Page 2 - OUTDOOR
2 Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust Remove any accumulations of dirt, water, ice or snow and wipe dry before moving to indoor storage. To avoid “sweating” of metal parts allow cold parts to reach room temperature. To dry parts and packages use a portable electric heater to get ...
Page 3 - Removing from Storage; Table of Contents; System Identification Tags; Duct Connections; NOTE; Fan System Components
3 Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust Removing from Storage As fans are removed from storage to be installed in their final location, they should be protected and maintained in a similar fashion, until the fan equipment goes into operation.Prior to assembly and installation of th...
Page 4 - CAUTION; Installation
4 Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust CAUTION When installing an ERS plenum cabinet, ensure the proper protective devices are used to protect personnel from moving parts and other hazards. Check local codes to ensure compliance for all protective devices.ERS plenum cabinet with c...
Page 5 - Plenum Service Clearances and; . Cut roof opening and locate curb; . Assemble factory supplied roof curbs; Assembly of Roof Curbs and ERS Plenum
5 Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust Plenum Service Clearances and Access Locations ERS plenum cabinet and Vektor fan bypass air plenum (BAP) require minimum clearances for access on three sides for routine maintenance. Filter replacement, drain pan inspection and cleaning, coil...
Page 6 - . Set the Vektor fan bypass air plenum; Assembly Hardware Kit; ERS and Vektor Fan Bypass Plenum; SKIRT BRACKET; Skirt Bracket; MARRIAGE WALL
6 Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust 5 . Set the Vektor fan bypass air plenum Before moving the Vektor fan BAP into position, gasketing must be installed to seal the plenum sections against leakage. This gasketing is attached to the ERS plenum cabinet prior to shipment. Verify t...
Page 7 - Plenum Bottom Inlet Opening; Length
7 Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust Duct Connections Plenum Bottom Inlet Opening Plenum Side Inlet Duct Dimension Cabinet Size Length (inches) Width (inches) 020 86 25 030 120 25 040 172 25 060 236 25 Cabinet Size Length (inches) Height (inches) 020 86 30 030 120 30 040 172 30 ...
Page 8 - Drain Trap; Installation of Water Coil Piping; RECOMMENDED DRAIN TRAP DESIGN
8 Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust Drain Trap Coils are provided with a stainless steel drain pan with 1 1/4-inch male NPT drain connection. A drain trap must be connected to the drain connection to allow excess water to flow out of the drain pan. More importantly though, due ...
Page 9 - Coil Installation Checklist; as indicated on the coil nameplate or casing.; Filter Replacement; External Pipe
9 Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust Coil Installation Checklist Use the following checklist to verify that all necessary installation procedures have been completed. 1. Coils are installed with airflow in same direction as indicated on the coil nameplate or casing. 2. Condensat...
Page 10 - Vektor Field Coating Touch-up Procedure; Optional Accessories; Vapor Tight Lights; Repair Kit Contents
10 Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust Vektor Field Coating Touch-up Procedure for Scratched Areas Standard coating and color for the Vektor laboratory exhaust system is Greenheck’s LabCoat™ – Industrial Gray (041).The procedure below details the correct method for repairing mino...
Page 11 - Routine Maintenance; • Internal Filter; Check for cleanliness. Replace if required.; • Door Seal; Check if intact and pliable.; • Coil Maintenance; Cleaning; Use caution; Fin Straightening
11 Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust Routine Maintenance CAUTION Use caution when removing access panels or other unit components, especially while standing on a ladder or other potentially unsteady base. Access panels and unit components can be heavy and serious injury may occ...
Page 12 - Warranty; Service; Coil Change Out Procedure; Cabinet; Maintenance Log
12 474118 • Model VKERS-MD IOM, Rev. 1, April 2011 Copyright 2011 © Greenheck Fan Corp. Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove defective during the warranty period will be r...