Honeywell 2605 - Installation Manual

Honeywell 2605

Honeywell 2605 – Installation Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
Page: / 16

Table of Contents:

  • Page 2 – Mounting Subbase; Fig. 2. Four TR21 Sensors providing temperature
  • Page 3 – SETTINGS
  • Page 4 – INSTALLER SETUP; CAUTION; Setup Using Keypad
  • Page 5 – Text
  • Page 7 – Holidays and 365 - Day Clock
  • Page 8 – Special Functions; Grouping
  • Page 9 – DEHUMIDIFICATION; Control Through Cooling; Reset Temp SetPt
  • Page 10 – Dehumid Hot Gas BP; Table 6. Hot Gas Bypass Dehumidification Logic.
  • Page 11 – WIRING DIAGRAMS
  • Page 12 – with one transformer.
  • Page 13 – Symptom
  • Page 16 – Automation and Control Solutions; By using this Honeywell literature, you agree that Honeywell will
Loading the manual

INSTALLATION INSTRUCTIONS

Place Bar Code Here

62-0258-05

T7351 Commercial Programmable Thermostat

FOR SINGLE- OR MULTI-STAGE CONVENTIONAL/HEAT PUMP SYSTEMS

APPLICATION

The T7351 Commercial Programmable Thermostat
controls 24 Vac commercial single zone heating,
ventilating and air conditioning (HVAC) equipment. The
T7351 consists of a thermostat and subbase. The
thermostat includes the display and keypad for 7-day
programming. The subbase includes equipment control
connections. The subbase mounts on the wall and the
thermostat mounts to the subbase.

MERCURY NOTICE

If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of properly.

Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of an old control. If you have
questions, call Honeywell Customer Care Center
at 1-800-468-1502.

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.

2.

Check ratings given in instructions and on the
product to ensure the product is suitable for your
application.

3.

Installer must be a trained, experienced service
technician.

4.

After installation is complete, check out product
operation as provided in these instructions.

CAUTION

Electrical Shock or Equipment Damage
Hazard. Can shock individuals or short
equipment circuitry.

Disconnect power supply before installation.

Location

Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.

— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall

behind the thermostat.

IMPORTANT

To avoid electrical interference, which can
cause erratic performances, keep wiring runs as
short as possible and do not run thermostat
wires adjacent to the line voltage electrical dis-
tribution systems. Use shielded cable. The
cable shield must be grounded only at the con-
trolled equipment case.

Subbase

WHEN USED TO SENSE ROOM TEMPERATURE

Install the thermostat about 5 ft. (1.5m) above the floor in
an area with good air circulation at average temperature.
(See Fig. 1.)

WHEN NOT USED TO SENSE ROOM TEMPERATURE

When using the remote-mounted temperature (and
humidity) sensor(s) to sense ambient conditions, install
the thermostat in an area that is accessible for setting
and adjusting the temperature and settings.

Install the remote-mounted sensor(s) about 5 ft. (1.5m)
above the floor in an area with good air circulation at
average temperature (See Fig. 1).

If multiple remote sensors are required, they must be
arranged in a temperature averaging network consisting
of four sensors (See Fig. 2).

NOTE: Only TR21 models with no setpoint adjustment

can be used for temperature averaging.

Fig. 1. Typical location of thermostat or

remote-mounted sensor.

5 FEET

(1.5 METERS)

YES

NO

NO

NO

M4823A

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for Honeywell 2605

Summary

Page 2 - Mounting Subbase; Fig. 2. Four TR21 Sensors providing temperature

T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT 62-0258—05 2 Mounting Subbase The subbase mounts horizontally. IMPORTANT • When using the internal temperature or humidity sensor, the device must be mounted horizontally (with the LCD facing upwards). Precise leveling is not needed. • When using remote room ...

Page 3 - SETTINGS

T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT 3 62-0258—05 Wiring Follow equipment manufacturer wiring instructions when available. Refer to the Wiring Diagram section for typical hookups. A letter code is located near each terminal for identification. IMPORTANT All wiring must comply with local electric...

Page 4 - INSTALLER SETUP; CAUTION; Setup Using Keypad

T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT 62-0258—05 4 Fig. 5. Thermostat key locations. INSTALLER SETUP For most applications, the thermostat factory settings do not need to be changed. Review the factory settings in Table 2. NOTE: When power is first applied to the thermostat, the display will show...