D770-16-00
1
I56-0964-000
SSM and SSV BELL Series
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Important
Please Read Carefully and Save
This instruction manual contains important information
about the installation and operation of bells. Purchasers
who install bells for use by others must leave this manual
or a copy of it with the user.
System Sensor supplies bells for nearly all sprinkler/fire
alarm/burglar applications.
These instructions apply to all System Sensor bells in the
series. Read all instructions carefully before beginning.
Follow only those instructions that apply to the model you
are installing.
Specifications
SSM Series:
Starting Voltage:
12 VDC
Voltage:
Regulated 24 VDC
Operating Voltage Limit:
16 - 33 VDC
Maximum Current:
45mA
Operating Temperature:
-31° to 150°F (-35° to +66°C)
SSV Series:
Starting Voltage:
96 VAC
Voltage:
Regulated 120 VAC
Operating Voltage:
96 - 132 VAC
Maximum Current:
53mA
Operating Temperature:
-31° to 150°F (-35° to +66°C)
ULC Reverberant Room
ULC Anechoic Room
Sound Output per UL 464 (dBA)
Sound Output (dBA)
24 VDC SSM
SSM24-6A
(6”, 24 VDC, P, S)
85
92
SSM24-8A
(8”, 24 VDC, P, S)
85
98
SSM24-10A (10”, 24 VDC, P, S)
86
97
120 VAC SSV
SSV120-6A
(6”, 120 VAC)
83
93
SSV120-8A
(8”, 120 VAC)
78
98
SSV120-10A (10”, 120 VAC)
85
97
P = Polarized
S = Suppressed
General Description
The Underwriters Laboratory Of Canada has published
codes, standards, and recommended practices for the
installation and use of the above appliances. These can
be found in CAN/ULC S524. It is recommended that the
installer be familiar with these requirements, with local
codes, and any special requirements of the authority hav-
ing jurisdiction.
These bells are intended to be connected to alarm indi-
cating circuits of ULC listed fire alarm control panels. The
SSM series is polarized to enable supervision of the instal-
lation wiring. The SSM bells require 24 VDC and the SSV
bells require 120 VAC.
CAUTION
Do not use in potentially explosive atmospheres.
Do not leave any unused wires exposed.
6581 Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5
1-800-SENSOR2, FAX: 905-812-0771
www.systemsensor.ca
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
D770-16-00 2 I56-0964-000 Before installing any alarm device, be thoroughly familiar with: CSA C22.1: Canadian Electrical Code, Part 1, Safety Standard for Electrical Installations ULC S524: Installation Of Fire Alarm Systems NFPA 72: National Fire Alarm Code NFPA 13: Installation of Sprinkler Syste...
D770-16-00 3 I56-0964-000 Figure 4. Weatherproof installation: A78-2727-01 3-1/8" 10" BELLS 2-19/32" 6" BELLS 3-3/8" SQUARE MOUNTING HOLE PATTERN (HOLES ARE LOCATED TO MOUNT TO A STANDARD 4" SQUARE OUTLET BOX) 10" 6" STRIKER LOCATED ON BOTTOM OF BELL (VISIBLE FROM REA...
D770-16-00 4 I56-0964-000 © System Sensor 2004 Three-Year Limited Warranty System Sensor warrants its enclosed SSM or SSV bell to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express ...