Honeywell TR21- Manual
Honeywell TR21– Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Communications; BEFORE INSTALLATION; CAUTION; Erratic System Operation Hazard.; IMPORTANT; INSTALLATION; Fig. 3. Mounting on Standard Utility Conduit Box or
- Page 3 – and Temperature Limit Set Screw Locations (TR23; Cover Disassembly; Improper Electrical Contact Hazard.; Wiring Wall Modules; not; Attaching the Cover
- Page 4 – Wiring and DIP switch settings:; Table 1. DIP Switch Settings and Terminal Connections.; No fan switching from sensor; default; Fan switching from sensor.
- Page 5 – TR22 and TR23 Setpoint Adjustment; When Used With Excel 10 Controllers:
- Page 6 – Table 7. Program Settings for Wall Modules with
- Page 8 – Automation and Control Solutions
INSTALLATION INSTRUCTIONS
62-0267-09
TR21, TR22, TR23, and TR24 Wall
Modules
FEATURES
The TR21, TR22, TR23, and TR24 family of wall modules
include:
• Models with setpoint adjustment.
• Models with humidity output.
• Models with occupied/unoccupied override (bypass)
with LED.
• Models with 3-position (auto/0/1) or 5-position
(auto/0/1/2/3 speed) fan switch.
• L
ON
W
ORKS
®
bus jack on all models except the TR21
and TR21-A models.
• Locking cover on all models.
• Operating range 45° to 99° F (7° to 37° C).
• Models (TR22 and TR23) with user-selectable
temperature setpoint dials in Fahrenheit, Celsius, and
Relative (- to +).
PRODUCT DESCRIPTION
The TR21, TR22, TR23, and TR24 are a family of direct-wired
wall modules for use with:
— Spyder Unitary Controllers: PUL, PVL
— Excel 10 W7750, W7751
a
, W7752, and W7753
controllers
— Honeywell Excel 800, 600, 500, 100, and 80 (all fully
programmable) controllers
— W7761 Controller
— ComfortPoint LON Controllers: CP-UL, CP-VL
All models have a space temperature sensor. Some models
have a temperature dial, setpoint adjustment, L
ON
W
ORKS
bus
jack, override (bypass) with LED, and fan switch.
NOTE: Refer to the
TR21, TR22, TR23, and TR24 Wall
Modules – Specification Data
, form 63-1321, for
specific model features and additional information.
SPECIFICATIONS
Models:
For specific model information, see
TR21, TR22,
TR23, and TR24 Wall Modules – Specification Data
,
form 63-1321.
Environmental Ratings:
• Operating Temperature: 45° to 99° F (7° to 37° C).
• Shipping Temperature: -40° to 150° F (-40° to 65.5° C).
Accessories:
50007298-001 (pack of 12) medium, cover
plate; 6-7/8 x 5 in. (175 x 127 mm).
Approvals:
CE; UL94 plastic enclosure; FCC Part 15, Class B
Temperature Sensor
TR21, TR22, TR23, and TR24 20K Ohm Nonlinearized
Sensor:
All models are furnished with a 20K Ohm nonlinear NTC
temperature sensor that follows a specific temperature
resistance curve. See Fig. 1 on page 2.
NOTE: The TR21-A wall module model has two (2) 20K
Ohm nonlinear NTC temperature sensors in parallel,
which provide 10K NTC temperature sensing
necessary for averaging.
a
The TR21, TR22, TR23, and TR24 wall modules are not
compatible with W7751A,C,E,G Controllers.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Honeywell TR21
Summary
TR21, TR22, TR23, AND TR24 WALL MODULES 62-0267—09 2 Fig. 1. Temperature vs. Resistance for Nonlinear Sensor. Communications All wall modules (except the TR21 and TR21-A models) have a L ON M ARK® bus communications port. If needed, the jack plug must be removed in the field, and terminals 3 and 4 w...
TR21, TR22, TR23, AND TR24 WALL MODULES 3 62-0267—09 Fig. 4. Wall Module Subbase Dimensions in Inches (mm) and Temperature Limit Set Screw Locations (TR23 Shown). Cover Disassembly A snap-fit locking mechanism is used to attach the cover of the wall module to its subbase. To disassemble the cover fr...
TR21, TR22, TR23, AND TR24 WALL MODULES 62-0267—09 4 Wiring and DIP switch settings: See Table 1 to determine DIP switch positions and terminal usage for each controller. Table 1. DIP Switch Settings and Terminal Connections. Controller Model(s) TR23-TR24 DIP Switch Settings TR22-TR24 Terminal Conne...