War ning

This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation &
wiring. Other detail infromation about programming and intructions is compatible with SV series; please see PLC
Application Manual. For more information about the optional peripherals, please see individual product instuction
shee or “DVP-PLC Application Manual: Special module”.

This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, humidity, electric
shock risk and vibration. Also, it is equipped with protective methods such as some special tools or keys to open the
enclosure, in order to prevent hazard to users or damage the PLC.

Do NOT connect the AC main circuit power supply to any of the input/output terminals, or it may damage the PLC.
Check all the wiring prior to power up. To prevent any electromagnetic noise, make sure the PLC is properly
grounded

. Do NOT touch terminals when power on.

Introduction

Product Profile & Outline

1

2

3

5

9

4

9

6

10

5

4

7

8

Open COM1 Cover

Communication port cover

Extension module connection port cover

I/O terminal cover

Input indicator

Function card/memory card cover

Output indicator

I/O terminals

DIN rail clip

I/O terminal No.

DIN rail (35mm)

3

1

2

6

7

1

2

5

4

8

Open COM2 cover

Mounting screw

Memory card port

Direct mounting hole

POWER/RUN/BAT.LOW/ERROR indicator

Battery socket

Extension module connection port

Function card mounting hole


ENGLISH

Removable Terminal Block

COM 2 (RS-485)

RUN / ST OP SW IT CH

VR 0

VR 1

COM 1 (RS-232)

Ba tter y

Remove RS-485

terminal

Part

Description

COM2 (RS-485)

For both master & slave modes

RUN/STOP switch

PLC RUN/STOP control

VR0

Enable M1178/corresponding value of D1178

VR1

Enable M1179/corresponding value of D1179

COM1 (RS-232)

For slave mode

Battery

Shall be changed within 1 min.

Dimension

4.6 X

2

W

W1

8

0

.0

9

0

.0

82 .2

Model

W (mm)

W1 (mm)

DVP16EH00R2/T2

113

103

DVP20EH00R2/T2

113

103

DVP32EH00R2/T2

143.5

133.5

DVP40EH00R2/T2

158.8

153.8

DVP48EH00R2/T2

174

164

DVP64EH00R2/T2

212

202

DVP80EH00R2/T2

276

266

Specifications

Model

Item

16EH00

2 20EH00

2 32EH00

2 40EH00

2 48EH00

2 64EH00

2 80EH00

2

Power supply
voltage

100 ~ 240V AC (-15% ~ 10%); 50/60Hz

±

5%

Fuse capacity

2A/250V AC

Power consumption

50VA

50VA

60VA

60VA

60VA

80VA

80VA

DC24V current
supply

500mA

500mA

500mA

500mA

500mA

500mA

500mA

Power protection

DC24V; output short-circuited

Withstand voltage

1,500V AC (Primary-Secondary); 1,500V AC (Primary-PE); 500V AC (Secondary-PE)

Insulation
resistance

> 5 M

(all I/O point-to-ground: 500V DC)

Noise immunity

ESD: 8KV Air Discharge; EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O:
250V; Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m

Earth

The diameter of grounding wire shall not be less than that of L, N terminal of the power. (When
many PLCs are in use at the same time, please make sure every PLC is properly grounded.)

Operation/storage

Operation: 0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -40 ºC ~ 70 ºC (temperature); 5 ~ 95% (humidity)

Vibration/shock
immunity

International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST
Ea)

Weight (g)

500/480

520/500

652/612

710/675

748/688

836/756

948/848

Input Point Specification

24VDC single com m on port input

Spec.

Items

Low speed

High speed (200KHz)

Note

Input wiring type

Change wiring from S/S to SINK or SOURCE

Input indicator

LED display; light on = ON, light off = OFF

Input voltage

24VDC

Off

On

X0 ~ X7, X12, X13, X16, X17, X20 ~ X47: >

18.5V DC

X10, X11, X14, X15: >

16.5V DC

Active
Level

On

Off

X0 ~ X47: <

8V DC

Response time/
noise immunity

10ms

0.5us

Input point X0 ~ X7, X10 ~ X17
can conduct 10 ~ 60ms digital
filter adjustment

Output Point Specification

Single com m on port transistor output

Spec.

