1
DT3
Series Temperature Controller Instruction Sheet
Precaution
DANGER! Caution! Electric Shock!
1.
Do not touch the AC terminals while the power is supplied to the controller to prevent an electric shock.
2.
Make sure power is disconnected while checking the unit inside.
WARNING!
This controller is an open-type temperature controller. Make sure to evaluate any dangerous application in which a
serious human injury or serious property damage may occur.
1.
Always use recommended solder-less terminals: Fork terminal with isolation. (M3 screw, width is 6.0mm)
2.
Do not allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning.
3.
Never modify or disassemble the controller.
4.
Do not connect anything to the “No used” terminals.
5.
Make sure all wires are connected to the correct polarity of terminals.
6.
Do not install and/or use the controller in places subject to:
y
Dust or corrosive gases and liquid
y
High humidity and high radiation
y
Vibration and shock
y
High voltage and high frequency
7.
Must turn power off when wiring and changing a temperature sensor.
8.
Be sure to use compensating wires that match the thermocouple types when extending or connecting the thermocouple wires.
9.
Please use wires with resistance when extending or connecting a platinum resistance thermometer (RTD).
10. Please keep the wire as short as possible when wiring a platinum resistance thermometer (RTD) to the controller and please
route power wires as far as possible from load wires to prevent interference and induced noise.
11. This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity, dripping water,
corrosive materials, airborne dust and electric shock or vibration.
12. Please make sure power cables and signals from instruments are all installed properly before energizing the controller,
otherwise serious damage may occur.
13. Please do not touch the terminals in the controller or try to repair the controller when power is applied to prevent an electric
shock.
14. Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not touch any internal
circuit within this period.
15. Do not use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to clean the controller.
Display, LED & Pushbuttons
Odering Information
DT3 Series
DT3: Delta 3 Series Temperature Controller
Panel Size (W×H)
20: 4848 1/16 DIN W48 × H48mm
30: 7272 W72 × H72mm
40: 4896 1/8 DIN W48 × H96mm
60: 9696 1/4 DIN W96 × H96mm
1st output group selection
R: Relay Output, 250 VAC, 5A
V: Voltage Pulse Output, 12V ±10%
C: DC Current Output, 4 ~ 20 mA
L: Linear Voltage Ouptut 0 ~ 10 VDC
Power supply
A: AC 80 ~ 260 V
D: DC 24 VDC
2nd output group selection
0: None
R: Relay Outupt,250 VAC, 5A
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
2 V: Voltage Pulse Output, 12V ±10% C: DC Current Output 4 ~ 20 m A L: Linear Voltage Ouptut 0 ~ 10 VDC EVENT inputs/ CT function (optional) 1 0: None, 1: Event Input3, 2: RS-485 Communication EVENT inputs/ CT function (optional) 2 0: None, 1: Event Input2, 2: CT measure input2, 3: Retransmission Ou...
6 Initial Start-up Setting 1. When setting up DT3 for the first time, press key for more than 3 seconds till the screen display and select according to your temperature sensor type. Please be aware that a selection of wrong model would cause PV temperature display error. (Refer to the chart below)...
8 ¾ To set Retransmission to positive/negative slopes (a Retransmission board must be installed first): In 【 Initial Setting Mode 】 set the parameter, the last digit (Y) of xxxY indicates when Y=0 positive slope; when Y=1 negative slope. ¾ To adjust the lower limit of Retransmission: a 、 Make sure t...