This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation &
wiring. Other detail infromation about programming and intructions is compatible with EH series; please see PLC
Application Manual. For more information about the optional peripherals, please see individual product instuction
shee or “DVP-PLC Application Manual: Special module”.

This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, humidity, electric
shock risk and vibration. Also, it is equipped with protective methods such as some special tools or keys to open the
enclosure, in order to prevent hazard to users or damage the PLC.

Do NOT connect the AC main circuit power supply to any of the input/output terminals, or it may damage the PLC.
Check all the wiring prior to power up. To prevent any electromagnetic noise, make sure the PLC is properly
grounded

. Do NOT touch terminals when power on.

Introduction

Thank you for choosing Delta DVP28SV. 28SV is a 28-point (16 input + 12 output) PLC MPU, offering various
instructions and is with 16K Steps program memory, able to connect with all SS/SA/SX/SC/SV series
extension models, including digital input/output (max. 512 input/output extension points), analog modules
(A/D, D/A tranformation and termperature units) and all kinds of new high-speed extenstion modules. Its
4-group high-speed (200KHz) pulse outputs and the two new 2-axis interpolation instructions satisfy all kinds
of applications. DVP28SV is small in size and easy to install.

Product Profile and Outline

1

2

3

4

5

6

7

14

10

9

8

13

12

11

70

3

9

0

3

17

18

16

15

60

20

19

21

Unit : mm

1 POW ER/RUN/BAT.LOW/ERROR indicator

12 Extension module connection port

2 COM1(RS-232) receiving communication (Rx) indicator 13 DIN rail (35mm)

3 COM2(RS-485) sending communication (Tx) indicator 14 Extension module fastening clip

4 Input/output indicator

15 COM2 (RS-485) communication port (Master/Slave)

5 RUN/STOP switch

16 Power input port

6 VR0: M1178 enabled/D1178 corresponding value

17 3 P removable terminal (standard component)

7 VR1: M1179enabled/D1179 corresponding value

18 Power input connection cable (standard component)

8 Input/output terminal

19 New high-speed extension module connection port

9 COM1(RS-232) program I/O communication port

20 Nameplate

10 DIN rail clip

21 Direct fastening hole

11 Extension module positioning hole

ENGLISH

Specifications

Model

Item

DVP28SV11R

DVP28SV11T

Power supply voltage

24V DC (-15% ~ 20%) (with counter-connection protection on the polarity of DC input power)

Inrush current

Max. 2.2A@24V DC

Power consumption

6W

Insulation resistance

> 5M

(all I/O point-to-ground: 500V DC)

Noise immunity

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV; Digital I/O: 1KV,
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

Earth

The diameter of grounding wire shall not be less than that of the wiring terminal of the power.

(When many PLCs are in use at the same time, please make sure every PLC is properly
grounded.)

Operation/storage

Operation: 0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -40ºC ~ 70ºC (temperature); 5 ~ 95% (humidity)

Vibration/shock immunity

International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27
(TEST Ea)

Weight (g)

260g

240g

Type

Current

Motion level

Responding time

Input
point

DC

(Sink or
Source)

24VDC

5mA

X0 ~ X7,X12 ~

X13,X16 ~ X17

Off

On

> 16.5VDC

X10 ~ X11, X14 ~ X15

Off

On

> 18.5VDC

X0 ~ X17

On

Off

< 8VDC

Approx. 10 ms (can be
adjusted within the range of
10 ~ 60 ms by D1020 and
D1021)

Type

Current

Voltage

Max. loading

Responding

time

Mechanical

life

Electrical life

relay-R

1.5A/1 point

(5A/COM)

250VAC,

> 30VDC

75VA

(inductive)

90 W

(resistive)

Approx.

10 ms

2×10

7

times

(without

load)

1.5×10

5

times (5A

30VDC)
5×10

5

times (3A

120VAC)
3×10

4

times (5A

250VAC)

Max. 10KHz
for Y5, Y7,
Y10 ~ Y13

Off

On

20us

On

Off

30us

Output

point

transist

or-T

General: 0.3A/1
point @40ºC

High-speed: <
1KHz, 0.3A/1 point
@ 40ºC;

1KHz,

30mA/1point@40
ºC

30VDC

Max. 200KHz
for Y0, Y1, Y2,
Y3, Y4, Y6

Off

On

0.2us

On

Off

0.2us

-

-

Model Name & I/O Configuration

Standard Functional MPU

Input/output specification

I/O configuration

Input

Output

Model

Power

Point

Type

Point

Type

Relay

Transistor Point

DVP28SV11R

Relay

DVP28SV11T

24VDC

16

DC (Sink

Or

Source)

