Delta DVP06AD-S - Manual
Delta DVP06AD-S – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
War ning
Please read this instruction carefully before use.
DO NOT tough any terminal when the power is switched on. Switch off the power before wiring.
DVP06AD-S is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device
(e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may occur.
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all
the wiring again before switching on the power.
DO NOT touch any internal circuit in 1 minute after the power is switched off.
Make sure the groud terminal
is correctly grounded in order to prevent electromagnetic interference.
Introduction
Model Explanation & Peripherals
Thank you for choosing Delta DVP series. The analog signal input module DVP06AD-S is able to receive 6
points of external analog signal inputs (both in voltage and current) and convert the signals into 14-bit
digital ones. It is able to read and write the data in the module through FROM/TO instructions given by the
program of DVP-PLC SS/SA/SX/SC/SV series MPU. There are 49 16-bit control registers in the module.
The user can select voltage or current output by wiring. Range of voltage output:
±
10V DC (resolution:
1.25mV). Range of current output:
±
20mA (resolution: 5
µ
A).
Product Profile & Outline
1. POW ER, ERROR, A/D indicator
2. DIN rail clip
3. Terminals
4. Extension unit/module mounting hole
5. Nameplate
6. Extension unit/module connection port
7. Extension unit/module fixing clip
8. DIN rail (35mm)
9. RS-485 communication port
10. Extension unit/module fixing notch
11. Power input port
3
.0
0
9
0
.0
0
3.00
25.20
60.00
3.40
1
2
12
3
4
6
8
2
5
7
10
9
11
60.00
3
.0
0
Unit: mm
12. Extension unit/module connection port
External Wiring
C H1
10 4.7 K
250
- 10V ~+ 10V
V +
I +
CO M
CH 1
100 K
C H6
10 4.7 K
250
-20m A ~ +20m A
V +
I +
CO M
CH 6
100 K
* 4
* 2
AG
AG
24+
24-
100 or less)
(
D C /D C
+ 15V
- 15V
A G
* 3
Vol t age i nput
Shieldi ng cabl e* 1
Shieldi ng cabl e* 1
Curr ent i nput
S yst em gr oundi ng
Ea rt h
C onnect ed t o
t er m inal
of the pow er module
Cover t er
DVP06AD-S
COM
V+
I+
COM
V+
I+
COM
V+
I+
COM
V+
I+
COM
V+
I+
COM
V+
I+
ENGLISH
*1: When performing analog input, p lease isolate other power wirings.
*2: When connecting to current signals, please make sure to short-circuit “V+” and “I+” terminals.
*3: Please connect the
terminal on both the power module and DVP06AD-S to the system earth point and ground the
system contact or connect it to the cover of power distribution cabinet.
*4: If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the
wiring to 0.1 ~ 0.47
µ
F 25V capacitor.
Note: DO NOT wire empty terminals
Specifications
Functions
Analog/Digital
(6A/D) module
Voltage input
Current input
Power supply voltage
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
Analog input channel
6 channels/module
Range of analog input
±10V
±20mA
Range of digital
conversion
±8,000
±4,000
Resolution
14 bits (1
LSB
=1.25mV)
13 bits (1
LSB
=5
µ
A)
Input impedance
200K
Ω
or more
250
Ω
Overall accuracy
±
0.5% when in full scale (25°C, 77°F)
±
1% when in full scale in the range of 0 ~ 55°C, 32 ~ 131°F
Response time
3ms × the number of channels
Isolation
Isolation between digital area and analog area. No isolation among channels.
Range of absolute input
±15V
±32mA
Digital data format
13 significant bits out of 16 bits are available; in 2’s complement.
Average function
Yes. Available for setting up in CR#2 ~ CR#7; range: K1 ~ K20.
Self-diagnosis
Upper and lower bound detection/channel
Communication mode
(RS-485)
ASCII/RTU mode.
Communication speed: 4,800/9,600/19,200/38,400/57,600/115,200
ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1)
RTU data format: 8-bit, even bit, 1 stop bit (8, E, 1)
RS-485 cannot be used when connected to PLC MPU in series.
When connected to
DVP-PLC MPU in series
The modules are numbered from 0 to 7 automatically by their distance from MPU.
Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/O
points.
Others
Power supply
Max. rated power
consumption
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2W, supplied by external power.