Items

Low speed

High speed*

Single com m on port relay

output

Max. frequency

10KHz

200KHz

Load ON/OFF control

Output indicator

LED display; light on = ON, light off = OFF

Min. load

-

2mA/DC power supply

Working voltage

5 ~ 30VDC

250V AC, 30V DC

Insulation

Photocoupler isolation

Magnetic isolation

Current
specification

0.3A/1 point @ 40ºC

<1KHz, 0.3A/1 point @ 40°C

1KHz, 30mA/1 point @ 40°C

2A/1 point (5A/COM)

75VA (conductive), 90W

(resistive)

Off

On: 20us

Max. output delay

time

On

Off: 30us

0.2us

10ms

Over-current
protection

N/A

Mechanical life

N/A

2×10

7

times (without load)

Electrical life

N/A

1.5×10

5

times (5A 30V DC);

5×10

5

times (3A 120V AC);

3×10

4

times (5A 250V AC)

*Hi gh-speed output poi nts (Y0, Y2) are only i n DVP20EH2 and DVP32EH2; high-speed output poi nts (Y0, Y1, Y2, Y3, Y4, Y6) are
only i n DVP40EH2.

Installation & Wiring

3.1 PLC Mounting Arrangements and Wiring Notes

How to install DIN rail:

DVP-PLC can be secured to a cabinet by using the DIN rail of 35mm in height and
7.5mm in depth. When mounting PLC to DIN rail, be sure to use the end bracket to stop
any side-to-side movement of PLC and reduce the chance of wires being loosen. A small
retaining clip is at the bottom of PLC. To secure PLC to DIN rail, place the clip onto the
rail and gently push it up. To remove it, pull the retaining clip down and gently remove
PLC from DIN rail, as shown in the figure.

How to screw:

Please use M4 screw according to the dimension of the product.

D V P M P U

> 50m m

> 50mm

> 50m m

> 50m m

Please install PLC in an enclosure with sufficient space around it to allow heat
dissipation as shown in the figure.

Wiring:

To suit M3.5 screw terminals

Below 6.2

Below 6.2

1. Use O-type or Y-type terminal. See the figure in the left hand side for its

specification. PLC terminal screws should be tightened to 5 ~ 8 kg-cm (4.3 ~
6.9 in-Ibs) and please use only 60/75ºC copper conductor.

2. DO NOT wire empty terminal • . DO NOT place the input signal cable and

output power cable in the same wiring circuit.

3. DO NOT drop tiny metallic conductor into the PLC while screwing and wiring.

Tear off the sticker on the heat dissipation hole for preventing alien
substances from dropping in, to ensure normal heat dissipation of the PLC.

3.2 Wiring Notes

Power Input Wiring

The power input of DVP-EH series is AC. When operating the PLC, please make sure that:

1. The input voltage should be current and its range should be 100 ~ 240V AC. The power should be

connected to L and N terminals. Wiring AC110V or AC220V to +24V terminal or input terminal will result in
serious damage on the PLC.

2. The AC power input for PLC MPU and I/O extension modules should be ON or OFF at the same time.

3. Use wires of 1.6mm (or longer) for the grounding of PLC MPU. The power shutdown of less than 10 ms will

not affect the operation of the PLC. However, power shutdown time that is too long or the drop of power
voltage will stop the operation of the PLC and all outputs will go OFF. When the power supply turns normal
again, the PLC will automatically return to its operation. Please be aware of the latched auxiliary relays and
registers inside the PLC when programming.