12

Transistor

S / S

X 0
X 1
X 2
X 3
X 4
X 5
X 6
X 7

S / S

X 1 0

X 11

X 1 2
X 1 3

X 1 5
X 1 6
X 1 7

C 0
Y 0
Y 1
Y 2

Y 3
Y 4
Y 5

Y 6
Y 7

Y 10

Y 11
Y 12
Y 13

C 1

C 2

C 3

S / S

X 0

X 1

X 2
X 3
X 4
X 5
X 6
X 7

S / S

X 1 0

X 11

X 1 2
X 1 3

X 1 5
X 1 6
X 1 7

C 0
Y 0
Y 1
C 1

C 2
Y 4
Y 5

Y 6
Y 7

Y 1 2
Y 1 3

C 3

Y 2
Y 3

C 4

Y 1 0
Y 11

Installation & Wiring

4.1 PLC Mounting Arrangements and Wiring Notes

How to install DIN rail:

DVP-PLC can be secured to a cabinet by using the DIN rail of 35mm in height and 7.5mm in depth. When
mounting PLC to DIN rail, be sure to use the end bracket to stop any side-to-side movement of PLC and reduce
the chance of wires being loosen. A small retaining clip is at the bottom of PLC. To secure PLC to DIN rail, place
the clip onto the rail and gently push it up. To remove it, pull the retaining clip down and gently remove PLC from
DIN rail, as shown in figure 1.

How to screw :

Please use M4 screw (see figure 2) according to the dimension of the product. Please install PLC in an
enclosure with sufficient space around it to allow heat dissipation (see figure 3).

9

0

53. 2

70

1

0

1

1

0

9

.4

PLC

D

D

D

D

D > 50 mm

Figure 1

Figure 2 (Unit: mm)

Figure 3

Wiring:

2 2 - 1 6 A W G

< 1 . 5 m m

1. Use 22-16AWG (1.5mm) single or multiple core wire on I/O wiring terminals. The

specification of the terminal is shown in the figure on the left. The PLC terminal
screws shall be tightened to 1.95 kg-cm (1.7 in-lbs).

2. DO NOT place the I/O signal wires and power supply wire in the same wiring duct.

3.

Use 60/75 ºC copper wires only.

DO NOT install PLC in an environment with:

Dust, smoke, metallic debris, corrosive or flammable gas

High temperature, humidity

Direct shock and vibration

4.2 Wiring Notes

Power input wiring

The power input of DVP-SV series is DC. When operating SV series, please make sure that:

1. The power is connected to the two terminals, 24V DC and 0V, and the range of power is 20.4 ~ 28.8V DC.

If the power voltage is less than 20.4V DC, PLC will stop running, all outputs will go “Off” and ERROR
indicator will flash continuously.

2. The power shutdown of less than 10 ms will not affect the operation of PLC. However, power shutdown

time that is too long or the drop of power voltage will stop the operation of PLC and all outputs will go “Off”.
When the power supply turns normal again, PLC will automatically return to its operation. (Please be
aware of the latched auxiliary relays and registers inside PLC when programming.)

24V

2A

S/S

X0

X1

X2

20.4V~ 28.8V

0V

DC/DC

5V

Safety wiring

Since DVP28SV is only compatible with DC power supply, Delta power supply modules (DVPPS01/DVPPS02)
are suitable power supplies for DVP28SV. Users are suggested to install the protection circuit at the power
supply terminal to protect DVPPS01 or DVPPS02.

AC power supply load

Power circuit protection fuse (3A

Power indicator

Emergency stop

This button can cut off the system power supply
when accidental emergency takes place.

System circuit isolation device

The device is made of electromagnetic contactor
and relay as the switch to prevent the instability of
system when the power is intermittently supplied.

DVPPS01/DVPPS02 (main processing unit)

Earth

M C

M C

N

L

1

1

2

3

4

5

6

7

8

Gua r d

Li mi t

M C

Power supply AC: 100 ~ 240V AC, 50/60Hz

Input point wiring

There are two types of DC inputs, SINK and SOURCE.

