Page 3 - iii; TABLE OF CONTENTS
GE Multilin EPM 5000 series Advanced Power Meters iii C HAPTER 1: AC P OWER M EASUREMENT ............. 1 1.1: Single Phase System................ 1 1.2: Three-Phase System ................ 2 1.3: Consumption, Demand and Poor Power Factor .................... 3 1.4: Waveform and Harmonics ........ 4 ...
Page 4 - iv
GE Multilin EPM 5000 series Advanced Power Meters iv C HAPTER 10: P ROGRAMMING G ROUP 1: V OLTAGE , A MP AND W ATT S CALE S ETTINGS ......... 55 10.1: Group 1, Function 0—Full Scale Voltage Settings, Scale Factor & Decimal Point Placement ............................... 55 10.2: Group 1, Functio...
Page 5 - CHAPTER 1: AC POWER MEASUREMENT; GE Multilin; single phase system; = phase difference between the potential and the current.; cos; Reactive power; delivered to the load:; in; . This is a measure of the inefficiency of the electrical system.; Apparent power; VA
CHAPTER 1: AC POWER MEASUREMENT GE Multilin EPM 5000 series Advanced Power Meters 1 CHAPTER 1 AC POWER MEASUREMENT The economics of electric power distribution networking dictate several configurations of AC power transmission. The number of phases and voltage levels characterize these configuration...
Page 6 - EPM 5000 series Advanced Power Meters; and reactive power
CHAPTER 1: AC POWER MEASUREMENT 2 EPM 5000 series Advanced Power Meters GE Multilin Apparent Power (VA) Real Power (W) Reactive Power (VAR) Figure 1.2 : Relationship between apparent, real and reactive power Ideal power distribution should have a PF of 1. This condition can be met only if no reactiv...
Page 7 - . Blondel’s Theorem; CONSUMPTION; = instantaneous power; WH; equation to determine the overall consumption in a billing
CHAPTER 1: AC POWER MEASUREMENT GE Multilin EPM 5000 series Advanced Power Meters 3 Voltages between the phases vary depending on loading factors and the quality of distribution transformers. The three-phase system is distributed in different voltage levels: 208V AC, 480V AC, 2400V AC, 4160V AC, 690...
Page 8 - SINUSOIDAL WAVEFORM; sin; DISTORTED WAVEFORM
CHAPTER 1: AC POWER MEASUREMENT 4 EPM 5000 series Advanced Power Meters GE Multilin 1.4: Waveform and Harmonics Ideal power distribution has sinusoidal waveforms on voltages and currents. In real-life applications, where inverters, computers, and motor controls are used, distorted waveforms are gene...
Page 9 - CHAPTER 2: MECHANICAL INSTALLATION; Standard installation; Installation with K-110 option for limited space conditions
CHAPTER 2: MECHANICAL INSTALLATION GE Multilin EPM 5000 series Advanced Power Meters 5 CHAPTER 2 MECHANICAL INSTALLATION These diagrams display the various possible mechanical installations and Communication Converter installation. The various models use the same hookup and installation. M A X /M IN...
Page 10 - SIDE VIEW; RECOMMENDED; BACK VIEW; W Port; Recommended wire gauge is 20 AWG for DC Output or RS-485 options.
CHAPTER 2: MECHANICAL INSTALLATION 6 EPM 5000 series Advanced Power Meters GE Multilin FIRST PUT (16) PIN CONNECTOR TOGETHER. (2) 8-32 SCREWS WILL SIDE VIEW 0.80 (4) 8-32 SCREWS LINE UP WITH 2 PEMS ON THE BACK PLATE. 0.198 DIA. 3.375 3.375 4.0 DIA. 1.6875 1.6875 RECOMMENDED CUTOUT BACK VIEW Diagram ...
Page 11 - CHAPTER 3: ELECTRICAL INSTALLATION; GE Industrial Systems; CT Size; : CT Size and Maximum Distance; WARNING; HELPFUL DEBUGGING TOOLS; CT C
CHAPTER 3: ELECTRICAL INSTALLATION GE Industrial Systems 5300P Advanced Power Meter 7 CHAPTER 3 ELECTRICAL INSTALLATION 3.1: Connecting the Current Circuit Install the wiring for the current at 600V AC insulation as a minimum. The cable connector should be rated for 6 Amps or greater and have a cros...
Page 12 - be; : Connection to the Main Power Supply; CONTROL POWER; : Control Power and Current; Note: Externally fuse power supply with a slow-blow 3 Amp fuse.
