Honeywell W7345 - Manual
Honeywell W7345 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 3 – INSTALLATION; Location and Mounting; Communicating Economizer Logic Modules; CAUTION; MOUNTING DIRECTLY TO THE MOTOR
- Page 4 – OUTDOOR AIR SENSING; DCV Min and Min Position Damper Set Up
- Page 6 – WIRING; Electrical Shock or Equipment Damage Hazard.
- Page 7 – OPERATION; SETTINGS AND ADJUSTMENT
- Page 8 – Demand Control Ventilation (DCV) Setpoint
- Page 9 – Limit On Minimum Damper Position; Equation 1. Formula to aid in minimum position adjustment.; Differential Enthalpy Changeover Setting; OA
- Page 10 – Temperature
- Page 11 – TROUBLESHOOTING; Description
- Page 12 – Automation and Control Solutions
PRODUCT DATA
63-2569—04
W7340, W7345
Communicating Economizer Logic Modules
FOR VENTILATION CONTROL
APPLICATION
The W7340 Communicating Economizer Logic Module is a full
featured economizer that incorporates Demand Control
Ventilation (DCV) to provide free cooling and ventilation for
occupants in a space while saving energy.
The W7345 Communicating Economizer Logic Module is a
dry bulb only economizer that does not incorporate Demand
Control Ventilation.
The W7340 is used with both solid state temperature and
humidity or enthalpy sensors. The W7345 is used with solid
state temperature sensors only.
FEATURES
• Solid state control package provides accuracy,
reliability and stability.
• Housed in high-impact, glass-fiber reinforced plastic
case.
• Terminals included for connecting optional S963B1136
Remote Potentiometer for remote minimum damper
position control.
• Communicates using a modified Modbus protocol.
• Case matches the lines of the M7215 Damper Motor.
• LED indicates the status of the device input.
W7340 Only
• Operates from the Modbus input, environmental
sensors, and a DCV sensor to provide a totally
integrated control system.
• Combines minimum damper position potentiometer
with solid state temperature (10K NTC) and humidity or
enthalpy changeover control to provide economizer
free cooling function; this control can be overridden
by input via Modbus or DCV sensor.
W7345 Only
• Operates from the Modbus input and mixed/discharge
air sensor to provide a temperature control system.
• Combines the Modbus indoor and/or outdoor
temperature input with the mixed air input to provide
economizer dry bulb free cooling function.
W7340
W7345
Contents
Application ......................................................................... 1
Features ............................................................................ 1
Specifications .................................................................... 2
Installation ......................................................................... 3
Wiring ................................................................................ 6
Operation........................................................................... 7
Settings and Adjustment ................................................... 7
Troubleshooting ................................................................. 11
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES 3 63-2569—04 Table 1. Logic Module Inputs and Outputs. a 2-wire (18, 20, 22 AWG) connection. INSTALLATION When Installing this Product... 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous con...
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES 63-2569—04 4 Fig. 3. Mounting to a Duct or Panel. Enthalpy Sensor (W7340 only) To measure enthalpy, the logic module accepts signals from either: — C7600C Humidity and 10K NTC temperature sensors. — or a C7400 Enthalpy Sensor. IMPORTANT • When usin...
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES 63-2569—04 6 WIRING CAUTION Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry. Disconnect power supply before installation. IMPORTANT 1. All wiring must comply with applicable local codes, ordinances an...