Environment
Operation/storage
Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2.
Storage: -25°C ~70°C (temperature); 5 ~ 95% (humidity).
Vibration/shock
immunity
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC
68-2-27 (TEST Ea)
Installation & Wiring
Mounting Arrangements and Wiring Notes
Control Registers
CR
#
RS-485
param eter
address
Latc hed
Register content
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
#0
H’40 00
○
R
Model name
Set by the s ystem. Data l ength: 8 bits (b7 ~ b0).
DVP06AD-S model code=H’C8.
Res erve d
CH6
CH5
CH4
CH3 CH2
CH1
#1
H’40 01
○
R/W Input mode setting
Input mode: Default=H’0000.
Mode 0: Voltage input (-10V ~ +10V)
Mode 1: Voltage input (-5V ~ +10V)
Mode 2: Current input (-12mA ~ +20mA)
Mode 3: Current input (-20mA ~ +20mA)
CR#1: The working mode of the 6 channels in the analog input module. There are 4 modes for each channel which can
be set up separately. For example, if the user needs to set up CH1: mode 0 (b2 ~ b0=00) and CH2: mode 1 (b5 ~ b3=01),
CH3: mode 2 (b8 ~ b6=10), CH4: mode 3 (b11 ~ b9=11), CH5: mode 0 (b11 ~ b9=00), CH6: mode 1 (b11 ~ b9=01), CR#1
has to be set as H’04EA and the higher bits (b12 ~ b15) have to be reserved. Default value=H’0000.
#2
H’40 02
○
R/W
CH2
CH1
#3
H’40 03
○
R/W
CH4
CH3
#4
H’40 04
○
R/W
CH1 ~ CH6
Average times setting
CH6
CH5
CR#2 ~ CR#4: Range of settings in CH1 ~ CH6: K1 ~ K20. The settings of average times of the signals at CH1 ~ CH6.
Range: K1 ~ K20. For example, if the average time at CH1 is to be set as K10 and CH2 as K18, CR#2 has to be set as
H’120A. CR#3 ~ 4 apply the same rule. The default setting of each channel=K10. Default settings of CR#2 ~ CR#4 are all
H’0A0A.
#6
H’40 06
╳
R
CH1 input average
#7
H’40 07
╳
R
CH2 input average
#8
H’40 08
╳
R
CH3 input average
#9
H’40 09
╳
R
CH4 input average
#10 H’40 0A
╳
R
CH5 input average
#11 H’40 0B
╳
R
CH6 input average
Average of input signals at CH1 ~ CH6
CR#6 ~ CR#11: The average of the signals at CH1~CH6 obtained from the settings in CR#2~CR#4. For example, if the
settings in CR#2~CR#4 is 10, the content in CR#6~CR#11 will be the average of the most recent 10 signals at CH1~CH6.
How to install DIN rail
DVP-PLC can be secured to a cabinet by using the DIN rail of
35mm in height and 7.5mm in depth. When mounting PLC to
DIN rail, be sure to use the end bracket to stop any side-to-side
movement of PLC and reduce the chance of wires being loosen.
A small retaining clip is at the bottom of PLC. To secure PLC to
DIN rail, place the clip onto the rail and gently push it up. To
remove it, pull the retaining clip down and gently remove PLC
from DIN rail, as shown in the figure.
Please install PLC in an
enclosure with sufficient
space around it to allow
heat dissipation as shown
in the figure.
DVP
M P
D
D
D
D
D > 50 mm
Wiring
2 2- 1 6AW G
< 1. 5 m m
1. Use 22-16AWG (1.5mm) single or multiple core wire on I/O wiring terminals. The
specification of the terminal is shown in the figure on the left. The PLC terminal
screws shall be tightened to 1.95 kg-cm (1.7 in-lbs).