CHAPTER 3: ELECTRICAL INSTALLATION 8 EPM 5000 series Advanced Power Meters GE Multilin O PTION 2: I SOLATING A CT C ONNECTION R EVERSAL USING VOLTAGE READINGS ! Remove potential connections to terminals 6 and 7. Observe the KW reading. It should be positive. ! If negative, reverse the CT wires on te...
Page 13 - on both. The DSP3 input module and the meter base MUST MATCH!; LIST OF CONNECTION DIAGRAMS; NOTE; LINE
CHAPTER 3: ELECTRICAL INSTALLATION GE Multilin EPM 5000 series Advanced Power Meters 9 • The meter and terminal module DSP3 are factory calibrated together; the serial numbers are matched on both. The DSP3 input module and the meter base MUST MATCH! • Mismatching of the meter and DSP3 input module w...
Page 14 - Note
CHAPTER 3: ELECTRICAL INSTALLATION 10 EPM 5000 series Advanced Power Meters GE Multilin + - POWER 7 6 5 4 3 2 1 8 9 10 11 12 13 PORT L1 L LINE A B C LOAD BACK VIEW II. Three-Phase, Three-Wire Open Delta with two CTs and two PTs Note : Remember to make sure Open Delta bit is programmed in the meter (...
Page 15 - V. Three Phase Four-Wire Wye with CT and PTs
CHAPTER 3: ELECTRICAL INSTALLATION GE Multilin EPM 5000 series Advanced Power Meters 11 CONTROL + - POWER 7 6 5 4 3 2 1 8 9 10 11 12 13 PORT L1 L LINE N A B C LOAD BACK VIEW IV. Three-Phase Four-Wire Wye with Direct Voltage and CTs 7 6 5 4 3 2 1 8 9 10 11 12 13 LINE N A B C LOAD L L1 POWER + - PORT ...
Page 18 - HYSTERISIS; RELAYS & 1 KYZ PULSE OUTPUT -NL OPTION
CHAPTER 3: ELECTRICAL INSTALLATION 14 EPM 5000 series Advanced Power Meters GE Multilin 3.7: Relay, Protection and Pulse Output (This section applies only to the -NL or -NL2 Relay Option.) EPM 5300P RELAY OVERVIEW The EPM 5300P offers dry contact relay output capability. The EPM 5200P only offers KY...
Page 19 - : Close-up of the Relay and KYZ pulse output on the rear panel.; KYZ RELAYS; STANDARD RATE TABLE FOR WATTS*; DECIMAL POINT PLACEMENT; three
CHAPTER 3: ELECTRICAL INSTALLATION GE Multilin EPM 5000 series Advanced Power Meters 15 2 0 2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8 N .O . N .C . C O M N .O . N .C . C O M K Y Z A L A R M # 1 A L A R M # 2 P U L S EO U T P U T Figure 3.1 : Close-up of the Relay and KYZ pulse output on the rear panel. Note: ...
Page 20 - . Follow the Decimal Point Placement corresponding to the; STANDARD RATE TABLE FOR WATTS
CHAPTER 3: ELECTRICAL INSTALLATION 16 EPM 5000 series Advanced Power Meters GE Multilin Note: Unless otherwise specified, standard KYZ setup for Pulse Output 0 is positive Watt Hour, Pulse Output 1 is negative Watt-Hour, and Pulse Output 2 is VA-hour. See table below for standard rate. Note: With Op...
Page 21 - CHAPTER 4: COMMUNICATION INSTALLATION; RS-232 COMMUNICATION CONNECTION; CONNECTION FOR DB-9 FEMALE
CHAPTER 4: COMMUNICATION INSTALLATION GE Multilin EPM 5000 series Advanced Power Meters 17 CHAPTER 4 COMMUNICATION INSTALLATION 4.1: RS-232C (This section applies to the RS-232C or RS-485.) All EPM 5300P and 5200P instruments can be equipped with RS-232C or RS-485 communication. RS-232C communicatio...
Page 22 - -Wire RS-485 Communication Connection Installation half duplex
CHAPTER 4: COMMUNICATION INSTALLATION 18 EPM 5000 series Advanced Power Meters GE Multilin RS-485 Hookup Diagram (2 wire) Half Duplex 5300P Instruments (rear view) (-) (+) R T RS-232 RS-485 R T RS-485 Communications Port Model#SF485DB UNICOM 2500 (Bottom View Shown) PC Figure 4.2: 2-Wire RS-485 Comm...