Input point loop equivalent circuit

Wiring loop

DC Signal IN

S/S

X0

Sinking

SINK

mode

(common port for current

input S/S)

24VDC

24 G

X0

S/S

+24V

SINK

+5V

24 G

S/S

X0

X1

X2

+24V

Sink Type

Input point loop equivalent circuit

Wiring loop

DC Signal IN

S/ S

X0

Sourcing

SOURCE

mode

(common port for current

output S/S)

24VDC

24 G

X0

S/S

+24V

SOURCE

+5V

24G

S/S

X0

X1

X2

+24V

Source Type

Output point wiring

Y0

RY

LED

C0

LO AD

PO WE R

DVP -**-**-11 -R

RELAY OUT PUT

DVP-**-**-11-T

TRANSISTOR OUTPUT

LED

Y0

C0

LOAD

< 0.3A

T
R
G

1. DVP-SV series have two output modules, relay and transistor. See “Specifications” for their specifications.

2. Be aware of the connection of shared terminals when wiring output terminals.

3.

Output terminals, Y0, Y1, and Y2, of relay models use C0 common port; Y3, Y4, and Y5 use C1 common

port; Y6, Y7, and Y10 use C2 common port; Y11, Y12, and Y13 use C3 common port, as shown in the
next page.

C 0 Y 0 Y 1 Y 2 C 1 Y 3 Y 4 Y 5 C 2 Y 6 Y 7 Y 10 C 3 Y 11 Y 12 Y 13

When output points are enabled, their corresponding indicators on the front panel will be on.

4. Output terminals, Y0 and Y1, of transistor models use C0 common port; Y2 and Y3 use C1 common port;

Y4 and Y5 use C2 common port; Y6 and Y7 use C3 common port; Y10, Y11, Y12 and Y13 use C4
common port, as shown below.

C 0 Y 0 Y 1

C 4 Y 10 Y 11 Y 12

C 1 Y 2 Y 3 C 2 Y 4 Y 5 C 3 Y 6 Y 7

Y 13

5. Isolation circuit: The optical coupler is used to isolate signals between the circuit inside PLC and input

modules.

Relay (R) contact circuit wiring

Y0

R Y

LED

C0

LOAD

PO WE R

DVP-**-**-**-R

RELAY OUTPUT

2

3

1

5

C 0

Y 0 Y 1

C 1 Y 3 Y 4 C 2 Y 6 Y 7

4

M C 1

M C 2

7

1 0

3

2

8

9

6

R

C

Flywheel diode (SB360 3A 60V): To extend the life span of contact

Emergency stop: Uses external switch

Fuse: Uses 5 ~ 10A fuse at the common port of output contacts to protect the output circuit.

Varistor: To reduce the interference on AC load (R=100~120

, C=0.1~0.2uF)

Empty terminal: not in use

DC power supply

Neon indicator

AC power supply

Incandescent light (resistive load)

Manually exclusive output: Uses external circuit and forms an interlock, together with the PLC
internal program, to ensure safety protection in case of any unexpected errors.

Transistor (T) contact circuit wiring

DVP-**-**-**-T

TRANSISTO R OUTPUT

LED

Y0

C0

LO AD

0

00

0 ....5555A

AA

A 以下

以下

以下

以下

MC1

M C 2

2

3

1

C 0 Y 0

Y 1

C 4 Y 1 0 Y 1 1 Y 1 2 Y 1 3

5

4

5

3

4

DC power supply

Emergency stop

Circuit protection fuse

Flywheel diode (SB360 3A 60V) + inductive load

Manually exclusive output: Uses external circuit and forms an interlock, together with the PLC
internal program, to ensure safety protection in case of any unexpected errors.

注意事項

本使用說明書僅提供電氣規格、功能規格、安裝配線部份說明,其它詳細之程式設計及指令與

EH

系列相容,

詳細說明請見

DVP-PLC

應用技術手冊【程式篇】,選購之週邊裝置詳細說明請見該產品隨機手冊或

DVP-PLC

應用技術手冊【特殊模組篇】。

本機為開放型

(OPEN TYPE)

機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊

/

衝擊

意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或意外
衝擊本體,造成危險及損壞。

交流輸入電源不可連接於輸入/出信號端,否則可能造成嚴重損壞,請在上電之前再次確認電源配線。請勿
在上電時觸摸任何端子。本體上之接地端子

務必正確的接地,可提高產品抗雜訊能力。

產品簡介

謝謝您採用台達

DVP

系列可程式控制器。

SV

28

點(

16

輸入點

+ 12

輸出點)

PLC

主機,提供豐富的指令集,

並具有

16K Steps

的程式記憶體,可連接

SS/SA/SX/SC/SV

全系列擴充機,包含數位輸入

/

輸出(最大輸入

/

輸出擴

充點數可達

512

點)、類比模組(

A/D

D/A

轉換及溫度單元)

