Greenheck SSFSD-211 - Manual

Greenheck SSFSD-211

Greenheck SSFSD-211 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
Page: / 7

Table of Contents:

  • Page 2 – Pressure Drop Data; AMCA Test Figures
  • Page 3 – AMCA 5.2 Pressure Drop; Pressure Drop
  • Page 4 – AMCA 5.3 Pressure Drop
  • Page 5 – AMCA 5.5 Pressure Drop
  • Page 6 – Damper Sleeve Dimensional Data; Application Data
  • Page 7 – Damper Sizing Information; Specifications; Transitioned Damper
Loading the manual

Model SSFSD-211 meets the requirements for fire

dampers, smoke dampers and combination fire

smoke dampers established by:

National Fire Protection Association

NFPA Standards 80, 90A, 92A, 92B, 101, & 105

ICBO Uniform Building Codes
IBC International Building Codes
New York City

(MEA listing #260-91-M)

SBCCI Standard Building Codes
California State Fire Marshall

Listing #: 3225-0981:103 (fire)
Listing #: 3230-0981:104 (smoke)

Application

Model SSFSD-211 is a severe environment 304SS combination

fire smoke damper with 3V style blades. The SSFSD-211 has been

qualified to 2000 fpm (10.2 m/s) and 4 in. wg (1.0 kPa) for operation

and dynamic closure in emergency fire smoke situations. Model

SSFSD-211 may be installed vertically (with blades running

horizontal) or horizontally and is rated for airflow and leakage in

either direction.

Ratings

UL 555 Fire Resistance Rating

Fire Rating:

1

1

2

Hours

Dynamic Closure Rating:

Actual ratings are size dependant

Maximum Velocity:

2000 fpm (10.2 m/s)

Maximum Pressure:

4 in. wg (1.0 kPa)

UL 555S Leakage Rating

Leakage Class:

I

Operational Rating:

Actual ratings are actuator

dependant

Maximum Velocity:

2000 fpm (10.2 m/s)

Maximum Pressure:

4 in. wg (1.0 kPa)

Maximum Temperature:

350ºF (177°C) —Depending on

actuator

Standard Construction

Frame:

5 in. x 1 in.(127mm x 25mm) 16 ga.

(1.5mm) 304 stainless steel hat

channel with reinforced corners . A

low profile head and sill are used on

sizes less than 17 in. (432mm) high

to maximize free area and

performance.

Blades:

16 ga. (1.5mm) 304 stainless steel,

reinforced with 3 longitudinal

structurally designed vee’s.

Seals:

Extruded silicone rubber blade

seals. Flexible 304 stainless steel

jamb seals.

Linkage:

304 stainless steel, concealed in

jamb.

Axles:

1/2 in. (13mm) diameter 304

stainless steel.

Bearings:

304 stainless steel sleeve type.

Closure Device:

165º F (74ºC) RRL

Size Limitations

Minimum Size:

8 in. W x 6 in. H

(203mm W x 152mm H)

Maximum

Size:

Single Section:

24 in. W x 30 in. H

Vertical or Horizontal Mount

(610mm x 762mm ) or

22 in. W x 36 in. H Vertical Mount

(559mm x 914mm)

Multiple Section:

48 in. W x 30 in. H

Vertical or Horizontal Mount

(1219mm W x 762mm H) or

88 in. W x 72 in. H Vertical mount

(2235mm x 1829mm )

Optional Features

• OCI (Open closed indication switches)
• 165º F (74°C), 212ºF (100°C), and 350ºF (177°C) RRL available
• TOR (remote override of 165ºF [74°C] closure allows damper to

perform smoke management functions during a fire emergency)

• Electric or pneumatic actuators to accomplish smoke manage-

ment and system functions.

Model SSFSD-211

Combination

FIRE SMOKE DAMPERS

Stainless Steel 3V Blades

UL 555S Leakage Class I

UL 555 1

1

2

Hour Fire Resistance Rating

“UL CLASSIFIED (see complete marking on

product)”

“UL CLASSIFIED to Canadian safety standards

(see complete marking on product)”

Standard 555 & 555S (Listing #R13317)

* W & H dimensions furnished approximately 1/4 in. (6mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.

H*

W*

LH

RH

Installation instructions available at www.greenheck.com

Greenheck Fan Corporation certifies that the
model SSFSD-211 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with
the requirements of the AMCA Certified Ratings
Programs. The AMCA Certified Ratings Seal applies
to air performance ratings only.

R

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Pressure Drop Data; AMCA Test Figures

Pressure Drop Data SSFSD-211 This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of .075 lb/ft 3 (1.201 kg/m 3 ). Actual pressure drop found in any HVAC system is a co...

Page 3 - AMCA 5.2 Pressure Drop; Pressure Drop

AMCA 5.2 Pressure Drop SSFSD-211 5D 6D 5D D = 4 (W) (H ) 3.14 Figure 5.3 Figure 5.2 Figure 5. 5 Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) 500 0.04 500 0.02 500 0.01 500 0.01 1000 0.14 1000 0...

Page 4 - AMCA 5.3 Pressure Drop

AMCA 5.3 Pressure Drop SSFSD-211 5D 6D 5D D = 4 (W) (H ) 3.14 Figure 5.3 Figure 5.2 Figure 5. 5 Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) 500 0.02 500 0.01 500 0.01 500 0.01 1000 0.09 1000 0...

Other Greenheck Models