Page 25 - -Wire RS-485 Communication Connection Installation full duplex; Connect the T- wire of the Unicom 2500 to the R- on the RS-485 port
CHAPTER 4: COMMUNICATION INSTALLATION GE Multilin EPM 5000 series Advanced Power Meters 21 RS-485 Hookup Diagram (4 wire) Full Duplex T+ T- R- R+ PC UNICOM 2500 (Bottom View Shown) RS-232 RS-485 Note: This does notrepresent a twisted pair. Itshows the cross-over from Rto T between the Unicomand the ...
Page 26 - Receive Pair; Enlarged view of twisted pair segments
CHAPTER 4: COMMUNICATION INSTALLATION 22 EPM 5000 series Advanced Power Meters GE Multilin RS-485 Hookup Diagram (4 wire) Full Duplex: Detail View G R+ T+ R- T- G R+ T+ R- T- RS-485 Communications Port Model# SF485DB RS-485 Communications Port Model# SF485DB Gnd R+ T+ R- T- UNICOM 2500 (Bottom View ...
Page 27 - : Network of Instruments and Long Distance Communication; COMPUTER; COMPUTER
CHAPTER 4: COMMUNICATION INSTALLATION GE Multilin EPM 5000 series Advanced Power Meters 23 4.3: Network of Instruments and Long Distance Communication The RS-485 Transceiver is required for a large network of instruments. • In a two-wire connection, a maximum of 900 instruments can be included in th...
Page 28 - Modem Manager
CHAPTER 4: COMMUNICATION INSTALLATION 24 EPM 5000 series Advanced Power Meters GE Multilin Y OU MAY WANT TO USE A M ODEM M ANAGER RS485-RS232 C ONVERTER When speaking to most RS-485 or RS-232C based devices, the remote modem must be programmed for the communication to work. This task is often quite ...
Page 29 - Debugging Communication Problems
CHAPTER 4: COMMUNICATION INSTALLATION GE Multilin EPM 5000 series Advanced Power Meters 25 Debugging Communication Problems If you experience NO communication, check these conditions: • Is the Baud Rate set correctly (see Part II: Programming Section)? • Is the Meter Address set correctly (see Part ...
Page 32 - : Accessing Voltage and Current Phases; AMPS; harmonic
CHAPTER 5: OVERVIEW 28 EPM 5000 series Advanced Power Meters GE Multilin 5.1: Accessing the Power Functions MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC AMPS POWER N C B A MAXMIN A N B N C N A B B C C A LM2 LM1 NEXT PHASE VOLTS AMPS POWER MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS...
Page 33 - : Viewing Individual Phase Indication for Power Functions
CHAPTER 5: OVERVIEW GE Multilin EPM 5000 series Advanced Power Meters 29 To access %THD: M AX/M IN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC AMPS POWER N C B A M AXMIN A N B N C N A B B C C A LM 2 LM 1 NEXT PHASE VOLTS AM PS POWER THDK THD THD MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS...
Page 34 - Integration Interval; VOLTS; UNPROTECTED MODE
CHAPTER 5: OVERVIEW 30 EPM 5000 series Advanced Power Meters GE Multilin 5.5: Accessing Max/Min Values Max/min values represent the highest and lowest average demand over a user programmable time period known as the Integration Interval . The readings are calculated using a rolling average technique...
Page 35 - UNPROTECTED RESET; PROTECTED RESET
CHAPTER 5: OVERVIEW GE Multilin EPM 5000 series Advanced Power Meters 31 UNPROTECTED RESET To reset the min of Amps A: MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC AMPS POWER N C B A MAXMIN A N B N C N A B B C C A LM2 LM1 NEXT PHASE VOLTS AMPS POWER MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KV...
Page 36 - SET LIMITS
CHAPTER 5: OVERVIEW 32 EPM 5000 series Advanced Power Meters GE Multilin 5.7: Resetting Hour Readings MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC AMPS POWER N C B A MAXMIN A N B N C N A B B C C A LM2 LM1 NEXT PHASE VOLTS AMPS POWER MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC AM...
Page 37 - : Voltage Phase Reversal and Imbalance; VOLTAGE PHASE REVERSAL:
CHAPTER 5: OVERVIEW GE Multilin EPM 5000 series Advanced Power Meters 33 MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC AMPS POWER N C B A MAXMIN A N B N C N A B B C C A LM2 LM1 NEXT PHASE VOLTS AMPS POWER a. To access the set limit, press MAX/MIN/LIMITS • 3 times for LM1 • 4 times for LM2 5...