及新型高速擴充機等各類機型。四組高速(

200KHz

脈波輸出、新增兩軸補間指令,可滿足各種應用場合,並且體積小,安裝容易。

產品外觀及各部介紹

1

2

3

4

5

6

7

14

10

9

8

13

12

11

70

3

9

0

3

17

18

16

15

60

20

19

21

尺寸單位:

mm

1

電源、運行、電池低電壓及錯誤指示燈

12

擴充機連接口

2

COM1 (RS-232)

通訊接收

(Rx)

指示燈

13

DIN

軌糟(

35mm

3

COM2 (RS-485)

通訊傳送

(Tx)

指示燈

14

擴充機固定扣

4

輸出

/

入點指示燈

15

COM2 (RS-485)

通訊口

(Master/Slave)

5

RUN/STOP

開關

16

電源輸入口

6

VR0

M1178

啟動

/D1178

對應值

17

3 P

脫落式端子(標準附件)

7

VR1

M1179

啟動

/D1179

對應值

18

電源輸入連接線(標準附件)

8

輸出

/

入端子

19

新型高速擴充機連接口

9

COM1 (RS-232)

程式輸出

/

入通訊口

20

銘牌

10

DIN

軌固定扣

21

直接固定孔

11

擴充機定位孔

繁體中文

繁體中文

繁體中文

繁體中文

電氣規格

機種

項目

DVP28SV11R

DVP28SV11T

電源電壓

24V DC (-15% ~ 20%)

(具直流輸入電源極性反接保護)

突入電流

MAX 2.2A @24V DC

電源保險絲容量

2.5A/30V DC

,可恢復式

(Polyswitch)

消耗電力

6W

絕緣阻抗

5 M

以上

(

所有輸出/入點對地之間

500V DC)

雜訊免疫力

ESD(IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT(IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV,
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS(IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

接地

接地配線之線徑不得小於電源端配線線徑(多台

PLC

同時使用時,請務必單點接地)

操作/儲存環境

操作:

0ºC ~ 55ºC

(溫度)

50 ~ 95%

(濕度)污染等級

2

儲存:

-40ºC ~ 70ºC

(溫度)

5 ~ 95%

(濕度)

耐振動/衝擊

國際標準規範

IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea)

重量(約

, g

260g

240g

輸入點電氣規格

輸出點電氣規格

輸入形式

流(

SINK

SOURCE

輸出形式

繼電器

-R

電晶體

-T

輸入電流

24VDC 5mA

電流規格

1.5A/1

點(

5A/COM

一般

0.3A/1

@40ºC

高速

> 1KHz, 0.3A/1

@40ºC

1KHz, 30mA/1

@40ºC

X0~X7,X12~X13,X16~X17

Off

On 16. 5VDC

以上

電壓規格

250VAC, 30VDC

以下

30VDC

X10~X11,X14~X15

Off

On 18. 5VDC

以上

最大負載

75VA

(電感性)

90W

(電阻性)

Y5,Y7,Y10 ~ Y13

最高為

10KHz

Y0,Y1,Y2,Y3,Y4,Y6

最高為

200KHz

動作位準

X0~X17
On

Off 8VDC

以下

反應時間

10 ms

Off

On 20us

On

Off 30us

Off

On 0.2us

On

Off 0 .2us

機械壽命

2×10

7

(

無負載

)

-

反應時間

10 ms

(由

D1020

D1021

可作

10~60 ms

的調整)

接點壽命

1.

5

×10

5

(5A

30VDC)

5×10

5

(3A 120VAC)

3×10

4

(5A 250VAC)

-

機種型號與

I/O

配置

標準功能型主機

輸入

輸入

輸入

輸入/

/輸出規格

輸出規格

輸出規格

輸出規格

I/O

配置

配置

配置

配置

輸入單元

輸出單元

機種

機種

機種

機種

電源

點數

形式

點數

形式

繼電器

電晶體

DVP28SV11R

繼電器

DVP28SV11T

24VDC

16

直流

Sink

Source

12

電晶體

S /S

X 0
X 1
X 2
X 3
X 4
X 5
X 6
X 7

S /S

X 10
X11
X 12
X 13

X 15
X 16
X 17

C 0
Y 0
Y 1
Y 2

Y 3
Y 4
Y 5

Y 6
Y 7

Y 10

Y11
Y 12
Y 13

C 1

C 2

C 3

S / S

X 0

X 1

X 2
X 3
X 4
X 5
X 6
X 7

S / S

X 10

X 11

X 12
X 13

X 15
X 16
X 17

C 0
Y 0

Y 1
C 1

C 2
Y 4
Y 5

Y 6
Y 7

Y 12
Y 13

C 3

Y 2
Y 3

C 4

Y 10
Y 11