AC Power Input

L

N

2.0 A

DC/DC

+5V

+24 V

24G

S/S

X0

X1

X2

100~24 0VAC

0.5A is the maximum power supply for +24V power supply output terminal. DO NOT connect other
external power supplies to this terminal. Every input terminal requires 6 ~ 7mA to be driven; e.g. the
16-point input will require approximately 100mA. Therefore, +24V cannot give output to extermal load
that is more than 400mA.

Safety Wiring

Since a PLC controls many devices, actions of any device may affect actions of other devices, and the
breakdown of any one device may cause the breakdown of the whole auto-control system and danger.
Therefore, we suggest you wire a protection circuit at the power input terminal, as shown in the figure below.

AC power supply load

Power circuit protection fuse (3A

Power indicator

Emergency stop

This button can cut off the system power supply when accidental
emergency takes place.

System circuit isolation device

The device is made of electromagnetic contactor and relay as the
switch to prevent the instability of system when the power is
intermittently supplied.

DVP-PLC (main processing unit)

Earth

M C

M C

N

L

1

1

2

3

4

5

6

7

8

G u ar d

L i m i t

M C

Power supply AC: 100 ~ 240V AC

Input Point Wiring

There are two types of DC inputs, SINK and SOURCE.

Input point loop equivalent circuit

Wiring loop

DC Signal IN

S/S

X0

Sinking

SINK

mode

(common port for current

input S/S)

24VDC

24G

X0

S/S

+24V

SINK

+5V

24G

S/ S

X0

X1

X2

+24 V

Sink Type

Input point loop equivalent circuit

Wiring loop

DC Signal IN

S/S

X0

Sourcing

SOURCE

mode

(common port for current

output S/S)

24VDC

24G

X0

S/S

+24V

SOURCE

+5V

24 G

S/S

X0

X1

X2

+24 V

Source Ty pe

Output Point Wiring

Relay (R) contact circuit wiring

Y0

RY

LED

C0

LOAD

POWER

DVP-**-**-**-R

RELAY OUTPUT

2

3

1

5

C 0

Y 0

Y 1

C 1 Y 3 Y 4 C 2 Y 6 Y 7

4

M C 1

M C 2

7

1 0

3

2

8

9

6

Flywheel diode: To extend the life span of contact

Emergency stop: Uses external switch

Fuse: Uses 5 ~ 10A fuse at the common port of output contacts to protect the output circuit.

Varistor: To reduce the interference on AC load

Empty terminal: not in use

DC power supply

Neon indicator

AC power supply

Incandescent light (resistive load)

Manually exclusive output: Uses external circuit and forms an interlock, together with the PLC internal
program, to ensure safety protection in case of any unexpected errors.

Transistor (T) contact circuit wiring

Y0

LED

C0

TRANSI STOR OUTPUT

LOAD

DVP-**-**-**-T

< 0 .5A

M C1

M C 2

2

3

1

C 0 Y 0

Y 1 C 1 Y 4 Y 5 Y 6

Y 7

5

4

5

3

4

DC power supply

Emergency stop

Circuit protection fuse

Flywheel diode + inductive load

Manually exclusive output: Uses external circuit and forms an interlock, together with the PLC internal
program, to ensure safety protection in case of any unexpected errors.

注意事項

本使用說明書僅提供電氣規格、功能規格、安裝配線部份說明,其它詳細之程式設計及指令與

SV

系列相容,

詳細說明請見

DVP-PLC

應用技術手冊【程式篇】,選購之週邊裝置詳細說明請見該產品隨機手冊或

DVP-PLC

應用技術手冊【特殊模組篇】。

本機為開放型

(OPEN TYPE)