Page 38 - ACCESS; Print Operating Data; Communication Converter.
CHAPTER 5: OVERVIEW 34 EPM 5000 series Advanced Power Meters GE Multilin 5.10: Access Modes The following access commands allow the user to perform specific operations. ACCESS COMMANDS OPERATION 1 Print Operating Data 2 Print Programming Data 3 Enter Programming Mode (see Programming Section) 4 Firm...
Page 41 - CHAPTER 6: PROGRAMMAING OVERVIEW; GROUPS are the main category.; Groups Functions Packs
CHAPTER 6: PROGRAMMAING OVERVIEW GE Industrial Systems 5300P Advanced Power Meter 37 CHAPTER 6 PROGRAMMING OVERVIEW 6:1: General Procedure Programming tasks are arranged into nine major GROUPS. Within each GROUP are the specific meter FUNCTIONS. Outlined is the general approach to alter programming ...
Page 42 - CHAPTER 6: PROGRAMMING OVERVIEW; BUTTON FUNCTION; VALUE
CHAPTER 6: PROGRAMMING OVERVIEW 38 EPM 5000 series Advanced Power Meters GE Multilin 6.3: Programming Mode Data Entry The EPM 5300P and EPM 5200P programming mode utilizes only three out of the five-keypad buttons: the MAX/MIN/LIMIT S , VOLTS/THD , and AMPS/THD buttons. T H D T H D M A X /M IN LIM I...
Page 43 - The following features are not available:; The keypad; The annunciators are highlighted one at a time.; Volts
CHAPTER 7: EPM 5200P GE Industrial Systems 5300P Advanced Power Meter 39 CHAPTER 7 EPM 5200P The EPM 5200P is similar to the regular EPM 5300P with the following exceptions: 1. The size of the display digits is smaller (0.300” instead of 0.560”). 2. The following features are not available: • The en...
Page 44 - Feature
CHAPTER 7: EPM 5200P 40 EPM 5000 series Advanced Power Meters GE Multilin EPM 5300P vs. EPM 5200P vs. EPM 5350P Feature 5300P 5200P 5350P Voltage 3-Phase ! ! ! Voltage Accuracy 0.2% 0.3% 0.2% Current 3-Phase and Neutral ! ! ! Current Accuracy 0.2% 0.3% 0.2% Watts, VARS, VA, PF ! ! ! Watts Accuracy 0...
Page 45 - CHAPTER 8: ENTERING PROGRAMMING MODE; Entering Programming Mode:; release
CHAPTER 8: ENTERING PROGRAMMING MODE GE Industrial Systems 5300P Advanced Power Meter 41 CHAPTER 8 ENTERING PROGRAMMING MODE 8.1: Checksum Error—Protective Self-Checking Algorithms This checksum error is a protective self-checking wealth algorithm designed to alert the user when a procedure has not ...
Page 46 - AUTO SCROLLING
CHAPTER 8: ENTERING PROGRAMMING MODE 42 EPM 5000 series Advanced Power Meters GE Multilin NOTE: AUTO SCROLLING will automatically show all of the readings on the face of the meter except LIMITS. To enter Auto Scrolling mode , follow the above steps except use the numbers 666 as the password. To exit...
Page 47 - CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP; FUNCTION; Press
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP GE Industrial Systems 5300P Advanced Power Meter 43 CHAPTER 9 PROGRAMMING GROUP 0 – GLOBAL METER SETUP The Global Meter Setup includes FUNCTIONS 0 through 7 that control configuration and basic operation. FUNCTION 3 System Configuration contains Sw...
Page 48 - METER ADDRESS
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP 44 EPM 5000 series Advanced Power Meters GE Multilin MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC AMPS POWER N C B A MAXMIN A N B N C N A B B C C A LM2 LM1 NEXT PHASE VOLTS AMPS POWER MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC...
Page 49 - —BAUD RATE; BAUD RATE
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP GE Multilin EPM 5000 series Advanced Power Meters 45 MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC AMPS POWER N C B A MAXMIN A N B N C N A B B C C A LM2 LM1 NEXT PHASE VOLTS AMPS POWER MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC...
Page 50 - contains four different Switch PACKS:
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP 46 EPM 5000 series Advanced Power Meters GE Multilin MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC AMPS POWER N C B A MAXMIN A N B N C N A B B C C A LM2 LM1 NEXT PHASE VOLTS AMPS POWER MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC...