2. DO NOT place the I/O signal wires and power supply wire in the same wiring duct.
3. Use 60/75 ºC copper wires only.
CR
#
RS-485
param eter
address
Latc hed
Register content
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
#12 H’40 0C
╳
R
CH1 input present value
#13 H’40 0D
╳
R
CH2 input present value
#14 H’40 0E
╳
R
CH3 input present value
#15 H’40 0F
╳
R
CH4 input present value
#16 H’40 10
╳
R
CH5 input present value
#17 H’40 11
╳
R
CH6 input present value
Present value of input signals at CH1 ~ CH6
#18 H’40 12
○
R/W Adjusted OFFSET value of CH1
#19 H’40 13
○
R/W Adjusted OFFSET value of CH2
#20 H’40 14
○
R/W Adjusted OFFSET value of CH3
#21 H’40 15
○
R/W Adjusted OFFSET value of CH4
#22 H’40 16
○
R/W Adjusted OFFSET value of CH5
#23 H’40 17
○
R/W Adjus ted OFFSET value of CH6
OFFSET settings at CH1 ~ CH6. Default=K0; Unit: LSB.
W hen voltage input, range: K-4,0 00
LSB
~ K4,000
LSB
.
W hen current input, range: K-4,0 00
LSB
~ K4,000
LSB
.
Please refer to this instruction sheet when setting OFFSET and
GAIN.
#24 H’40 18
○
R/W Adjusted GAIN value of CH1
#25 H’40 19
○
R/W Adjusted GAIN value of CH2
#26 H’40 1A
○
R/W Adjusted GAIN value of CH3
#27 H’40 1B
○
R/W Adjusted GAIN value of CH4
#28 H’40 1C
○
R/W Adjusted GAIN value of CH5
#29 H’40 1D
○
R/W Adjusted GAIN value of CH6
GAIN settings at CH1 ~ CH6. Default=K4,000; Unit: LSB.
W hen voltage input, range: K-3,2 00
LSB
~ K16,000
LSB
.
W hen current input, range: K-3,2 00
LSB
~ K10,400
LSB
.
Please refer to this instructi on sheet when setting OFFSET and
GAIN.
CR#18 ~ CR#29: Please note that: GAIN value – OFFSET value=+800
LSB
~ +12,000
LSB
(voltage) or +800
LSB
~ +6,400
LSB
(current) W hen GAIN – OFFSET is small (steep oblique), the resolution of input signal will be finer and variation on the
digital value will be greater. W hen GAIN – OFFSET is big (gradual oblique), the resolution of input signal will be rougher
and variation on the digital value will be smaller.
#30 H’40 1E
╳
R
Error status
Register for storing all error status.
See the table of error status for more information.
CR #30: Error status value (see the table below):
Error status
Content
b15 ~ b8
b7
b6
b5
b4
b3
b2
b1
b0
Abnormal power supply
K1 (H’1)
0
0
0
0
0
0
0
1
Incorrect mode setting
K4 (H’4)
0
0
0
0
0
1
0
0
Offs et/Gain error
K8 (H’8)
0
0
0
0
1
0
0
0
Hardware malfunction
K16 (H’10)
0
0
0
1
0
0
0
0
Abnormal digital range
K32 (H’20)
0
0
1
0
0
0
0
0
Incorrect average times setting
K64 (H’40)
0
1
0
0
0
0
0
0
Instruction error
K12 8 (H’80)
Res erve d
1
0
0
0
0
0
0
0
Note: Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors
occurring at the same time. 0=normal; 1=error
#31 H’40 1F
○
R/W Communication address setting
For setting RS-485 communication address.
Range: 01 ~ 254. Default=K1.
#32 H’40 20
○
R/W
Communication speed (baud
rate) setting
For setting up RS-485 communication speed: 4,800/ 9,600/
19,200/ 38,400/ 57,600/ 115,200bps. A SCII data format: 7-bit,
even bit, 1 stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1
stop bit (8, E, 1).
b0: 4,800 bps. b1: 9,600 bps (default).
b2: 19,200 bps. b3: 38,400 bps.
b4: 57,600 bps. b5: 115,200 bps.
b6 ~ b13: Reserved.
b14: High/low bit exchange of CRC checksum (only valid in
RTU mode).
b15: Switch between ASCII/RTU mode.
Return to default
CH6
CH5
CH4 CH3
CH2
CH1
#33 H’40 21
○
R/W
Return to default setting;
OFFSET/GAIN tuning
authorization
Take the setting of CH1 for example:
1. b0: Switch for upper/lower bound alarm on the input value for
the channel. 0=disabled; 1=enabled (default).
2. b1: OFFSET/GAIN tuning. 0=forbidden; 1=allowed (default).
3. W hen b12 ~ b15=1, all values in CH1 ~ CH6 will return to
default settings. b12 ~ b15 will return to 0 automatically after
the setting is completed.