機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊

/

衝擊

意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或意外
衝擊本體,造成危險及損壞。

交流輸入電源不可連接於輸入/出信號端,否則可能造成嚴重損壞,請在上電之前再次確認電源配線。請勿
在上電時觸摸任何端子。本體上之接地端子

務必正確的接地,可提高產品抗雜訊能力。

產品簡介

產品外觀及各部介紹

1

2

3

5

9

4

9

6

10

5

4

7

8

COM1

上蓋打開

通訊口上蓋

擴充機連接口上蓋

輸出/入端子蓋

輸入點指示燈

功能卡/記憶卡上蓋

輸出點指示燈

輸出/入端子

DIN

軌固定扣

輸入/輸出端子編號

固定

DIN

軌糟

(35mm)

3

1

2

6

7

1

2

5

4

8

COM2

上蓋開啟

機身固定螺絲

記憶卡插槽

直接固定孔

電源、運行、錯誤及電池狀態指示

電池插槽

擴充機連接口

功能卡固定孔

繁體中文

繁體中文

繁體中文

繁體中文

脫落式端子

COM 2 (RS-485)

RUN / STOP

開關

VR 0

VR 1

COM 1 (RS-232)

電池

RS-485

端子取出

COM2 (RS-485)

Master/Slave

模式兩用

RUN/STOP

開關

PLC RUN/STOP

控制

VR0

M1178

啟動

/D1178

對應值

VR1

M1179

啟動

/D1179

對應值

COM1 (RS-232)

Slave

模式使用

電池

更換電池時,必須在

1

分鐘內完成。

外觀及尺寸

4.6 X

2

W

W1

8

0

.0

9

0

.0

82 .2

W (mm)

W1 (mm)

DVP16EH00R2/T2

113

103

DVP20EH00R2/T2

113

103

DVP32EH00R2/T2

143.5

133.5

DVP40EH00R2/T2

158.8

153.8

DVP48EH00R2/T2

174

164

DVP64EH00R2/T2

212

202

DVP80EH00R2/T2

276

266

電氣規格

機種

項目

16EH00

2

20EH00

2

32EH00

2

40EH00

2

48EH00

2

64EH00

2

80EH00

2

電源電壓

100 ~ 240V AC (-15% ~ 10%); 50/60Hz

±

5%

電源保險絲容量

2A/250V AC

消耗電力

50VA

50VA

60VA

60VA

60VA

80VA

80VA

DC24V

供應電流

500mA

500mA

500mA

500mA

500mA

500mA

500mA

電源保護

DC24V

輸出具短路保護

突波電壓耐受量

1,500V AC (Primary-Secondary); 1 ,500V AC (Primary-PE); 500V AC (Secondary-PE)

絕緣阻抗

5 M

Ω以上

(

所有輸出

/

入點對地之間

500VDC)

雜訊免疫力

ESD: 8KV Air Discharge; EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O:
250V; Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m

接地

接地配線之線徑不得小於電源端

L, N

之線徑(多台

PLC

同時使用時,請務必單點接地)

操作

/

儲存環境

操作:

0°C ~55°C

(溫度),

50 ~ 95%

(濕度),污染等級

2

儲存:

-40°C ~70°C

(溫度),

5 ~ 95%

(濕度)

耐振動

/

衝擊

國際標準規範

IEC61131-2, IEC 68 -2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

重量

(

), (g)

500/480

520/500

652/612

710/675

748/688

836/756

948/848

輸入點規格

24V DC

單端共點輸入

單端共點輸入

單端共點輸入

單端共點輸入

規格

項目

低速

高速

200KHz

備註

備註

備註

備註

輸入接線型式

由端子

S/S

變換接線為

SINK

SOURCE

輸入動作指示

LED

顯示;燈亮表示為

ON

,不亮表示為

OFF

輸入信號電壓

24V DC

Off

On

X0 ~ X7, X12, X13, X16, X17, X20 ~ X47: >

18.5V DC

X10, X11, X14, X15: >

16.5V D C

動作位準

On

Off

X0~X47: <

8V DC

反應時間

/

雜訊抑制

10 ms

0.5us

輸入點

X0 ~ X7

X10 ~

X17

可作

10 ~ 60 ms

數位

濾波調整