Page 51 - PACK SWITCH; : System Configuration—Switch Packs for Group 0, Function 3
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP GE Multilin EPM 5000 series Advanced Power Meters 47 PACK SWITCH FEATURE SEGMENT POSITION A Reserved — B Reserved — C Reserved — 0 D Phase Reversal Limit Detection UP: Enable DOWN: Disable A Non-significant will blank leading zero UP: Enable DOWN: ...
Page 52 - OPEN DELTA SYSTEM INSTALLATION PROGRAMMING; For MODBUS protocol, ASCII framing: PACK; Modbus Plus Capability; DISABLING PREVENTS; Corrupting printing commands through communications.
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP 48 EPM 5000 series Advanced Power Meters GE Multilin OPEN DELTA SYSTEM INSTALLATION PROGRAMMING A special switch is used to indicate that the electrical system being monitored is a Three-phase WYE or Three-Wire Open Delta System using the connectio...
Page 53 - To change the System Configuration Switch Settings:; (This example shows enabling of Open Delta Installation
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP GE Multilin EPM 5000 series Advanced Power Meters 49 9.6: Group 0, Function 3—Programming Procedure To change the System Configuration Switch Settings: NOTE: Press MAX/MIN/LIMITS , at any time, to cancel before storing the last digit or switch. MAX...
Page 54 - : Relays are not available for the EPM 5200P.; R E S E T; S E T
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP 50 EPM 5000 series Advanced Power Meters GE Multilin 9.7: Relay Mode NOTE : Relays are not available for the EPM 5200P. SWITCH DESCRIPTION Segment Position A Reversal Imbalance Control UP ! Enable DOWN ! Disable B AND/OR Logic UP ! AND DOWN ! OR C ...
Page 55 - Normally reset—non-event condition is reset relay; GROUP 0—FUNCTION NUMBER DESCRIPTION; Controls Relay 1
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP GE Multilin EPM 5000 series Advanced Power Meters 51 PROGRAMMING STEPS: 1. Enter in GROUP 0, FUNCTION 4, PACK ‘P’, Segment C and D: UP, UP. 2. Enter in GROUP 5, FUNCTION 4, LIMIT 1, Segments B, C, and D: DOWN, UP, DOWN. Value: 58.00. 3. Enter in GR...
Page 56 - To change the Relay Mode
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP 52 EPM 5000 series Advanced Power Meters GE Multilin To change the Relay Mode to either Fail-safe or Reset: NOTE : Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch. MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOL...
Page 57 - GROUP AND FUNCTION NUMBER; Relay 1: On to Off Delay Time
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP GE Multilin EPM 5000 series Advanced Power Meters 53 9.8: Group 0, Functions 4–5—Time Delay for Relays 1 and 2 (Option – NL) GROUP 0, FUNCTIONS 4–5 sets the time delay for Relays 1 and 2 between 0 and 255 seconds. This allows conditions (example be...
Page 58 - To change Time Delays:; To program Relay 2 and 3:; once; See Chapter 14 to Exit.
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP 54 EPM 5000 series Advanced Power Meters GE Multilin To change Time Delays: NOTE: Press MAX/MIN/LIMITS at any time, to cancel before storing the last digit or Switch . MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC AMPS POWER N C B A MAXMIN...
Page 59 - PARAMETER DESCRIPTION
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP GE Multilin EPM 5000 series Advanced Power Meters 55 9.9: Group 0, Function 6—KYZ Parameter Selection NOTE : FUNCTION 6 applies only if Option -NL or -NL2 was ordered. OPTION -NL : This option gives the meter 2 Relays and one KYZ pulse. The KYZ pul...
Page 60 - —or—
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP 56 EPM 5000 series Advanced Power Meters GE Multilin MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC AMPS POWER N C B A MAXMIN A N B N C N A B B C C A LM2 LM1 NEXT PHASE VOLTS AMPS POWER MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC...
Page 61 - HOW TO USE KYZ PULSE VALUE TABLE FOR MULTIPLICATION:
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP GE Multilin EPM 5000 series Advanced Power Meters 57 HOW TO USE KYZ PULSE VALUE TABLE FOR MULTIPLICATION: S ITUATION 1: FSW=9999. • Selection is Multiply by 2 • This means that every .5 unit WH =1 pulse. • Unit=Kilo (see Group 1, Function 2) • Resu...
Page 62 - at any time to cancel before storing the last digit or switch.
CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP 58 EPM 5000 series Advanced Power Meters GE Multilin 9.10: Group 0, Function 7—Number of Phases NOTE: E NTER 1 FOR SINGLE PHASE / SINGLE WIRE . E NTER 2 FOR SINGLE PHASE / TWO WIRE . E NTER 3 FOR THREE PHASE / THREE OR FOUR WIRE . • *STANDARD FACTO...
Page 63 - CHAPTER 10: PROGRAMMING GROUP 1; The full scale for a CT ratio of 3000/5 should be 03.00 kA.; Full Scale Selection for Volts; : Group 1 Programming Format; and
CHAPTER 10: PROGRAMMING GROUP 1 GE Multilin EPM 5000 series Advanced Power Meters 59 CHAPTER 10 PROGRAMMING GROUP 1 – VOLTAGE, AMP AND WATT SCALE SETTINGS NOTE: The EPM 5300P and 5200P full scales will already be programmed if the order specified current and voltage transformer ratios. The meter lab...
Page 64 - SECONDARY PT VALUES; KV
CHAPTER 10: PROGRAMMING GROUP 1 60 EPM 5000 series Advanced Power Meters GE Multilin SECONDARY PT VALUES PT RATIO FULL SCALE 75 V (Suffix 75) L-N MAX 120:1 9.00 KV 120/208 V 1:1 (Direct) 120.0 120/208 V 4:1 0480 V 120/208 V 120:1 014.4 KV 277/480 V (Suffix G) 1:1 (Direct) 0300 V 120/208V 600:1 072.0...
Page 65 - Kilovolts
CHAPTER 10: PROGRAMMING GROUP 1 GE Multilin EPM 5000 series Advanced Power Meters 61 MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC AMPS POWER N C B A MAXMIN A N B N C N A B B C C A LM2 LM1 NEXT PHASE VOLTS AMPS POWER MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC AMPS POWER N C B A ...
Page 66 - CT T; FULL; Direct Input
CHAPTER 10: PROGRAMMING GROUP 1 62 EPM 5000 series Advanced Power Meters GE Multilin 10.2: Group 1, Function 1—Amperage Full Scale CT T YPE FULL SCALE Direct Input 05.00 A 600/5 0600 A 1000/5 1000 A 2000/5 2000 A 3000/5 03.00 KA 5000/5 05.00 KA Table 10-3 : Full Scale Settings for Amps Also note tha...
Page 68 - by moving the decimal point one position left.
CHAPTER 10: PROGRAMMING GROUP 1 64 EPM 5000 series Advanced Power Meters GE Multilin Full Scale Wattage (FSW) is the product of FSV and FSA. For FSW for three phases multiply the FSW per phase by 3. Example 1: Full Scale Voltage (FSV)=120 V Full Scale Amperage (FSA)=5.00 A FSW (one phase) =120 Vx5.0...
Page 71 - CHAPTER 11: PROGRAMMING GROUP 2 – METER CALIBRATION; WARNING—READ THIS SECTION CAREFULLY BEFORE PROCEEDING:; Exit Programming Group 2; : Group 2 Programming Format
CHAPTER 11: PROGRAMMING GROUP 2 – METER CALIBRATION GE Industrial Systems 5300P Advanced Power Meter 67 CHAPTER 11 PROGRAMMING GROUP 2—METER CALIBRATION WARNING—READ THIS SECTION CAREFULLY BEFORE PROCEEDING: • Any rescaling, such as a change in a transformer ratio, can be accomplished in GROUP 1. Ca...
Page 72 - VOLTAGE RANGE; A CT High End; , Functions 0–2—High End Calibration of Voltage Channels, High
CHAPTER 11: PROGRAMMING GROUP 2 – METER CALIBRATION 68 EPM 5000 series Advanced Power Meters GE Multilin VOLTAGE RANGE INPUT SOURCE GROUP 2 VALUE 69.3/120V 75V 1440 120/208V 120V L-N 1440 277/480V 300V 0300 5A CT High End 5A 2000 2.5A Low End 2.5A 1000 Table 11-2 : Calibration Source, Full Scale and...
Page 75 - EXAMPLE OF LM1/LM2 SET LIMITS; THE FOLLOWING GROUPS ALLOW THE USER TO PROGRAM LIMITS AND RELAYS:; neutral
CHAPTER 12: GROUPS 4, 5, AND 6 – SET LIMITS AND RELAYS GE Industrial Systems 5300P Advanced Power Meter 71 CHAPTER 12 GROUPS 4, 5 AND 6—SET LIMITS AND RELAYS The EPM 5300P -NL offers a comprehensive limit and set point functionality. The user can program above or below limits for every reading, incl...