CR for input mode, setting of average times, OFFSET value and GAIN value will be reset after returning to default settings.
#34 H’40 22
○
R
Firmware version
Displaying the current firmware version in hex, e.g. version
1.00 is indicated as H’0100.
#35 ~ #48
For system use
Symbols:
○
: Latched (when written in through RS-485 communication).
╳
: Non-latched.
R: Able to read data by FRO M instruction or RS-485 communication.
W: Able to write data by TO instruction or RS-485 communication.
LS B (Least Significant Bit): 1. For voltage input: 1
LSB
=10V/8,000=1.25mV.
2. For current input: 1
LSB
=20m A/4,000=5
µ
A.
※
CR#0 ~ CR#34: The corresponding parameter addresses H’4000 ~ H’4022 are for users to read/write data
by RS-485 communication. When using RS-485, the user has to separate the module with MPU first.
a. Function codes: 03’H (read register data); 06’H (write 1 word datum to register); 10’H (write many words
data to register).
b. Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written
by MPU through TO/DTO instruction.
Adjusting A/D Conversion Cur ve
Voltage input mode:
CR#1 mode 0:
GAIN=5V (4,000
LSB
). OFFSET=0V (0
LSB
).
CR#1 mode 1:
GAIN=6V (4,800
LSB
). OFFSET=2V (1,600
LSB
).
GAIN:
The voltage input value when the digital input value=4,000.
Range: -3,200
LSB
~ +16,000
LSB
.
OFFSET:
The voltage output value when the digital input value=0.
Range: -4,000
LSB
~ +4,000
LSB
.
+
0 0
+ 4 , 00 0
-4 ,
0
0 0
1 0 V
V o l t a g e i n p u t
- 8 ,
0
0 0
-6 V
-1 0 V
6 V
5V
2V
0
M o d e 1
M o d e 0
GA IN
OF FS E T
d
ig
it
a
lo
u
tp
u
t
GAIN - OFFSET: Range: +800
LSB
~ +12,000
LSB
.
Current input mode:
CR#1 mode 2:
GAIN=20mA (4,000
LSB
). OFFSET=4mA (800
LSB
).
CR#1 mode 3:
GAIN=20mA (4,000
LSB
). OFFSET=0mA (0
LSB
).
GAIN:
The current input value when the digital input value=+4,000.
Range: -3,200
LSB
~ +10,400
LSB
.
OFFSET:
The current input value when the digital input value=0.
Range: -4,000
LSB
~ +4,000
LSB
.
+ 4 , 00 0
cu r r e n t i n pu t
- 4 ,
0
00
-12mA
-20m A
4mA
0
M o d e 2
M ode 3
OFFSET
2 0m A
GAIN
GAIN - OFFSET: Range: +800
LSB
~ +6,400
LSB
.
The user can adjust the OFFSET/GAIN curves according to the actual needs by changing the OFFSET value
(CR#18 ~ CR#23) and GAIN value (CR#24 ~ CR#29).
注意事項
請在使用之前,詳細閱讀本使用說明書。
請勿在上電時觸摸任何端子。實施配線,務必關閉電源。
本機為開放型
(OPEN TYPE)
機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊
/
衝擊
意外之外殼配線箱內。另必須具備保護措施
(
如
:
特殊之工具或鑰匙才可打開
)
防止非維護人員操作或意外衝
擊本體,造成危險及損壞。
交流輸入電源不可連接於輸入
/
出信號端,否則可能造成嚴重的損壞,因此請在上電之前再次確認電源配線。
輸入電源切斷後,一分鐘之內,請勿觸摸內部電路。
本體上之接地端子
務必正確的接地,可提高產品抗雜訊能力。
產品簡介
說明及週邊裝置
謝謝您採用台達
DVP
系列產品。
DVP06AD-S
類比信號輸入模組可接受外部
6
點類比信號輸入(電壓或電
流皆可),將之轉換成
14
位元之數位信號。透過
DVP-PLC SS/SA/SX/SC/SV
主機程式以指令
FROM/TO
來
讀寫模組內之資料,模組內具有
49
個
CR (Control Register)
暫存器,每個暫存器為
16 bits
。
使用者可經由配線選擇電壓輸入或電流輸入。電壓輸入範圍
±10V DC (
解析度為
1.25mV)
。電流輸入範圍
±20mA (
解析度為
5
µ
A)
。
產品外觀及各部介紹
1.
