HEAT ENGINE RENEWAL Refer also to Section 2.1 - ‘Boiler Exploded View’ IMPORTANT - Before starting the removal procedure, protect the gas and electrical controls with a waterproof sheet or plastic bag. 1. Refer to Section 3.8. 2. Drain the boi...
Page 54 - Ensure that the boiler front panel is
54 Installation and Servicing SECTION 3 - SERVICING 3.32 EXPANSION VESSEL RECHARGING & REPLACEMENT 3.33 BOILER SEALING PANEL SEAL REPLACEMENT 1. Refer to Section 3.8. 2. Remove the old seal from the casing and thoroughly clean the casing surfaces. 3. Fit the new self adhesive seal ensuring all j...
Page 55 - SECTION 4 - FAULT FINDING; FAULT FINDING; FAULT FINDING CHART MAIN MENU; RESTART PROCEDURE: To restart boiler press the restart button.; ‘FU’
55 F AUL T FINDING F AUL T FINDING F AUL T FINDING F AUL T FINDING F AUL T FINDING Installation and Servicing SECTION 4 - FAULT FINDING 4 FAULT FINDING 4.1 FAULT FINDING CHART MAIN MENU ‘L1’ GO TO SECTION 4.2 - FLOW TEMPERATURE OVERHEAT LOCKOUT ‘L2’ ‘L6’ ‘F1’ ‘F2 or Fn or Ln’ ‘F3’ ‘L4 or F4’ ‘L5 or ...
Page 56 - Is the Boiler and CH System filled with water and all; ‘L2’ - IGNITION LOCKOUT; Check flue is installed correctly.
56 F AUL T FINDING F AUL T FINDING F AUL T FINDING F AUL T FINDING F AUL T FINDING Installation and Servicing SECTION 4 - FAULT FINDING 4.2 ‘L1’ - FLOW TEMPERATURE OVERHEAT LOCKOUT Is the Boiler and CH System filled with water and all isolation and radiator valves open? YES Fill and vent the system ...
Page 57 - RESTART PRO; ‘LC’ - 5 RESETS WITHIN 15 MINS
57 F AUL T FINDING F AUL T FINDING F AUL T FINDING F AUL T FINDING F AUL T FINDING Installation and Servicing SECTION 4 - FAULT FINDING Restart the boiler, does Boiler Work OK? NO Check condition of ignitor and spark generator. Replace if required. Check routing and integrity of internal boiler wiri...
Page 58 - Is the top flue manifold seal present
58 F AUL T FINDING F AUL T FINDING F AUL T FINDING F AUL T FINDING F AUL T FINDING Installation and Servicing SECTION 4 - FAULT FINDING 4.7 ‘F2 OR FN OR LN’ - FLAME LOSS Does the boiler ignite for a short time and then extinguish? YES YES Is the Gas Pressure available at the Boiler Inlet (18 mbar)? ...
Page 60 - If fault persists replace PCB
60 F AUL T FINDING F AUL T FINDING F AUL T FINDING F AUL T FINDING F AUL T FINDING Installation and Servicing SECTION 4 - FAULT FINDING Disconnect the wires to the outside sensor. Check the resistance using a suitable multimeter connected across the Outside Sensor’s terminal pins. At 0 o C expect 31...
Page 62 - Are the flow rates correct as per Section 1.16.
62 F AUL T FINDING F AUL T FINDING F AUL T FINDING F AUL T FINDING F AUL T FINDING Installation and Servicing SECTION 4 - FAULT FINDING 4.16 NO HW BUT CH ON Does the display show “dH” when a tap is on? NO YES Are the flow rates correct as per Section 1.16. Is the wiring between the PCB and the diver...
Page 63 - SECTION 5 - SPARE PARTS; SPARE PARTS; do so could affect safety or performance of this appliance.
63 Installation and Servicing SECTION 5 - SPARE PARTS 5 SPARE PARTS When replacing any part on this appliance use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised...
Page 65 - Benchmark Commissioning &
65 Installation and Servicing © Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk * All installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certific...
Page 67 - SERVICE & INTERIM BOILER WORK RECORD
© Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk * All installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the...
Page 69 - FLOWCHART FOR CO LEVEL AND COMBUSTION RATIO; PRIOR TO CO LEVEL AND COMBUSTION RATIO CHECK; = The CO reading measured in ppm divided by the CO; ppm; FLUE & INTEGRITY CHECKS
69 Installation and Servicing FLOWCHART FOR CO LEVEL AND COMBUSTION RATIO CHECK ON COMMISSIONING A CONDENSING BOILER Important Preliminary Information on Checks The air gas ratio valve is factory-set and must not be adjusted DURING COMMISSIONING.If the boiler requires conversion to operate with a di...
Page 71 - NOTES
Page 72 - USER GUIDE; For Installation Guide see reverse of book; THESE INSTRUCTIONS TO BE RETAINED BY USER; combination boilers; Ideal is a trademark of Ideal Boilers.
USER GUIDE For Installation Guide see reverse of book THESE INSTRUCTIONS TO BE RETAINED BY USER combination boilers Ideal is a trademark of Ideal Boilers. Registered Office Ideal Boilers Ltd., National Avenue, Hull, East Yorkshire, HU5 4JB Tel 01482 492251 Fax 01482 448858 Registration No. London 32...