Page 76 - Group 4: Programming Format for Limit Condition; : Group 4 Programming Format; These functions have a two-part entry:; RELAY 1
CHAPTER 12: GROUPS 4, 5, AND 6 – SET LIMITS AND RELAYS 72 EPM 5000 series Advanced Power Meters GE Multilin 12.3: Group 4, Functions 0–3—LM1/LM2 Set Limits Group 4: Programming Format for Limit Condition GROUP AND FUNCTION NUMBER FUNCTION 40. LM1/LM2 Set Limits for Volts AN, BN, CN 41. LM1/LM2 Set L...
Page 77 - RELAY 2; 0 V, LM2 is triggered and Relay 2 is enabled.; : Group 5 Programming Format for Limit Condition
CHAPTER 12: GROUPS 4, 5, AND 6 – SET LIMITS AND RELAYS GE Multilin EPM 5000 series Advanced Power Meters 73 LM1 LED LM2 LED ABOVE/BELOW RELAY 1 RELAY 2 VALUE ON OFF Digit Up Digit Up Digit Down 0135 OFF ON Digit Down Digit Down Digit Up 0090 Table 12.3 : Group 4: Example for Function 0 EXAMPLE : If ...
Page 78 - THERE ARE 3 SWITCHES TO SET WITH LIMITS:; SPECIAL CASES; second
CHAPTER 12: GROUPS 4, 5, AND 6 – SET LIMITS AND RELAYS 74 EPM 5000 series Advanced Power Meters GE Multilin THERE ARE 3 SWITCHES TO SET WITH LIMITS: 1) Switch 1: Sets the limit to trip either above or below the Limit Value. 2) Switch 2: Sets whether Relay 1 will trip when the condition occurs. 3) Sw...
Page 79 - : Group 6 Programming Format For THD Limit Conditions
CHAPTER 12: GROUPS 4, 5, AND 6 – SET LIMITS AND RELAYS GE Multilin EPM 5000 series Advanced Power Meters 75 Programming Group 6, LM1/LM2 Set Limits K V A R P FK W K V A F R E Q K W H K V A H A C V O L T S A C A M P S P O W E R N C B A M A X M I N A N B N C N A B B C C A L M 2 L M 1 M A X / M I N L I...
Page 80 - : Limits or Relays Programming Procedure; GROUP
CHAPTER 12: GROUPS 4, 5, AND 6 – SET LIMITS AND RELAYS 76 EPM 5000 series Advanced Power Meters GE Multilin 12.5: Group 6, Functions 0–5—LM1/LM2 Set Limits and Relay Triggers for Over/Under %THD Conditions LM1 LED LM2 LED SWITCH 1 ABOVE/BELOW SWITCH 2 RELAY 1 SWITCH 3 RELAY 2 LEVEL ON OFF Digit Up D...
Page 81 - Follow this step for; DISABLING LIMITS; Trip Relay 1
CHAPTER 12: GROUPS 4, 5, AND 6 – SET LIMITS AND RELAYS GE Multilin EPM 5000 series Advanced Power Meters 77 MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC AMPS POWER N C B A MAXMIN A N B N C N A B B C C A LM2 LM1 NEXT PHASE VOLTS AMPS POWER Step 3: a. Press AMPS once. ! Lower display is repl...
Page 83 - CHAPTER 13: PHASE REVERSAL AND PHASE IMBALANCE SET RELAYS; : Phase Reversal and Phase Imbalance; PHASE REVERSAL; Limits Triggered; TRIP RELAY 1
CHAPTER 13: PHASE REVERSAL AND PHASE IMBALANCE SET RELAYS GE Industrial Systems 5300P Advanced Power Meter 79 CHAPTER 13 PHASE REVERSAL AND PHASE IMBALANCE SET LIMITS/RELAYS 13.1: Phase Reversal and Phase Imbalance The set limit alerts the user of an unbalanced or a reversed phase in a Three-phase S...
Page 84 - CHAPTER 14: EXITING PROGRAMMING MODE; GROUP AND FUNCTION; Voltage Phase Reversal Detection; Repeat procedure for
CHAPTER 14: EXITING PROGRAMMING MODE 80 EPM 5000 series Advanced Power Meters GE Multilin 13.3: Group 7, Function 0—Voltage Phase Reversal Detection GROUP AND FUNCTION NUMBER FUNCTION 70. Voltage Phase Reversal Detection 71. Voltage Phase Imbalance 7E. Exit Programming GROUP 7 Table 13.1 : Group 7 P...
