Table of Contents:

  • Page 2 – SPECIFICATIONS; Environmental Ratings:; Terminal Wiring Location; NOTE: 18 Vdc power for the LCD wall modules is sup-; Module Dimensions
  • Page 3 – LCD Display; Sample Tenant LCD Displays
  • Page 4 – Automation and Control Solutions; Fig. 8. Sample Contractor parameter display showing; TYPICAL SPECIFICATION
Loading the manual

SPECIFICATION DATA

63-1322-02

Zio

®

/Zio Plus LCD Wall Modules

TR70, TR71, TR75 WITH Sylk

®

Bus

GENERAL

The TR70 Series Zio (TR70/TR70-H, TR71/TR71-H) and Zio

Plus (TR75/TR75-H) are 2-wire, non-polarity sensitive, Sylk

bus communicating wall modules for use with Spyder

®

and

ComfortPoint™ programmable controllers.

All models have a space-temperature sensor, network bus

jack, and an LCD panel with three softkeys and two Up/Down

adjustment keys. The TR7-H, TR71-H and TR75-H models

include an onboard humidity sensor.

NOTE: Refer to the Zio/Zio Plus LCD Wall Modules Oper-

ating Guide (form 63-2719) for information about

customizing the wall module configuration in the

WEBs-AX Workbench, such as modifying the

default Home screens or creating your own appli-

cation.

FEATURES

The TR70 Series wall modules include:

• Ability to control tenant access to controller

parameters via password protection.

• Ability to assign labels for enumerated values.
• Customized parameter access, by using the Honeywell

WEBs-AX Workbench tool.

• Ability to link setpoint limits to a network variable.

• Programmable for: Home screen options, tenant

access, contractor access, optional password

protection to contractor mode, access to controller

parameters, setpoint, override, fan, and other

parameters.

• Ability to access and adjust most parameters in the

programmable controller.

• TR75 can access and adjust the controller schedule.
• Ability to balance the VAV system from the wall

module.

• Home screen can display one to three of any of the

following parameters: Temperature Setpoint, Room

Temperature, Room Humidity, Outdoor Humidity,

Outdoor Temperature, and Time, or one of virtually any

parameter in the controller.

• Network bus jack.
• Simple 2-wire terminal connection to the

programmable controller (includes power) and an

optional 2-wire terminal connection for the network. All

connections are polarity insensitive.

• Permanent retention of user configuration, including

setpoints after a power outage.

* Support for up to four TR71 and/or TR75s per Spyder, and if

a TR70 is present, a maximum of three Zios (any combina-

tion of models) are allowed.

Table 1. TR70 Series Features.

Features

Zio

TR70

Zio

TR71

Zio Plus

TR75

Scheduling

x

Parameter Memory (bytes)

1K

2K

4.9K

Up to four Zios on Sylk

x*

x

x

Enumerated Values

x

x

Setpoint Limits as NVs – linking

now possible

x

x

System and Fan command as NVs

x

x

Password protection

x

x

Firmware version/model visible on

display

x

x

0.5 and 5 value increments

x

x

"-" and "/" characters in parameter

names

x

x

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - SPECIFICATIONS; Environmental Ratings:; Terminal Wiring Location; NOTE: 18 Vdc power for the LCD wall modules is sup-; Module Dimensions

ZIO ® /ZIO PLUS LCD WALL MODULES 63-1322—02 2 SPECIFICATIONS Compatibility: Full feature set, including scheduling and password protection requires the latest Spyder firmware (field upgradeable with Spyder Flash Tool), Spyder Tool version greater than 5.18, and WEBs-AX Workbench ver- sion 3.4.57 or ...

Page 3 - LCD Display; Sample Tenant LCD Displays

ZIO ® /ZIO PLUS LCD WALL MODULES 3 63-1322—02 and S-BUS is 18-24 AWG (0.82 to 0.20 sq mm) depending on application, plenum or non-plenum rated, unshielded, twisted pair, solid conductor wire. LCD Display The LCD display may be customized for tenant and contractor users. The following are a few sampl...

Page 4 - Automation and Control Solutions; Fig. 8. Sample Contractor parameter display showing; TYPICAL SPECIFICATION

ZIO ® /ZIO PLUS LCD WALL MODULES Automation and Control Solutions Honeywell International Inc.1985 Douglas Drive NorthGolden Valley, MN 55422customer.honeywell.com ® U.S. Registered Trademark© 2011 Honeywell International Inc.63-1322—02 M.S. Rev. 12-11 Printed in United States SET VIEW MORE - allows...