D770-16-00

1

I56-0964-000

SSM and SSV BELL Series

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Important

Please Read Carefully and Save

This instruction manual contains important information

about the installation and operation of bells. Purchasers

who install bells for use by others must leave this manual

or a copy of it with the user.

System Sensor supplies bells for nearly all sprinkler/fire

alarm/burglar applications.

These instructions apply to all System Sensor bells in the

series. Read all instructions carefully before beginning.

Follow only those instructions that apply to the model you

are installing.

Specifications

SSM Series:

Starting Voltage:

12 VDC

Voltage:

Regulated 24 VDC

Operating Voltage Limit:

16 - 33 VDC

Maximum Current:

45mA

Operating Temperature:

-31° to 150°F (-35° to +66°C)

SSV Series:

Starting Voltage:

96 VAC

Voltage:

Regulated 120 VAC

Operating Voltage:

96 - 132 VAC

Maximum Current:

53mA

Operating Temperature:

-31° to 150°F (-35° to +66°C)

ULC Reverberant Room

ULC Anechoic Room

Sound Output per UL 464 (dBA)

Sound Output (dBA)

24 VDC SSM

SSM24-6A

(6”, 24 VDC, P, S)

85

92

SSM24-8A

(8”, 24 VDC, P, S)

85

98

SSM24-10A (10”, 24 VDC, P, S)

86

97

120 VAC SSV

SSV120-6A

(6”, 120 VAC)

83

93

SSV120-8A

(8”, 120 VAC)

78

98

SSV120-10A (10”, 120 VAC)

85

97

P = Polarized

S = Suppressed

General Description

The Underwriters Laboratory Of Canada has published

codes, standards, and recommended practices for the

installation and use of the above appliances. These can

be found in CAN/ULC S524. It is recommended that the

installer be familiar with these requirements, with local

codes, and any special requirements of the authority hav-

ing jurisdiction.

These bells are intended to be connected to alarm indi-

cating circuits of ULC listed fire alarm control panels. The

SSM series is polarized to enable supervision of the instal-

lation wiring. The SSM bells require 24 VDC and the SSV

bells require 120 VAC.

CAUTION

Do not use in potentially explosive atmospheres.

Do not leave any unused wires exposed.

6581 Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5

1-800-SENSOR2, FAX: 905-812-0771

www.systemsensor.ca

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - WARNING; field. If bell does not perform properly, replace the en

D770-16-00 2 I56-0964-000 Before installing any alarm device, be thoroughly familiar with: CSA C22.1: Canadian Electrical Code, Part 1, Safety Standard for Electrical Installations ULC S524: Installation Of Fire Alarm Systems NFPA 72: National Fire Alarm Code NFPA 13: Installation of Sprinkler Syste...

Page 3 - Figure 1. Typical SSM and SSV bell wiring diagrams:

D770-16-00 3 I56-0964-000 Figure 4. Weatherproof installation: A78-2727-01 3-1/8" 10" BELLS 2-19/32" 6" BELLS 3-3/8" SQUARE MOUNTING HOLE PATTERN (HOLES ARE LOCATED TO MOUNT TO A STANDARD 4" SQUARE OUTLET BOX) 10" 6" STRIKER LOCATED ON BOTTOM OF BELL (VISIBLE FROM REA...

Page 4 - The Limitations of Alarm Devices

D770-16-00 4 I56-0964-000 © System Sensor 2004 Three-Year Limited Warranty System Sensor warrants its enclosed SSM or SSV bell to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express ...