Analog Output Module

Instruction Sheet

Warning

9

Please read this instruction carefully before use.

9

Switch off the power before wiring.

9

DVP04DA-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of
airborne dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance
staff from operating the device (e.g. key or specific tools are required to open the enclosure) in case
danger and damage on the device may occur.

9

DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may
occur. Check all the wiring again before switching on the power.

9

DO NOT tough any terminal when the power is switched on. DO NOT touch any internal circuit in 1
minute after the power is switched off.

9

Make sure the groud terminal

is correctly grounded in order to prevent electromagnetic

interference.

Introduction

1.1 Model Explanation & Peripherals

™

Thank you for choosing Delta DVP series. DVP04DA-H2 is able to read and write data of DVP04DA-H2 analog

signal output modules through FROM/TO instructions given by the program of DVP-EH2 series MPU. The
analog signal output module receives 4 groups of 12-bit digital data from PLC MPU and converts the data into 4
points of analog signals for output in either voltage or current.

™

The user can select voltage or current output by wiring. Range of voltage output: 0V ~ +10VDC (resolution:

2.5mV). Range of current output: 0mA ~ 20mA (resolution: 5

μ

A).

™

Nameplate Explanation

0 4 D A - H 2 0 T 6 5 0 0 0 0 1

V X .X X X X

24 Vdc 4.5W

MA D E I N X X X X X X

2.5 m V or 5 A

0 V ~ + 10 V or 0m A ~ + 20m A

P ow er i n put s pe c if i c ati o n

De lta PLC mo del nam e

Bar c od e, Ser ial No. , Ve rs i on

Ana log I/O mod ul e s pec ifi c a ti on

™

Model/Serial No. Explanation

1.2 Product Profile (Indicators, Terminal Block, I/O Terminals)

Unit: mm

D -

V

+

I +

V

+

24V

0

V

I

+

V

+

I +

V

+

I +

D +

C

O

M

8

C

H

1

C

H2

C

H

3

C

H4

R

S

-485

FG

FG

FG

CO
M

C

O

M

CO
M

1

DIN rail (35mm)

6

Terminals

2

Connection port for extension modules

7

Mounting hole

3

Model name

8

I/O terminals

4

POWER, ERROR, D/A indicator

9

Mounting port for extension modules

5

DIN rail clip


1.3 External

Wiring

V+

I+

COM

V+

I+

COM

24+

24-

DC/DC

+15V

-15V

AG

FG

FG

CH1

CH1

0V~+10V

*2

*3

0mA~20mA

DC24V

CH4

CH4

AC drive, recorder,

scale valve...

AC drive, recorder,
scale valve...

voltage output

shielding cable *1

shielding cable *1

current output

converter

terminal of

power module

system grounding

class 3 grounding

(100

or less)

Note:

1.

When performing analog output, please isolate other power wirings.

2.

If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the
wiring to 0.1 ~ 0.47

μ

F 25V capacitor.

3.

Please connect the

terminal on both the power modules and DVP04DA-H2 to the system earth point and ground the

system contact or connect it to the cover of power distribution cabinet.

4.

DO NOT wire empty terminals

Specifications

2.1. Functions

Digital/Analog (4D/A) Module

Voltage Output

Current Output

Power supply voltage

24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)

Analog output channel

4 channels/module

Range of analog output

0 ~ 10V

0 ~ 20mA

Range of digital data

0 ~ 4,000

0 ~ 4,000

Resolution

12 bits (1

LSB

= 2.5mV)

12 bits (1

LSB

= 5

μ

A)

Output impedance

0.5

or lower

Overall accuracy

±

0.5% when in full scale (25°C, 77°F)

±

1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F

Responding time

3ms × the number of channels

Max. output current

10mA (1K

~ 2M

) -

Tolerable load impedance

-

0 ~ 500

Digital data format

11 significant bits out of 16 bits are available; in 2’s complement

Isolation

Internal circuit and analog output terminals are isolated by optical coupler.
No isolation among analog channels.

Protection

Voltage output is protected by short circuit. Short circuit lasting for too long may
cause damage on internal circuits. Current output can be open circuit.

Communication mode
(RS-485)

ASCII/RTU mode.
Communication speed: 4,800/9,600/19,200/38,400/57,600/115,200 bps
ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1)
RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1)
RS-485 cannot be used when connected to PLC MPU.

When connected to
DVP-PLC MPU in series

The modules are numbered from 0 to 7 automatically by their distance from MPU.

No.0 is the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed
to connect to MPU and will not occupy any digital I/O points.

