Purpose/Application

National and local safety standards and codes recognize
the ability of air duct systems to transfer smoke, toxic
gases, and flame from area to area. Sometimes smoke can
be of such quantity as to be a serious hazard to life safety
unless blowers are shut down and dampers are actuated.
The primary purpose of duct smoke detection is to prevent
injury, panic, and property damage by reducing the spread
(recirculation) of smoke. The detector samples air currents
passing through a duct and gives dependable performance
for management of smoke and combination fire smoke
dampers. Duct smoke detection can also serve to protect the
air conditioning system itself from fire and smoke damage.

There are several important documents that provide guidance
concerning the performance, application and installation of
duct detectors:

1) NFPA Standard 90A,

Installation of Air Conditioning

and Ventilating Systems

2) NFPA Standard 92A,

Recommended Practice for

Smoke Control Systems

3) NFPA Standard 72,

National Fire Alarm Code

4) NFPA Standard 101,

Life Safety Code

5) UL Standard 268A,

Standard for Smoke Detectors for

Duct Applications

6) ASHRAE Handbook and Product Directory, “Fire and

Smoke Control”

7) System Sensor,

Guide for Proper Use of Smoke

Detectors in Duct Applications

.

Duct detectors are:

NOT

a substitute for an open area smoke detector.

NOT

a substitute for early warning detection, and

NOT

a replacement for a building’s regular fire detection

system.

Availability

For use with all FSD, SSFSD, SMD, SSSMD, and CFSD
models. Not available on SMDR models.

Listings

UL 268A

Configuration

Maximum wall thickness: 6 in. (152mm) on FSD & SSFSD

applications

(Consult factory for walls greater
than 6 in. [152mm])

Actuator Location: Must be right hand drive

Must be externally mounted

Detector Location: Mounts opposite actuator side

Must be external

Sampling tubes longer than three feet must be supported
on each end. Holes in duct smoke detector sampling tubes
must face into the airflow.

Specifications

Type: Photoelectric

Air duct velocity: 100 to 4000 fpm (.5 m/s to

20.3 m/s)

Operating temperature range: 32°F to 131°F (0°C to 55°C)

Operating humidity range: 10% to 93% R.H.

Operation Voltage: 24 VAC/DC or

120/240 VAC

Features

• Textured cover for convenient visual inspection.
• The detector provides a trouble signal in the event that the

front cover is removed.

• Integral filter system included to reduce dust and residue

effects on detector and housing, thereby reducing
maintenance and servicing.

• Terminal connections are of the strip and clamp method

suitable for 12-18 AWG wiring.

• Outside mounting tabs for easy connection to sleeve or

ductwork (when detector ships loose).

DUCT SMOKE DETECTOR

DH100ACDCLP

Refer to Greenheck Installation Supplement: Part #463813 IOM-Smoke Detector Supplement

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Sleeve Length; Ordering Options; Factory Mounted

ORDERiNg OPTiONS SLEEvE LENgTH Sleeve Length Height less than 25 in. (635mm): 24 in. (610mm) sleeve (15 in. [381mm]‘A’ dimension) (detector mounted parallel to sleeve) Height greater than or equal to 25 in. (635mm): 21 in. (533mm) sleeve (11 in. [279mm] ‘A’ dimension) (detector mounted perpendicular...

Page 3 - Electrical Ratings; Current Requirements; ELECTRiCAL RATiNgS; Dampers Less Than 25 inches (635mm) in Height

Electrical Ratings Power Supply Voltage: 20-29 VDC 24 VAC 50-60 Hz 120 VAC 50-60 Hz 220/240 VAC 50-60 Hz Input Capacitance: 270 µF max. 270 µF max. N/A N/A Reset Voltage: 3.0 VDC min. 2.0 VAC min. 10 VAC min. 20 VAC min. Reset Time: 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. Power Up Ti...

Page 4 - Fusible Link; DUCT SMOKE DETECTOR; OCI

OPTIONAL SECOND MOTOR L2 MOTOR WHITE MOTOR L1 BLUE BLAC K DH100ACDCLP DUCT DETECTOR 115 VAC RED 15 5 12 11 2 1 14 13 3 4 18 8 16 17 6 7 19 20 9 10 C A B BLAC K WHITE WHITE MOTOR BLAC K OPTIONAL THIRD MOTOR DH100ACDCLP DUCT DETECTOR BLUE RED WHITE 24 VAC/VDC WHITE 12 11 14 13 1 2 3 4 5 15 18 16 17 19...