Page 85 - : Group 7, Function 1—Percentage Voltage Phase Imbalance
CHAPTER 13: PHASE REVERSAL AND PHASE IMBALANCE SET RELAYS GE Multilin EPM 5000 series Advanced Power Meters 81 MAX/MIN LIMITS KVAR PF KWKVA FREQ KWH KVAH AC VOLTS AC AMPS POWER N C B A MAXMIN A N B N C N A B B C C A LM2 LM1 NEXT PHASE VOLTS AMPS POWER ! Middle and Lower display indicate FUNCTION 0 s...
Page 87 - always; necessary to store any new changes and to calculate a new
CHAPTER 14: EXITING PROGRAMMING MODE GE Industrial Systems 5300P Advanced Power Meter 83 CHAPTER 14 EXITING PROGRAMMING MODE NOTE : Steps to exit Programming Mode vary depending on the programming stage. Exiting the Programming Mode is always necessary to store any new changes and to calculate a new...
Page 89 - CHAPTER 15: PROGRAMMING QUICK REFERENCE; Programming
CHAPTER 15: PROGRAMMING QUICK REFERENCE GE Industrial Systems 5300P Advanced Power Meter 85 CHAPTER 15 PROGRAMMING QUICK REFERENCE 15.1: Entering the Programming Mode 1. Hold PHASE/NEXT key and press AMPS key. 2. Display blanks and shows either a ‘0’, ‘1’, or ‘3’. 3. If ‘3’ is not displayed then pre...
Page 90 - Reserved
CHAPTER 15: PROGRAMMING QUICK REFERENCE 86 EPM 5000 series Advanced Power Meters GE Multilin 15.4: Group 0—Global Meter Setup 00. Interval. 01. Meter Address for Communication. 02. Baud Rate for Communication. 03. System Configuration Switch Packs. 030. Reserved Switches. 031. A. Blank Non Significa...
Page 93 - KEY DESIGNATIONS
CHAPTER 15: PROGRAMMING QUICK REFERENCE GE Multilin EPM 5000 series Advanced Power Meters 89 8P2. Power Uni/Bi Directional Selection A. Port 4 B. Port 5 C. Port 6 D. Port 7 8P3. Power Uni/Bi Directional Selection A. Port 8 B. Port 9 C . Reserved D . Reserved 80. DC output Port 0 80F. Parameter Mappi...
Page 95 - CHAPTER 16: ETHERNET OPTION; ETHERNET; LED DETAIL
CHAPTER 16: ETHERNET OPTION GE Multilin EPM 5000 series Advanced Power Meters 91 CHAPTER 16 ETHERNET OPTION The EPM5350P, Meter with the Ethernet Option, has all the components of the standard Meter PLUS the capability of connecting to multiple devices over Ethernet. The Meter face is the same as th...
Page 96 - LED Description
CHAPTER 16: ETHERNET OPTION 92 EPM 5000 series Advanced Power Meters GE Multilin See the Table below for a description of the Status LED functions. LED Description LED Functions 1 Serial Port (Channel) 1 Status Lights solid green to indicate Channel 1 is IDLE. Blinks green to indicate Channel 1 is c...
Page 97 - ARP ON UNIX
CHAPTER 16: ETHERNET OPTION GE Multilin EPM 5000 series Advanced Power Meters 93 16.3: Default IP Address The Ethernet Interface ships with a default IP address set to 0.0.0.0, whish automatically enables DHCP within the Ethernet Interface. Provided a DHCP server exists on the network, it will suppl...
Page 98 - ARP ON WINDOWS; Be sure to include a space between the IP address and 9999.
CHAPTER 16: ETHERNET OPTION 94 EPM 5000 series Advanced Power Meters GE Multilin ARP ON WINDOWS In order for the ARP command to work on Windows, the RP table on the PC must have at least one IP address defined other than its own. If the ARP table is empty, the command will return an error message. T...
Page 99 - Enter
CHAPTER 16: ETHERNET OPTION GE Multilin EPM 5000 series Advanced Power Meters 95 16.7: Configuration Parameters After entering Setup Mode (confirm by pressing Enter), you an configure the parameters by entering one of the numbers on the Change Setup Menu, or you can confirm default values by pressin...
Page 100 - multilin
g GE Multilin 215 Anderson Avenue Markham, Ontario Canada L6E 1B3 Tel: (905) 294-6222 Fax: (905) 201-2098 http://www.GEindustrial.com/ multilin