2.2. Others

Power Supply

Max. rated power
consumption

24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)., 4.5W supplied by external power

Environment

Operation/storage

Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -40°C ~ 70°C (temperature); 5 ~ 95% (humidity)

Vibration/shock
immunity

International standards: IEC1131-2, IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC
68-2-27 (TEST Ea)

Control Registers

DVP04DA-H2 analog output module

Description

CR#

RS-485

parameter

address

Latched Register content

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

#0

H’4032

R

Model name

Set up by the system. DVP04DA-H2 model code = H’6401

reserved

CH4

CH3

CH2

CH1

#1

H’4033

R/W

Output mode
setting

Output mode: Default = H’0000
Mode 0: Voltage output (0V ~ 10V)

Mode 1: Voltage output (2V ~ 10V)
Mode 2: Current output (4mA ~ 20mA)
Mode 3: Current output (0mA ~ 20mA)

#2 ~ #5

Reserved

#6

H’4038

R/W CH1 output value

#7

H’4039

R/W CH2 output value

#8

H’403A

R/W CH3 output value

#9

H’403B

R/W CH4 output value

Range of output value at CH1 ~ CH4: K0 ~ K4,000
Default = K0 (unit: LSB)

#10 ~ #17

Reserved

#18

H’4044

R/W

Adjusted OFFSET
value of CH1

#19

H’4045

R/W

Adjusted OFFSET
value of CH2

#20

H’4046

R/W

Adjusted OFFSET
value of CH3

#21

H’4047

R/W

Adjusted OFFSET
value of CH4

Range of OFFSET at CH1 ~ CH4: K-2,000 ~ K2,000
Default = K0 (unit: LSB)

#22 ~ #23

Reserved

#24 H’404A

R/W

Adjusted GAIN
value of CH1

#25 H’404B

R/W

Adjusted GAIN
value of CH2

#26 H’404C

R/W

Adjusted GAIN
value of CH3

#27 H’404D

R/W

Adjusted GAIN
value of CH4

Range of GAIN at CH1 ~ CH4: K-1,600 ~ K8,000
Default = K2,000 (unit: LSB)

#28 ~ #29

Reserved

#30

H’4050

R

Error status

Register for storing all error status. See the table of error status for more information.

#31

H’4051

R/W

Communication
address setting

For setting up RS-485 communication address. Range: 01 ~ 255
Default = K1

#32

H’4052

R/W

Communication
speed (baud rate)
setting

Default = H’0002. For setting up communication speed: 4,800 / 9,600 / 19,200 /
38,400 / 57,600 / 115,200bps
ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1)
RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1)
b0: 4,800bps b1: 9,600bps (default)
b2: 19,200bps b3: 38,400bps
b4: 57,600bps b5: 115,200bps
b6 ~ b13: reserved
b14: High/low bit exchange of CRC checksum (only valid in RTU mode)
b15: Switch between ASCII/RTU mode. 0 = ASCII mode (default)

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

reserved CH4 CH3 CH2 CH1

#33 H’4053

R/W

Return to default
setting;
OFFSET/GAIN
tuning
authorization

Default = H’0000. Take the setting of CH1 for example:

1. When b0 = 0, the user is allowed to tune CR#18 (OFFSET) and CR#24 (GAIN)

of CH1. When b0 = 1, the user is not allowed to tune CR#18 (OFFSET) and
CR#24 (GAIN) of CH1.

2. b1 represents whether the OFFSET/GAIN tuning registers are latched. b1 = 0

(default, latched); b1 = 1 (non-latched)

3. When b2 = 1, all settings will return to default values. (except CR#31, CR#32)

#34

H’4054

R

Firmware version

Displaying the current firmware version In hex; e.g. version 1.0A is indicated as
H’010A.

#35 ~ #48

For system use.

Symbols

: latched (when written in through RS-485 communication)

: non-latched

R: Able to read data by FROM instruction or RS-485 communication
W: Able to write data by TO instruction or RS-485 communication
LSB (Least Significant Bit): For voltage output 1

LSB

= 10V/4,000 = 2.5mV

For current output 1

LSB

= 20mA/4,000 = 5

μ

A

Explanations:

1.

CR#0: Model name. The user can read the model name from the program and see if the extension module

exists.

2.

CR#1: The working mode of the four channels in the analog input module. There are 4 modes for each channel

which can be set up separately. For example, if the user needs to set up CH1: mode 0 (b2 ~ b0 = 000); CH2:
mode 1 (b5 ~ b3 = 001), CH3: mode 2 (b8 ~ b6 = 010) and CH4: mode 3 (b11 ~ b9 = 011), CR#1 has to be set
as H’000A and the higher bits (b12 ~ b15) have to be reserved. Default value = H’0000.

3.

CR#2 ~ CR#5, CR#10 ~ CR#17, CR#22, CR#23, CR#28 and CR#29 are reserved.

4.

CR#6 ~ CR#9: The output values of CH1 ~ CH4 (range: K0 ~ K4,000; default = K0; unit: LSB)

5.

CR#18 ~ CR#21: The adjusted OFFSET value of CH1 ~ CH4 (default = K0, unit = LSB), representing the analog

output voltage or current when the output digital value = 0 after calculation. The adjustable range: -2,000 ~
+2,000.

The adjustable range of voltage: -5V ~ +5V (-2,000

LSB

~ +2,000

LSB

)

The adjustable range of current: -10mA ~ +10mA (-2,000

LSB

~ +2,000

LSB

)

6.

CR#24 ~ CR#2: The adjusted GAIN value of CH1 ~ CH4 (default = K2,000, unit = LSB), representing the analog

output voltage or current when the output digital value = 2,000 after calculation.