電源、錯誤及運行指示燈
2. DIN
軌固定扣
3.
端子
4.
擴充機
/
擴充模組定位孔
5.
銘牌
6.
擴充機
/
擴充模組連接口
7.
擴充機
/
擴充模組固定扣
8. DIN
軌糟
(35mm)
9. RS-485
通訊口
10.
擴充機
/
擴充模組固定槽
11.
電源輸入口
3
.0
0
9
0
.0
0
3.00
25.20
60.00
3.40
1
2
12
3
4
6
8
2
5
7
10
9
11
60.00
3
.0
0
尺寸單位:
mm
12.
擴充機
/
擴充模組連接
外部配線
C H1
1 0 4 . 7 K
2 5 0
隔離線
* 1
電壓輸入
- 1 0 V ~ + 1 0 V
V +
I +
C O M
C H1
1 0 0 K
C H6
1 0 4 . 7 K
2 5 0
隔離線
* 1
電流輸入
- 2 0 m A ~ + 2 0 m A
V +
I +
C O M
C H6
1 0 0 K
* 4
* 2
A G
A G
2 4 +
2 4 -
接至電源模
組之
端
接地
(
1 0 0
)
接地阻抗
以下
D C /D C
轉換器
+1 5 V
- 1 5 V
A G
* 3
系統接地點
DVP06AD-S
C O M
V +
I +
C O M
V +
I +
C O M
V +
I +
C O M
V +
I +
C O M
V +
I +
C O M
V +
I +
繁體中文
註
1
:類比輸入請與其他電源線隔離。
註
2
:如果連接電流信號時,
V+
及
I+
端子請務必短路。
註
3
:請將電源模組之
端及
DVP06AD-S
類比信號輸入模組之
端連接到系統接地點,再將系統接點作第
三種接地或接到配電箱之機殼上。
註
4
:如果輸入電壓有漣波造成配線受雜訊干擾時請連接
0.1 ~ 0.47
µ
F 25V
之電容。
注意:空端子
請勿配線。
規格
功能規格
類比
/
數位
(6A/D)
模組
電壓輸入
(Voltage input)
電流輸入
(Current input)
電源電壓
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
類比訊號輸入通道
6
通道
/
台
類比輸入範圍
±10V
±20mA
數位轉換範圍
±8,000
±4,000
解析度
14 bits (1LSB=1.25mV)
13 bits (1LSB=5
µ
A)
輸入阻抗
200K
Ω
以上
250
Ω
總和精密度
±
0.5%
在
(25°C, 77°F)
範圍內滿刻度時。
±
1%
在
(0 ~ 55°C, 32 ~ 131°F)
範圍內滿刻度時。
響應時間
3ms ×
通道數
隔離方式
數位區與類比區有隔離,通道間未隔離。
絕對輸入範圍
±15V
±32mA
數位資料格式
16
位元二補數,最大有效位
13 bits
。
平均功能
有
(CR#2 ~ CR#7
可設定,範圍
K1 ~ K20)
自我診斷功能
上下極限偵測
/
通道
通訊模式
(RS-485)
有,包含
ASCII/RTU
模式,通訊速率可選
(4,800/9,600/19,200/38,400/57,600
/115,200)
,
ASCII
模式資料格式固定為
7 bits
、偶位元、
1 stop bit (7, E, 1)
,
RTU
模式資料格式固定為
8 bits
、偶位元、
1 stop bit (8, E, 1)
。當與
PLC
主機串接時,
RS-485
通訊無法使用。
與
DVP-PLC
主機串接說明
模組編號以靠近主機之順序自動編號由
0
到
7
,最大可連接
8
台且不佔用數位
I/O
點數。
其他規格
電源規格
額定最大消耗功率
直流
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2W,
由外部電源供應。
環境規格
操作
/
儲存環境
操作:
0
°
C ~ 55
°
C (
溫度
)
,
50 ~ 95% (
濕度
)
,污染等級
2
;
儲存:
-25
°
C ~ 70
°
C (
溫度
)
,
5 ~ 95%
(濕度)
耐振動
/
衝擊
國際標準規範
IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27
(TEST Ea)
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.