Summary

Page 2 - Pressure Drop Data; AMCA Test Figures

Pressure Drop Data SSFSD-211 This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of .075 lb/ft 3 (1.201 kg/m 3 ). Actual pressure drop found in any HVAC system is a co...

Page 3 - AMCA 5.2 Pressure Drop; Pressure Drop

AMCA 5.2 Pressure Drop SSFSD-211 5D 6D 5D D = 4 (W) (H ) 3.14 Figure 5.3 Figure 5.2 Figure 5. 5 Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) 500 0.04 500 0.02 500 0.01 500 0.01 1000 0.14 1000 0...

Page 4 - AMCA 5.3 Pressure Drop

AMCA 5.3 Pressure Drop SSFSD-211 5D 6D 5D D = 4 (W) (H ) 3.14 Figure 5.3 Figure 5.2 Figure 5. 5 Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) 500 0.02 500 0.01 500 0.01 500 0.01 1000 0.09 1000 0...