INSTALLATION INSTRUCTIONS

69-0625—03

Place Bar Code Here

VR8304 Intermittent Pilot

Combination Gas Control

APPLICATION

These intermittent pilot gas controls are used in gas-fired
appliances with capacities up to 300 ft

3

/hr at 1 in. WC

pressure drop (8.5 m

3

/h at 0.25 kPa) on natural gas.

They include a manual valve, two automatic operators,
and a pressure regulator. See Table 1 for temperature
ranges and regulator types.

Table 1. Temperature ranges and regulator types

SPECIFICATIONS

Body pattern:

Straight-through body pattern.

Inlet x outlet sizes available:

1/2 x 1/2 in., 1/2 x 3/4 in.,

and 3/4 x 3/4 in. (factory-installed inlet flange).

Adapters

Adapters available for 3/8, 1/2 and 3/4 in.

straight and angle connections. Refer to Table 2.

Electrical Ratings:

voltage and frequency: 24 Vac,

50/60 Hz.

Current Draw:

0.7A.

Capacity:

See Table 3.

Approvals:

• American Gas Association Design Certificate:

UP-70-69A

• Canadian Gas Association Design Certificate:

UP-70-69A.

• Australian Gas Association Certificate: Applied for.
• Delta C: Applied for.

Table 2. Flange part numbers

NOTE: Flange kits include one flange with attached O-

ring and fan mounting screw.

Table 3. Capacity

a

Capacity based on 1000 Btu/ft

3

, 0.64 specific gravity

natural gas at 1 in. WC pressure drop (37.3 MJ/m

3

,

0.64 specific gravity natural gas at 0.25 kPa pressure
drop.

Use conversion factors in Table 4 to convert capacities
for other gases.

Table 4. Gas capacity conversion factors

Model number

Ambient

temperature range Regulator type

VR8304H

0 F to 175 F
(-18 C to +79 C)

Slow-opening

VR8304K

-40 F to 175 F
(-40 C to +79 C)

Slow opening

VR8304M

-40 F to 175 F
(-40 C to +79 C)

Standard-opening

VR8304P

-40 F to 175° F
(-40 C to +79 C)

Step-opening

Inlet/outlet pipe size

Flange type

Part number

3/8 inch NPT

Straight

393690-11

1/2 inch NPT

Elbow

393690-13

3/4 inch NPT

Straight

393690-4

Elbow

393690-15

Size

(inlet x

outlet)

Capacity at 1 in.

WC pressure

drop

a

Minimum

regulated

capacity

Maximum

regulated

capacity

1/2 x 1/2

240 ft

3

/hr

(6.8 m

3

/hr)

30 ft

3

/hr

(0.8 m

3

/hr)

340 ft

3

/hr

(9.6 m

3

/hr)

1/2 X 3/4 270 ft

3

/hr

(7.6 m

3

/hr)

30 ft

3

/hr

(0.8 m

3

/hr)

370 ft

3

/hr

(10.5 m

3

/hr)

3/4

X 3/4 300 ft

3

/hr

(8.5 m

3

/hr)

30 ft

3

/hr

(0.8 m

3

/hr)

415 ft

3

/hr

(11.8 m

3

/r)

Gas

Specific gravity

Multiply listed

capacity by

Manufactured

0.60

0.516

Mixed

0.70

0.765

Propane

1.53

1.62

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for Honeywell VR8304

Summary

Page 2 - INSTALLATION; WARNING; Install Adapters to Gas Control; Flanges

VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROL 69-0625—03 2 INSTALLATION When installing this product ... 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to ensu...

Page 3 - Choose Gas Control Location

VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROL 3 69-0625—03 Choose Gas Control Location Do not locate the gas control where it may be affected by steam cleaning, high humidity, dripping water, corrosive chemicals, dust or grease accumulation, or excessive heat. To ensure proper operation, follow ...

Page 4 - WIRING; Gas Control Knob Settings

VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROL 69-0625—03 4 Fig. 5. Proper use of a wrench on a gas control with and without flanges. 3. Unscrew compression titling from the pilot outlet (Fig. 4). 4. Slip the compression fitting over the tubing and slide out of the way. 5. Push the tubing into th...